| Date |
Text |
| 2020-06-16 14:12:59 | PETER E VALENTI |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6673 |
| | |
| | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| | FBC B = FBC BUILDING |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | FBC R = FBC RESIDENTIAL |
| | FBC M = FBC MECHANICAL |
| | |
| | 2ND BUILDING REVIEW DENIED: |
| | |
| | 1) FBC B/WPB AMENDMENTS 109.3, THE BUILDING VALUATION |
| | IS TOO LOW. PROVIDE DETAILED COST BREAK DOWN INCLUDING: |
| | BUILDING, ROOFING, MECHANICAL, ELECTRIC & PLUMBING. |
| | 2) FBC B 107, PROVIDE CITY PLACE APPROVAL STAMP ON |
| | PLANS. |
| | 3) OK |
| | 4) OK WITH PROVISO: 107.3.4.1 & 1803.5.2, PROVIDE THE |
| | GEO-TECH REPORT WITH ENGINEER'S APPROVAL AND DESIGNER |
| | OF RECORD'S REVIEW STAMP PRIOR TO CANOPY FOOTING STEEL |
| | PLACEMENT. |
| | 5) FBC EC C401.2, PROVIDE ENERGY CODE |
| | DOCUMENTS/CALCULATIONS. (THE BUILDING ENERGY COSTSHALL |
| | BE EQUAL TO OR LESS THAN 85 PERCENT OF THE STANDARD |
| | REFERENCEDESIGN BUILDING) |
| | 6) OK WITH PROVISO: |
| | AWS D1.1 CLAUSE 3.1: AT TIME OF INSPECTION PLEASE |
| | PROVIDE A WELD PROCEDURE SPECIFICATION; THE W.P.S. |
| | SPECIFIES THE REQUIRED ESSENTIAL VARIABLES INCLUDING: |
| | BASE MATERIALS, JOINTS, PROCESS, AND FILLER METALS TO |
| | BE USED. |
| | AWS D1.1 CLAUSE 4.15: AT TIME OF INSPECTION PLEASE |
| | PROVIDE A WELDER PERFORMANCE QUALIFICATION RECORD; THE |
| | W.P.Q.R. PROVIDES INFORMATION WHICH CAN BE USED TO |
| | VERIFY THE WELDER?S QUALIFICATION AND CERTIFICATION AS |
| | IT RELATES TO THE WELDING REQUIREMENTS OF THE PROJECT. |
| | 7) OK |
| | 8) FBC B 107.3.4.1, PROVIDE ALL DEFERRED SUBMITTALS |
| | INCLUDING PRODUCT APPROVALS ON PLANS. THESE PRODUCT |
| | APPROVALS SHALL BE REVIEW STAMPED BY THE DESIGNER OF |
| | RECORD. |
| | 9) FBC B 107, IDENTIFY GLAZING/ MULLIONS. PLEASE |
| | IDENTIFY ON THEPRODUCT APPROVAL BEFORE SUBMITTING TO |
| | DESIGNER OFRECORD AND BEFORE SUBMISSION TO THE BUILDING |
| | DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE |
| | IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF |
| | GLAZING,MULLION SIZE, LENGTH IF UNREINFORCED OR |
| | REINFORCED INFORMATION IF REQUIRED, ATTACHMENTS AND |
| | ASSOCIATE |
| | PRESSURES FOR EACH OPENING SIZE. 2017 FBC-B 1405.13.1 |
| | INSTALLATION. WINDOWS AND DOORS SHALL BE INSTALLED IN |
| | ACCORDANCE WITH APPROVED MANUFACTURER'S |
| | INSTRUCTIONS.FASTENER SIZE AND SPACING SHALL BE |
| | PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED |
| | BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS. |
| | 10) OK |
| | 11A) OK |
| | 11B) OK |
| | 11C) FBC B 107.2.1.2, THE PLANS ARE INCOMPLETE. ON PAGE |
| | A-604 SEVERAL DETAILS REFERENCE PAGE A-907. THERE IS NO |
| | PAGE A-907. |
| | 11D) OK |
| | 12) FBC B 107, FBC A 505.2 & 505.3, PROVIDE THE |
| | ACCESSIBLE PARKING SPACE AND ACCESS AISLE STRIPING AND |
| | MEASUREMENT DETAILS ON PAGE A-200 FOR THE RECHARGEABLE |
| | STATIONS. |
| | 13) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. A |
| | THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE |
| | THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED |
| | DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE |
| | MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS |
| | AND INFORMATION LACKING UNDER THE PRIOR REVIEW. |
| | |
| | |
| | |