| Plan Review Notes For Permit 20050140 |
| Permit Number |
20050140 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-05-13 09:53:48 | CODES IN EFFECT: | | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | | | | PLAN REVIEW - BUILDING | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | PLANS EXAMINER BUILDING - PX3169 | | | PLANS EXAMINER 1&2 FAMILY - SFP306 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | 1ST REVIEW | | | | | | RESULTS: DENIED | | | | | | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED | | | BELOW. | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | 1. ENGINEERED DESIGN PRESSURES FOR SGD OPENINGS ARE | | | CALCULATED AT 68.95/-68.95. DESIGN UTILIZES NOA | | | 19-0603.03. | | | NOA SUBMITTED IS 17-1011.18 WHICH DOES NOT MEET THE | | | DESIGN PRESSURES SPECIFIED BY THE ENGINEER. | | | | | | 2. SUBMIT NOA 19-0603.03 FOR REVIEW. SPECIFY DOOR | | | HEIGHT WITH OR WITHOUT INTERLOCK SYSTEM. ALSO SPECIFY | | | SILL HEIGHT REQUIRED. | | | | | | FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE | | | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED | | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. | | | SPECIFICALLY, PROVIDE DOOR SUBMITTALS. |
|