| 2020-06-24 10:07:29 | 2ND REVIEW FBC-2017 PLUMBING |
| | PERMIT- 20050095 |
| | 6/24/2020 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | THE 1ST REVIEW COMMENTS LISTED BELOW WERE NOT |
| | COMPLETELY ADDRESSED. THE COMMENTS WILL BE MARKED AS |
| | PASSED OR FAILED. PLEASE NOTE ADDITIONAL REMARKS FOR |
| | FAILED COMMENTS. |
| | |
| | 1) FAILED. SHEET P-000: PROVIDE PLUMBING FIXTURE |
| | CALCULATIONS IN ACCORDANCE WITH TABLE 403.3 FBC P. |
| | PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND |
| | PROVIDED NUMBER OF FIXTURES. THE ARCHITECT OF RECORD'S |
| | RESPONSE WAS TO SEE PLUMBING. THE SCHEDULE WAS NOT |
| | PROVIDED ON PLUMBING PLANS. |
| | |
| | 2) FAILED. PROVIDE ENLARGED DIMENSIONED TOILET ROOM |
| | FLOOR PLANS AND DETAILS SHOWING COMPLIANCE WITH THE |
| | FBC-17 ACCESSIBILITY. THE ENLARGED DRAWINGS SHALL SHOW: |
| | A) FAILED- NEW PLANS SHEET A-205: CLEAR FLOOR SPACE |
| | DIMENSIONS FOR THE WATER CLOSETS- SECTION 604.3 FBC |
| | ACC. THE PLAN SHOWS A FLOOR MOUNTED WATER CLOSET WHICH |
| | REQUIRES A 59" DEEP X60" WIDE CLEAR FLOOR SPACE- FIGURE |
| | 604.8.1.1 & SECTION 604.8.1.7 FBC ACC. |
| | B) FAILED. CLEAR FLOOR SPACE DIMENSIONS FOR THE |
| | LAVATORIES- SECTION 606.2. BECAUSE DIMENSIONS HAVE NOT |
| | BEEN PROVIDED FOR THE TOILET COMPARTMENTS. THE |
| | LOCATIONS OF THE LAVS CANNOIT BE APPROVED AT THIS TIME- |
| | SECTION 604.8.1.6 FBC ACC. |
| | C) FAILED. TOILET COMPARTMENT WIDTH AND LENGTH |
| | MEASUREMENTS- SECTIONS 604.2-604.8. FBC ACC, AND |
| | SECTION 405.3.1 FBC P. DIMENSIONS NOT PROVIDED. |
| | D) FAILED TOILET COMPARTMENT DOOR WIDTHS, DOOR SWINGS, |
| | AND WHEELCHAIR APPROACHES- SECTION 604.8.1.2 & |
| | 604.8.1.3 FBC ACC. SHEET A-201- PLEASE REFER TO FIGURES |
| | 404.2.4 (B), (C), & (J): PROVIDE THE WIDTH DIMENSIONS |
| | OF THE BOH CORRIDOR AND CLEARANCE MEASUREMENT |
| | BETWEENTHE DRINKING FOUNTAINS AND RESTROOM 103 DOORWAY. |
| | E) PASSED. TURNING SPACE DIAMETERS- SECTION 304.3. |
| | F) FAILED. CENTERLINES OF THE WATER CLOSETS FROM THE |
| | SIDE WALLS OR PARTITIONS- SECTION 604.2. SHEET A-201 |
| | SHOWS 1'10-7/8" TO CENTERLINE OF THE WATER CLOSET- SEE |
| | SECTION 604.2: MINIMUM 16" AND MAXIMUM 18" TO CENTELINE |
| | FROM ADJACENT WALL. THE CORRECT DIMENSION IS SHOWN ON |
| | A-205. |
| | |
| | 3) FAILED. PROVIDE TOILET ROOM ELEVATION DRAWINGS |
| | INDICATING: |
| | A) HEIGHTS OF THE WATER CLOSET SEATS FROM THE FINISHED |
| | FLOORS- SECTION 604.4. |
| | B) HEIGHTS OF THE FRONT RIM OF THE LAVATORY FROM THE |
| | FINISHED FLOOR- SECTION 606.3 |
| | C) KNEE AND TOE CLEARANCES FOR THE LAVATORIES- SECTION |
| | 306. |
| | D) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB |
| | BARS- SECTION 604.5 |
| | E) LOCATIONS OF THE WATER CLOSET FLUSH CONTROLS- |
| | SECTION 604.6. |
