Plan Review Notes
Plan Review Notes For Permit 20050077
Permit Number 20050077
Review Stop G
Sequence Number 1
Notes
Date Text
2020-05-19 10:31:22REVIEWED BY JERRY SMITH.
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 NFPA 54 = NATIONAL FUEL GAS CODE
 NFPA 58 = LIQUIFIED PETROLEUM GAS CODE
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 20050077 2300 TECUMSEH CIR
  
 1ST REVIEW
  
 GAS COMMENTS: DENIED
 1. A REVIEW OF CITY RECORDS FAILED TO SHOW ANY
 PERMITTED GAS WORK AT THIS ADDRESS. PER WPB FBC SECTION
 105, THE PERMIT APPLICATION SHALL INCLUDE THE EXISTING
 SYSTEM IN ITS? ENTIRETY. A GAS PLAN PROVIDING COMPLETE
 PLANS, APPLIANCE/ EQUIPMENT SPECIFICATIONS AND GAS
 RISER THAT REFLECT THE ENTIRE SCOPE OF EXISTING GAS
 WORK AS WELL AS THE UNDERGROUND TANK REPLACEMENT. PER
 WPB FBC 110.2.1, A TEST OF THE EXISTING SYSTEM SHALL BE
 REQUIRED PRIOR TO ISSUANCE OF PERMIT; EXISTING WORK
 WHICH IS CONCEALED MAY BE REQUIRED TO BE EXPOSED. CALL
 561-805-6692 FOR FURTHER INFORMATION. PER WPB FBC
 109.4, APPLICATION IS SUBJECT TO PENALTY FEES IN
 ADDITION TO THE REGULAR PERMIT FEES.
 2. THE FOLLOWING COMMENTS REGARDING THE TANK SHALL BE
 ADDRESSED
 A. SHALL BE ANCHORED PER NFPA 58 SEC.3-2.2.7 (H).
 SUBMIT DETAILS ON SIZE AND QUANTITY OF AUGERS AND SIZE,
 LENGTH AND QUANTITY OF STRAPS
 B. CATHODIC PROTECTION SYSTEM SHALL BE REQUIRED PER
 NFPA 58 SECS. 5.2.1.11, 6.6.6.1 (I) AND SHALL BE
 MONITORED PER NFPA 58 SEC.6.6.6.1 (J). SUBMIT DETAILS
 ON THE TYPE OF CATHODIC PROTECTION, SIZE (LBS) & NUMBER
 OF MAGNESIUM BAG(S), SIZE & TYPE OF ANODE CABLE.
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
 ALL PLANS TO BE SIGNED AND SEALED BY THE DESIGNER AS
 REQUIRED BY FAC AND FS.
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-246-0882 MOBILE
  
 20050077 2300 TECUMSEH CIR
  
  
  
  
  