| 2020-05-11 13:44:43 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT-20050095 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET M-301- PLEASE PROVIDE OUTSIDE AIR CALCULATIONS |
| | FOR EACH ROOM. FBC M TABLE 403.3.1.1 |
| | |
| | 2) PROVIDE ENERGY CALCULATIONS AND MANUAL J |
| | CALCULATIONS. FBC EC 107.2.1 |
| | |
| | 3) PROVIDE SPECIFICATION SHEETS FOR FCU-1, FCU-2, CRU-1 |
| | AND EF-1. FBC FS 107.2.1 |
| | |
| | 4) PLEASE PROVIDE RATING OF TENANT SEPARATION WALL. IF |
| | IT IS A RATED WALL, PLEASE SHOW CODE COMPLIANT DAMPERS |
| | FOR THE FRESH AIR AND EXHAUST AIR DUCTS WHERE THEY |
| | PENETRATE THIS WALL. FBC FS 107.2.1 |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| | UPDATED. |
| | |
| | |