| | F) LOCATIONS, CLEARANCES, AND MOUNTING HEIGHTS FOR |
| | PAPER DISPENSERS- SECTION 604.7 |
| | G) HEIGHTS OF THE MIRROR FROM THE FINISHED FLOOR TO THE |
| | BOTTOM OF THE REFLECTIVE SURFACES- SECTION 603.3. |
| | PLEASE NOTE THE AOR RESPONSE WAS TO SEE SHEETS A-605 |
| | AND G-003, HOWEVER A-605 DOES NOT SHOW ANY MOUNTING |
| | HEIGHT MEASUREMENTS. G-003 SHOWS A WALL HUNG WATER |
| | CLOSET, HOWEVER A FLOOR MOUNTED HAS BEEN SPECIFIED. |
| | CONCERNING THE GRAB BARS AT THE TOILET PAPER DISPENSER, |
| | REFER TO SECTION 60. 3 AND FIGURE 609.3 AND VERIFY |
| | COMPLIANCE. |
| | |
| | 4) FAILED. P-000 & P-101: REFER TO SECTION 211.1.2 FBC |
| | ACC, AND TABLE 404.3 FBC P. NO FEWER THAN TWO DRINKING |
| | FOUNTAINS SHALL BE PROVIDED. ONE DRINKING FOUNTAIN |
| | SHALL COMPLY WITH SECTIONS 602.1 & 602.6, AND ONE SHALL |
| | COMPLY WITH 602.7. SECTION 602.7 REQUIRES THAT SPOUT |
| | OUTLETS FOR STANDING PERSONS SHALL BE 38 INCHES MINIMUM |
| | AND 43 INCHES MAXIMUM FROM THE FINISHED FLOOR. REVISE |
| | THE PLANS TO SHOW COMPLIANCE AND PROVIDE THESE DETAILS: |
| | A) THE CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR |
| | FORWARD WHEELCHAIR APPROACH- SECTION 602.2. FBC ACC. |
| | B) KNEE AND TOE CLEARANCES- SECTION 306. |
| | C) SPOUT HEIGHT AND SPOUT LOCATION- SECTION 602.4 AND |
| | 602.5. |
| | THE AOR RESPONSE WAS TO SEE DETAIL 2/A-606, HOWEVER NO |
| | CLEARANCES OR DIMENSIONS ARE PROVIDED ON THE DETAIL. |
| | |
| | 5) PASSED. P101: THE CONDENSATE FROM THE FCU'S SHALL |
| | NOT DRAIN INTO THE CITY SANITARY SEWER PER SEC.90-126 |
| | WPB CODE OR ORDINANCES. PLEASE PROVIDE AN APPROVED |
| | LOCATION SUCH AS THE STORM DRAIN OR PERMEABLE GROUND. |
| | |
| | 6) PASSED. P101: NOTE #6 REFERS TO CIVIL PLANS FOR ROOF |
| | DRAINAGE AND STORM DRAINAGE CONTINUATIONS. PLEASE |
| | PROVIDE THE CIVIL PLANS. |
| | |
| | 7) FAILED. P001 & P101: ROOF DRAINAGE SYSTEM: |
| | A) PROVIDE CALCULATIONS FOR SIZING OF THE SYSTEM- |
| | SECTION 1106.1- 1106.5 FBC P. |
| | B) VERIFY PROPOSED ROOF DESIGN IS IN COMPLIANCE WITH |
| | SECTION 1101.7 FOR MAX PONDING DEPTH LOAD ETC. |
| | C) SHOW THE LOCATIONS OF EMERGENCY ROOF DRAINS OR |
| | OVERFLOW SCUPPERS, AND PROVIDE SIZING CALCULATIONS - |
| | SECTIONS 1108.1- 1108.3. SEE SECTION 1503.4 FBC B FOR |
| | SCUPPER DESIGN. |
| | D) IDENTIFY THE MAKE AND MODEL OF THE ROOF DRAIN SHOWN |
| | IN THE DETAIL AND SUBMIT MANUFACTURER?S SPECIFICATIONS- |
| | SECTIONS 1102.6 &1105.1. |
| | COMMENTS 6A-6D WERE NOT ADDRESSED |
| | REFER TO FIGURE 1106.5 FBC P: THE RAINFALL RATE IS |
| | CALCULATED AT 5"/HR. |
| | |
| | 8) NEW COMMENT- SHEET P101: PROVIDE A BACKFLOW |
| | PREVENTER FOR THE WATER SUPPLY LINE TO THE REMOTE |
| | CHILLER- SECTION 608.3 FBC P. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |