| Date |
Text |
| 2020-06-04 16:11:01 | 1ST REVIEW FBC-2017 PLUMBING |
| | PERMIT- 20050095 |
| | 6/4/2020 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET P-000: PROVIDE PLUMBING FIXTURE CALCULATIONS |
| | IN ACCORDANCE WITH TABLE 403.3 FBC P. PROVIDE A |
| | SCHEDULE THAT INDICATES THE REQUIRED AND PROVIDED |
| | NUMBER OF FIXTURES. |
| | |
| | 2) PROVIDE ENLARGED DIMENSIONED TOILET ROOM FLOOR PLANS |
| | AND DETAILS SHOWING COMPLIANCE WITH THE FBC-17 |
| | ACCESSIBILITY. THE ENLARGED DRAWINGS SHALL SHOW: |
| | A) CLEAR FLOOR SPACE DIMENSIONS FOR THE WATER CLOSETS- |
| | SECTION 604.3 FBC ACC. |
| | B) CLEAR FLOOR SPACE DIMENSIONS FOR THE LAVATORIES- |
| | SECTION 606.2. |
| | C) TOILET COMPARTMENT WIDTH AND LENGTH MEASUREMENTS- |
| | SECTIONS 604.2-604.8. FBC ACC, AND SECTION 405.3.1 FBC |
| | P. |
| | D) TOILET COMPARTMENT DOOR WIDTHS, DOOR SWINGS, AND |
| | WHEELCHAIR APPROACHES- SECTION 604.8.1.2 & 604.8.1.3 |
| | FBC ACC. |
| | E) TURNING SPACE DIAMETERS- SECTION 304.3. |
| | F) CENTERLINES OF THE WATER CLOSETS FROM THE SIDE WALLS |
| | OR PARTITIONS- SECTION 604.2. |
| | |
| | 3) PROVIDE TOILET ROOM ELEVATION DRAWINGS INDICATING: |
| | A) HEIGHTS OF THE WATER CLOSET SEATS FROM THE FINISHED |
| | FLOORS- SECTION 604.4. |
| | B) HEIGHTS OF THE FRONT RIM OF THE LAVATORY FROM THE |
| | FINISHED FLOOR- SECTION 606.3 |
| | C) KNEE AND TOE CLEARANCES FOR THE LAVATORIES- SECTION |
| | 306. |
| | D) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB |
| | BARS- SECTION 604.5 |
| | E) LOCATIONS OF THE WATER CLOSET FLUSH CONTROLS- |
| | SECTION 604.6. |
| | F) LOCATIONS, CLEARANCES, AND MOUNTING HEIGHTS FOR |
| | PAPER DISPENSERS- SECTION 604.7 |
| | G) HEIGHTS OF THE MIRROR FROM THE FINISHED FLOOR TO THE |
| | BOTTOM OF THE REFLECTIVE SURFACES- SECTION 603.3. |
| | |
| | 4) P-000 & P-101: REFER TO SECTION 211.1.2 FBC ACC, AND |
| | TABLE 404.3 FBC P. NO FEWER THAN TWO DRINKING FOUNTAINS |
| | SHALL BE PROVIDED. ONE DRINKING FOUNTAIN SHALL COMPLY |
| | WITH SECTIONS 602.1 ? 602.6, AND ONE SHALL COMPLY WITH |
| | 602.7. SECTION 602.7 REQUIRES THAT SPOUT OUTLETS FOR |
| | STANDING PERSONS SHALL BE 38 INCHES MINIMUM AND 43 |
| | INCHES MAXIMUM FROM THE FINISHED FLOOR. REVISE THE |
| | PLANS TO SHOW COMPLIAN E AND PROVIDE THESE DETAILS: |
| | A) THE CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR |
| | FORWARD WHEELCHAIR APPROACH- SECTION 602.2. FBC ACC. |
| | B) KNEE AND TOE CLEARANCES- SECTION 306. |
| | C) SPOUT HEIGHT AND SPOUT LOCATION- SECTION 602.4 AND |
| | 602.5. |
| | |
| | 5) P101: THE CONDENSATE FROM THE FCU'S SHALL NOT DRAIN |
| | INTO THE CITY SANITARY SEWER PER SEC.90-126 WPB CODE OR |
| | ORDINANCES. PLEASE PROVIDE AN APPROVED LOCATION SUCH AS |
| | THE STORM DRAIN OR PERMEABLE GROUND. |
| | |
| | 6) P101: NOTE #6 REFERS TO CIVIL PLANS FOR ROOF |
| | DRAINAGE AND STORM DRAINAGE CONTINUATIONS. PLEASE |
| | PROVIDE THE CIVIL PLANS. |
| | |
| | 7) P001 & P101: ROOF DRAINAGE SYSTEM: |
| | A) PROVIDE CALCULATIONS FOR SIZING OF THE SYSTEM- |
| | SECTION 1106.1- 1106.5 FBC P. |
| | B) VERIFY PROPOSED ROOF DESIGN IS IN COMPLIANCE WITH |
| | SECTION 1101.7 FOR MAX PONDING DEPTH LOAD ETC. |
| | C) SHOW THE LOCATIONS OF EMERGENCY ROOF DRAINS OR |
| | OVERFLOW SCUPPERS, AND PROVIDE SIZING CALCULATIONS - |
| | SECTIONS 1108.1- 1108.3. SEE SECTION 1503.4 FBC B FOR |
| | SCUPPER DESIGN. |
| | D) IDENTIFY THE MAKE AND MODEL OF THE ROOF DRAIN SHOWN |
| | IN THE DETAIL AND SUBMIT MANUFACTURER?S SPECIFICATIONS- |
| | SECTIONS 1102.6 &1105.1. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |