| 2020-05-11 14:04:23 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) SHEET FP 101 - THERE IS NO INDICATIONS OF FIRE |
| | SPRINKLER PROTECTION UNDER THE CANOPY WHERE VEHICLES |
| | ARE PROPOSED TO BE STORED. |
| | |
| | PER NFPA 13, |
| | |
| | CHAPTER 4 GENERAL REQUIREMENTS |
| | 4.1 LEVEL OF PROTECTION. A BUILDING, WHERE PROTECTED BY |
| | AN |
| | AUTOMATIC SPRINKLER SYSTEM INSTALLATION, SHALL BE |
| | PROVIDED WITH |
| | SPRINKLERS IN ALL AREAS EXCEPT WHERE SPECIFIC SECTIONS |
| | OF THIS |
| | STANDARD PERMIT THE OMISSION OF SPRINKLERS. |
| | |
| | FIRE SPRINKLER PROTECTION IS REQUIRED. PLEASE CORRECT. |
| | |
| | |
| | |
| | 2) SHEET M 101 - CONNECTING THE A/C OUTSIDE AIR AT |
| | EXISTING POINTS1 & 4 IS INDICATED; HOWEVER, THERE IS NO |
| | INDICATION OF REQUIRED FIRE DAMPERS AT THE TENANT WALL |
| | EITHER PROPOSED OR NEW. |
| | |
| | PER NFPA 101, CHAPTER 38, NEW BUSINESS |
| | |
| | 38.5.2 HEATING, VENTILATING, AND AIR-CONDITIONING. |
| | HEATING, |
| | VENTILATING, AND AIR-CONDITIONING EQUIPMENT SHALL |
| | COMPLY WITH THE |
| | PROVISIONS OF SECTION 9.2. |
| | |
| | NFPA 101, CH 9 |
| | |
| | 9.2 HEATING, VENTILATING, AND AIR-CONDITIONING. |
| | 9.2.1 AIR-CONDITIONING, HEATING, VENTILATION DUCTWORK, |
| | AND RELATED EQUIPMENT. |
| | AIR-CONDITIONING, HEATING, VENTILATING DUCTWORK AND |
| | RELATED EQUIPMENT |
| | SHALL BE IN ACCORDANCE WITH NFPA 90A, |
| | STANDARD FOR THE INSTALLATION OF AIR-CONDITIONING AND |
| | VENTILATING |
| | SYSTEMS, OR NFPA 90B, STANDARD FOR THE INSTALLATION OF |
| | WARM AIR |
| | HEATING AND AIR-CONDITIONING SYSTEMS, AS APPLICABLE, |
| | UNLESS SUCH |
| | INSTALLATIONS ARE APPROVED EXISTING INSTALLATIONS, |
| | WHICH SHALL BE |
| | PERMITTED TO BE CONTINUED IN SERVICE. |
| | |
| | NFPA 90A |
| | |
| | 5.3* PENETRATIONS ? PROTECTION OF OPENINGS. |
| | 5.3.1 FIRE-RATED WALLS AND PARTITIONS. |
| | 5.3.1.1* APPROVED FIRE DAMPERS SHALL BE PROVIDED WHERE |
| | AIR |
| | DUCTS PENETRATE OR TERMINATE AT OPENINGS IN WALLS OR |
| | PARTITIONS |
| | REQUIRED TO HAVE A FIRE RESISTANCE RATING OF 2 HOURS OR |
| | MORE. |
| | 5.3.1.1.1* FIRE DAMPERS SHALL NOT BE REQUIRED WHERE |
| | OTHER |
| | OPENINGS THROUGH THE WALL ARE NOT REQUIRED TO BE |
| | PROTECTED. |
| | 5.3.1.2 APPROVED FIRE DAMPERS SHALL BE PROVIDED IN ALL |
| | AIR |
| | TRANSFER OPENINGS IN PARTITIONS THAT ARE REQUIRED TO |
| | HAVE A FIRE |
| | RESISTANCE RATING AND IN WHICH OTHER OPENINGS ARE |
| | REQUIRED TO |
| | BE PROTECTED. |
| | |
| | PLEASE REVIEW AND PROVIDE DETAILS |
| | |
| | |
| | |
| | 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |