Plan Review Notes
Plan Review Notes For Permit 20050095
Permit Number 20050095
Review Stop B
Sequence Number 2
Notes
Date Text
2020-06-16 14:12:59PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
  
 2ND BUILDING REVIEW DENIED:
  
 1) FBC B/WPB AMENDMENTS 109.3, THE BUILDING VALUATION
 IS TOO LOW. PROVIDE DETAILED COST BREAK DOWN INCLUDING:
 BUILDING, ROOFING, MECHANICAL, ELECTRIC & PLUMBING.
 2) FBC B 107, PROVIDE CITY PLACE APPROVAL STAMP ON
 PLANS.
 3) OK
 4) OK WITH PROVISO: 107.3.4.1 & 1803.5.2, PROVIDE THE
 GEO-TECH REPORT WITH ENGINEER'S APPROVAL AND DESIGNER
 OF RECORD'S REVIEW STAMP PRIOR TO CANOPY FOOTING STEEL
 PLACEMENT.
 5) FBC EC C401.2, PROVIDE ENERGY CODE
 DOCUMENTS/CALCULATIONS. (THE BUILDING ENERGY COSTSHALL
 BE EQUAL TO OR LESS THAN 85 PERCENT OF THE STANDARD
 REFERENCEDESIGN BUILDING)
 6) OK WITH PROVISO:
 AWS D1.1 CLAUSE 3.1: AT TIME OF INSPECTION PLEASE
 PROVIDE A WELD PROCEDURE SPECIFICATION; THE W.P.S.
 SPECIFIES THE REQUIRED ESSENTIAL VARIABLES INCLUDING:
 BASE MATERIALS, JOINTS, PROCESS, AND FILLER METALS TO
 BE USED.
 AWS D1.1 CLAUSE 4.15: AT TIME OF INSPECTION PLEASE
 PROVIDE A WELDER PERFORMANCE QUALIFICATION RECORD; THE
 W.P.Q.R. PROVIDES INFORMATION WHICH CAN BE USED TO
 VERIFY THE WELDER?S QUALIFICATION AND CERTIFICATION AS
 IT RELATES TO THE WELDING REQUIREMENTS OF THE PROJECT.
 7) OK
 8) FBC B 107.3.4.1, PROVIDE ALL DEFERRED SUBMITTALS
 INCLUDING PRODUCT APPROVALS ON PLANS. THESE PRODUCT
 APPROVALS SHALL BE REVIEW STAMPED BY THE DESIGNER OF
 RECORD.
 9) FBC B 107, IDENTIFY GLAZING/ MULLIONS. PLEASE
 IDENTIFY ON THEPRODUCT APPROVAL BEFORE SUBMITTING TO
 DESIGNER OFRECORD AND BEFORE SUBMISSION TO THE BUILDING
 DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE
 IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF
 GLAZING,MULLION SIZE, LENGTH IF UNREINFORCED OR
 REINFORCED INFORMATION IF REQUIRED, ATTACHMENTS AND
 ASSOCIATE
 PRESSURES FOR EACH OPENING SIZE. 2017 FBC-B 1405.13.1
 INSTALLATION. WINDOWS AND DOORS SHALL BE INSTALLED IN
 ACCORDANCE WITH APPROVED MANUFACTURER'S
 INSTRUCTIONS.FASTENER SIZE AND SPACING SHALL BE
 PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED
 BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS.
 10) OK
 11A) OK
 11B) OK
 11C) FBC B 107.2.1.2, THE PLANS ARE INCOMPLETE. ON PAGE
 A-604 SEVERAL DETAILS REFERENCE PAGE A-907. THERE IS NO
 PAGE A-907.
 11D) OK
 12) FBC B 107, FBC A 505.2 & 505.3, PROVIDE THE
 ACCESSIBLE PARKING SPACE AND ACCESS AISLE STRIPING AND
 MEASUREMENT DETAILS ON PAGE A-200 FOR THE RECHARGEABLE
 STATIONS.
 13) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. A
 THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
  
  