| 2020-05-19 10:31:22 | REVIEWED BY JERRY SMITH. |
| | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH |
| | EDITION |
| | FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION |
| | NFPA 54 = NATIONAL FUEL GAS CODE |
| | NFPA 58 = LIQUIFIED PETROLEUM GAS CODE |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | 20050077 2300 TECUMSEH CIR |
| | |
| | 1ST REVIEW |
| | |
| | GAS COMMENTS: DENIED |
| | 1. A REVIEW OF CITY RECORDS FAILED TO SHOW ANY |
| | PERMITTED GAS WORK AT THIS ADDRESS. PER WPB FBC SECTION |
| | 105, THE PERMIT APPLICATION SHALL INCLUDE THE EXISTING |
| | SYSTEM IN ITS? ENTIRETY. A GAS PLAN PROVIDING COMPLETE |
| | PLANS, APPLIANCE/ EQUIPMENT SPECIFICATIONS AND GAS |
| | RISER THAT REFLECT THE ENTIRE SCOPE OF EXISTING GAS |
| | WORK AS WELL AS THE UNDERGROUND TANK REPLACEMENT. PER |
| | WPB FBC 110.2.1, A TEST OF THE EXISTING SYSTEM SHALL BE |
| | REQUIRED PRIOR TO ISSUANCE OF PERMIT; EXISTING WORK |
| | WHICH IS CONCEALED MAY BE REQUIRED TO BE EXPOSED. CALL |
| | 561-805-6692 FOR FURTHER INFORMATION. PER WPB FBC |
| | 109.4, APPLICATION IS SUBJECT TO PENALTY FEES IN |
| | ADDITION TO THE REGULAR PERMIT FEES. |
| | 2. THE FOLLOWING COMMENTS REGARDING THE TANK SHALL BE |
| | ADDRESSED |
| | A. SHALL BE ANCHORED PER NFPA 58 SEC.3-2.2.7 (H). |
| | SUBMIT DETAILS ON SIZE AND QUANTITY OF AUGERS AND SIZE, |
| | LENGTH AND QUANTITY OF STRAPS |
| | B. CATHODIC PROTECTION SYSTEM SHALL BE REQUIRED PER |
| | NFPA 58 SECS. 5.2.1.11, 6.6.6.1 (I) AND SHALL BE |
| | MONITORED PER NFPA 58 SEC.6.6.6.1 (J). SUBMIT DETAILS |
| | ON THE TYPE OF CATHODIC PROTECTION, SIZE (LBS) & NUMBER |
| | OF MAGNESIUM BAG(S), SIZE & TYPE OF ANODE CABLE. |
| | |
| | END OF COMMENTS. |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | ALL PLANS TO BE SIGNED AND SEALED BY THE DESIGNER AS |
| | REQUIRED BY FAC AND FS. |
| | |
| | |