Plan Review Notes
Plan Review Notes For Permit 20050095
Permit Number 20050095
Review Stop P
Sequence Number 2
Notes
Date Text
2020-06-24 10:07:292ND REVIEW FBC-2017 PLUMBING
 PERMIT- 20050095
 6/24/2020
  
 CODES IN EFFECT:
  
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
 THE 1ST REVIEW COMMENTS LISTED BELOW WERE NOT
 COMPLETELY ADDRESSED. THE COMMENTS WILL BE MARKED AS
 PASSED OR FAILED. PLEASE NOTE ADDITIONAL REMARKS FOR
 FAILED COMMENTS.
  
 1) FAILED. SHEET P-000: PROVIDE PLUMBING FIXTURE
 CALCULATIONS IN ACCORDANCE WITH TABLE 403.3 FBC P.
 PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND
 PROVIDED NUMBER OF FIXTURES. THE ARCHITECT OF RECORD'S
 RESPONSE WAS TO SEE PLUMBING. THE SCHEDULE WAS NOT
 PROVIDED ON PLUMBING PLANS.
  
 2) FAILED. PROVIDE ENLARGED DIMENSIONED TOILET ROOM
 FLOOR PLANS AND DETAILS SHOWING COMPLIANCE WITH THE
 FBC-17 ACCESSIBILITY. THE ENLARGED DRAWINGS SHALL SHOW:
 A) FAILED- NEW PLANS SHEET A-205: CLEAR FLOOR SPACE
 DIMENSIONS FOR THE WATER CLOSETS- SECTION 604.3 FBC
 ACC. THE PLAN SHOWS A FLOOR MOUNTED WATER CLOSET WHICH
 REQUIRES A 59" DEEP X60" WIDE CLEAR FLOOR SPACE- FIGURE
 604.8.1.1 & SECTION 604.8.1.7 FBC ACC.
 B) FAILED. CLEAR FLOOR SPACE DIMENSIONS FOR THE
 LAVATORIES- SECTION 606.2. BECAUSE DIMENSIONS HAVE NOT
 BEEN PROVIDED FOR THE TOILET COMPARTMENTS. THE
 LOCATIONS OF THE LAVS CANNOIT BE APPROVED AT THIS TIME-
 SECTION 604.8.1.6 FBC ACC.
 C) FAILED. TOILET COMPARTMENT WIDTH AND LENGTH
 MEASUREMENTS- SECTIONS 604.2-604.8. FBC ACC, AND
 SECTION 405.3.1 FBC P. DIMENSIONS NOT PROVIDED.
 D) FAILED TOILET COMPARTMENT DOOR WIDTHS, DOOR SWINGS,
 AND WHEELCHAIR APPROACHES- SECTION 604.8.1.2 &
 604.8.1.3 FBC ACC. SHEET A-201- PLEASE REFER TO FIGURES
 404.2.4 (B), (C), & (J): PROVIDE THE WIDTH DIMENSIONS
 OF THE BOH CORRIDOR AND CLEARANCE MEASUREMENT
 BETWEENTHE DRINKING FOUNTAINS AND RESTROOM 103 DOORWAY.
 E) PASSED. TURNING SPACE DIAMETERS- SECTION 304.3.
 F) FAILED. CENTERLINES OF THE WATER CLOSETS FROM THE
 SIDE WALLS OR PARTITIONS- SECTION 604.2. SHEET A-201
 SHOWS 1'10-7/8" TO CENTERLINE OF THE WATER CLOSET- SEE
 SECTION 604.2: MINIMUM 16" AND MAXIMUM 18" TO CENTELINE
 FROM ADJACENT WALL. THE CORRECT DIMENSION IS SHOWN ON
 A-205.
  
