| 2020-06-11 09:29:09 | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 20050119 |
| | ADD: 651 OKEECHOBEE BLVD. / SUITE: 811 |
| | CONT: PULY USA |
| | TEL: 561-358-9468 |
| | E-MAIL: [email protected] |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | DATE: THURS. JUNE 11TH/ 2020 |
| | ACTION: DENIED |
| | |
| | 1) 2ND REQUEST. IN THE 2ND VERSION OF PLANS IT LOOKS |
| | LIKE THERE HAS BEEN A SIGNTURE LINE ADDED IN THE |
| | TITLEBLOCK FOR THE QUALIFIER OF THE COMPANY BUT NO |
| | SIGNATURE. |
| | CERTIFICATION BY CONTRACTOR. THE CONTRACTOR (QUALIFIER) |
| | THAT CREATED / DRAWN THE SET OF PLANS WILL NEED TO |
| | IDENTIFY THEMSELVES AS THE AUTHOR OF THE PLANS. PLEASE |
| | PRINT YOUR NAME, SIGN YOUR NAME AND LICENSE NUMBER FOR |
| | THE TRADE YOU ARE LICENSED IN AND PLANS DRAWN. |
| | 107.3.4.3 CERTIFICATION BY CONTRACTOR. |
| | |
| | 2) 2ND REQUEST. THE SUBMITTED 3 FLOOR PLANS SHOW THE |
| | REMOVAL OF EXISTING FLOORING AND NEW FLOOR TILE BEING |
| | INSTALLED WITH SOUND UNDERLAYMENT. IN VERSION 2 OF THE |
| | FLOOR PLANS THE DESCRIPTION OF THE FLOOR UNDERLAYMENT |
| | TO BE USED WITH THE MARBLE/ TILE FLOOR IS PROTECTO |
| | WHISPERMAT HW. PLEASE NOTE WHISPER MAT HW IS TO BE |
| | INSTALLED WITH WOOD FLOORING, IT HAS NEVER BEEN TESTED |
| | FOR INSTALATION WITH EITHER TILE OR MARBLE FLOORING. |
| | THE ONLY TESTING WE HAVE SEEN FOR THE WHISPER MAT HW IS |
| | ALSO FOR 8 INCH SLABS NOT THE REQUIRED 6 INCH SLABS. |
| | |
| | THE CITY IS IN RECEIPTOF TESTING FOR WHISPER MAT CS FOR |
| | TILE (7.3 MM) OR 5/16 INCH TILE, WE ALSO USE THIS SAME |
| | REPORT FOR MARBLE 5/16 INCH OR THICKER MARBLE. IF YOU |
| | WITH TO USE THIS PRODUCT PLEASE CHANGE THE LISTED |
| | PRODUCT IN THE PLANS. WE CAN UPLOAD THE PRODUCT SHEETS |
| | DIRECTLY INTO PROJECT DOX. |
| | |
| | NO TESTING REPORTS WERE SUBMITTED. |
| | FLOOR INSULATION (FBC-B 2017) |
| | FOR TILE, STONE, MARBLE, VINYL AND WOOD FLOORING ALL |
| | NEED TO HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR |
| | ASSEMBLIES TO THE FOLLOWING STANDARDS AND MEET THE |
| | QUALIFICATIONS LISTED UNDER EACH OF THE STANDARDS FOR A |
| | 6 INCH CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING: |
| | PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH: |
| | |
| | TYPE I AND II BUILDINGS |
| | 2A) FBC-B 2017 1207.3 STRUCTURE-BORNE SOUND. |
| | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| | |
| | 2B) FBC-B 2017 1207.2 AIR-BORNE SOUND. |
| | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| | SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| | PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| | CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| | E 90. |
| | |
| | 2C) FLAME SPREAD- FBC-B 2017 603.1. EXCEPTION 2. |
| | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. |
| | |
| | FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS |
| | A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL |
| | MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A |
| | MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. |
| | 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | PLEASE NOTE WE ARE WORKING FROM HOME IF YOU WOULD LIKE |
| | TO CONTACT ME, MY CELL NUMBER IS 561-718-9724. |
| | JAMES A. WITMER BN, PX, SFP, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |
| | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6717 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |
| | |
| | |
| | |