Plan Review Notes
Plan Review Notes For Permit 20050095
Permit Number 20050095
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2020-05-11 14:04:23THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET FP 101 - THERE IS NO INDICATIONS OF FIRE
 SPRINKLER PROTECTION UNDER THE CANOPY WHERE VEHICLES
 ARE PROPOSED TO BE STORED.
  
 PER NFPA 13,
  
 CHAPTER 4 GENERAL REQUIREMENTS
 4.1 LEVEL OF PROTECTION. A BUILDING, WHERE PROTECTED BY
 AN
 AUTOMATIC SPRINKLER SYSTEM INSTALLATION, SHALL BE
 PROVIDED WITH
 SPRINKLERS IN ALL AREAS EXCEPT WHERE SPECIFIC SECTIONS
 OF THIS
 STANDARD PERMIT THE OMISSION OF SPRINKLERS.
  
 FIRE SPRINKLER PROTECTION IS REQUIRED. PLEASE CORRECT.
  
  
  
 2) SHEET M 101 - CONNECTING THE A/C OUTSIDE AIR AT
 EXISTING POINTS1 & 4 IS INDICATED; HOWEVER, THERE IS NO
 INDICATION OF REQUIRED FIRE DAMPERS AT THE TENANT WALL
 EITHER PROPOSED OR NEW.
  
 PER NFPA 101, CHAPTER 38, NEW BUSINESS
  
 38.5.2 HEATING, VENTILATING, AND AIR-CONDITIONING.
 HEATING,
 VENTILATING, AND AIR-CONDITIONING EQUIPMENT SHALL
 COMPLY WITH THE
 PROVISIONS OF SECTION 9.2.
  
 NFPA 101, CH 9
  
 9.2 HEATING, VENTILATING, AND AIR-CONDITIONING.
 9.2.1 AIR-CONDITIONING, HEATING, VENTILATION DUCTWORK,
 AND RELATED EQUIPMENT.
 AIR-CONDITIONING, HEATING, VENTILATING DUCTWORK AND
 RELATED EQUIPMENT
 SHALL BE IN ACCORDANCE WITH NFPA 90A,
 STANDARD FOR THE INSTALLATION OF AIR-CONDITIONING AND
 VENTILATING
 SYSTEMS, OR NFPA 90B, STANDARD FOR THE INSTALLATION OF
 WARM AIR
 HEATING AND AIR-CONDITIONING SYSTEMS, AS APPLICABLE,
 UNLESS SUCH
 INSTALLATIONS ARE APPROVED EXISTING INSTALLATIONS,
 WHICH SHALL BE
 PERMITTED TO BE CONTINUED IN SERVICE.
  
 NFPA 90A
  
 5.3* PENETRATIONS ? PROTECTION OF OPENINGS.
 5.3.1 FIRE-RATED WALLS AND PARTITIONS.
 5.3.1.1* APPROVED FIRE DAMPERS SHALL BE PROVIDED WHERE
 AIR
 DUCTS PENETRATE OR TERMINATE AT OPENINGS IN WALLS OR
 PARTITIONS
 REQUIRED TO HAVE A FIRE RESISTANCE RATING OF 2 HOURS OR
 MORE.
 5.3.1.1.1* FIRE DAMPERS SHALL NOT BE REQUIRED WHERE
 OTHER
 OPENINGS THROUGH THE WALL ARE NOT REQUIRED TO BE
 PROTECTED.
 5.3.1.2 APPROVED FIRE DAMPERS SHALL BE PROVIDED IN ALL
 AIR
 TRANSFER OPENINGS IN PARTITIONS THAT ARE REQUIRED TO
 HAVE A FIRE
 RESISTANCE RATING AND IN WHICH OTHER OPENINGS ARE
 REQUIRED TO
 BE PROTECTED.
  
 PLEASE REVIEW AND PROVIDE DETAILS
  
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  