 3) FAILED. PROVIDE TOILET ROOM ELEVATION DRAWINGS
 INDICATING:
 A) HEIGHTS OF THE WATER CLOSET SEATS FROM THE FINISHED
 FLOORS- SECTION 604.4.
 B) HEIGHTS OF THE FRONT RIM OF THE LAVATORY FROM THE
 FINISHED FLOOR- SECTION 606.3
 C) KNEE AND TOE CLEARANCES FOR THE LAVATORIES- SECTION
 306.
 D) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB
 BARS- SECTION 604.5
 E) LOCATIONS OF THE WATER CLOSET FLUSH CONTROLS-
 SECTION 604.6.
 F) LOCATIONS, CLEARANCES, AND MOUNTING HEIGHTS FOR
 PAPER DISPENSERS- SECTION 604.7
 G) HEIGHTS OF THE MIRROR FROM THE FINISHED FLOOR TO THE
 BOTTOM OF THE REFLECTIVE SURFACES- SECTION 603.3.
 PLEASE NOTE THE AOR RESPONSE WAS TO SEE SHEETS A-605
 AND G-003, HOWEVER A-605 DOES NOT SHOW ANY MOUNTING
 HEIGHT MEASUREMENTS. G-003 SHOWS A WALL HUNG WATER
 CLOSET, HOWEVER A FLOOR MOUNTED HAS BEEN SPECIFIED.
 CONCERNING THE GRAB BARS AT THE TOILET PAPER DISPENSER,
 REFER TO SECTION 60. 3 AND FIGURE 609.3 AND VERIFY
 COMPLIANCE.
  
 4) FAILED. P-000 & P-101: REFER TO SECTION 211.1.2 FBC
 ACC, AND TABLE 404.3 FBC P. NO FEWER THAN TWO DRINKING
 FOUNTAINS SHALL BE PROVIDED. ONE DRINKING FOUNTAIN
 SHALL COMPLY WITH SECTIONS 602.1 & 602.6, AND ONE SHALL
 COMPLY WITH 602.7. SECTION 602.7 REQUIRES THAT SPOUT
 OUTLETS FOR STANDING PERSONS SHALL BE 38 INCHES MINIMUM
 AND 43 INCHES MAXIMUM FROM THE FINISHED FLOOR. REVISE
 THE PLANS TO SHOW COMPLIANCE AND PROVIDE THESE DETAILS:
 A) THE CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR
 FORWARD WHEELCHAIR APPROACH- SECTION 602.2. FBC ACC.
 B) KNEE AND TOE CLEARANCES- SECTION 306.
 C) SPOUT HEIGHT AND SPOUT LOCATION- SECTION 602.4 AND
 602.5.
 THE AOR RESPONSE WAS TO SEE DETAIL 2/A-606, HOWEVER NO
 CLEARANCES OR DIMENSIONS ARE PROVIDED ON THE DETAIL.
  
 5) PASSED. P101: THE CONDENSATE FROM THE FCU'S SHALL
 NOT DRAIN INTO THE CITY SANITARY SEWER PER SEC.90-126
 WPB CODE OR ORDINANCES. PLEASE PROVIDE AN APPROVED
 LOCATION SUCH AS THE STORM DRAIN OR PERMEABLE GROUND.
  
 6) PASSED. P101: NOTE #6 REFERS TO CIVIL PLANS FOR ROOF
 DRAINAGE AND STORM DRAINAGE CONTINUATIONS. PLEASE
 PROVIDE THE CIVIL PLANS.
  
 7) FAILED. P001 & P101: ROOF DRAINAGE SYSTEM:
 A) PROVIDE CALCULATIONS FOR SIZING OF THE SYSTEM-
 SECTION 1106.1- 1106.5 FBC P.
 B) VERIFY PROPOSED ROOF DESIGN IS IN COMPLIANCE WITH
 SECTION 1101.7 FOR MAX PONDING DEPTH LOAD ETC.
 C) SHOW THE LOCATIONS OF EMERGENCY ROOF DRAINS OR
 OVERFLOW SCUPPERS, AND PROVIDE SIZING CALCULATIONS -
 SECTIONS 1108.1- 1108.3. SEE SECTION 1503.4 FBC B FOR
 SCUPPER DESIGN.
 D) IDENTIFY THE MAKE AND MODEL OF THE ROOF DRAIN SHOWN
 IN THE DETAIL AND SUBMIT MANUFACTURER?S SPECIFICATIONS-
 SECTIONS 1102.6 &1105.1.
 COMMENTS 6A-6D WERE NOT ADDRESSED
 REFER TO FIGURE 1106.5 FBC P: THE RAINFALL RATE IS
 CALCULATED AT 5"/HR.
  
 8) NEW COMMENT- SHEET P101: PROVIDE A BACKFLOW
 PREVENTER FOR THE WATER SUPPLY LINE TO THE REMOTE
 CHILLER- SECTION 608.3 FBC P.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  