| 2020-09-15 11:50:17 | 20050060 1791 PALM BEACH LAKES BLVD # W113 |
| | |
| | PLUMBING COMMENTS: APPROVED |
| | |
| | PROVISOS/CLARIFICATIONS: SEE APPROVED PLAN P-100 |
| | |
| | 1. PER WPB FBC 107.2.1 AND WPB FBC 107.3.4.1, PROVIDE |
| | AS A DEFERRED SUBMITTAL, A SLAB REPAIR DETAIL FOR |
| | REVIEW AND ONCE APPROVED HAVE TWO (2) COPIES AT THE JOB |
| | SITE PRIOR TO THE FIRST INSPECTION. SHOW THE WIDTH OF |
| | THE REPAIR, THE MINIMUM THICKNESS OF THE CONCRETE TO BE |
| | REPLACED, AND THE PSI OF THE CONCRETE. SHOW THE SIZE |
| | AND LENGTH OF THE DOWELS, THE MINIMUM EMBEDMENT INTO |
| | THE EXISTING SLAB, THE ANCHORING MATERIAL FOR THE |
| | DOWELS AND THE SPACING OF THE DOWELS ON CENTER. THE |
| | REPAIR SHALL ALSO INCLUDE TERMITE TREATMENT OF THE SOIL |
| | AND THE REQUIRED VAPOR BARRIER OVER WELL COMPACTED |
| | SOIL. A COPY OF THE TERMITE CERTIFICATE SHALL BE ONSITE |
| | FOR THE FINAL INSPECTION. PROCEED AT YOUR OWN RISK. |
| | 2. PER FBC PL 608.3, A LEAD FREE BACKFLOW PREVENTER |
| | SHALL BE PROVIDED IN-LINE AT THE CONNECTION FOR THE |
| | WATER COOLER |
| | 3. PER FBC PL 504.2, PROVIDE VACUUM RELIEF VALVE, NOT |
| | VACUUM BREAKER AT COLD WATER TO WATER HEATER |
| | |
| | PROVISOS/CLARIFICATIONS: SEE REDLINED A-203 |
| | |
| | 1. A-203/DETAIL 9: PER FBC 1210.2.2 AND FBC PL 310.3, |
| | THE FIBERGLASS PANEL IS REQUIRED AT THE MOP BASIN |
| | 2. THE CENTERLINE OF THE WATER CLOSET SHALL BE 16 |
| | INCHES MINIMUM TO 18 INCHES MAXIMUM FROM THE SIDE WALL |
| | OR PARTITION PER FBC ACC 604.2 |
| | 3. TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND |
| | SHALL BE 7 INCHES MINIMUM AND 9 INCHES MAXIMUM IN FRONT |
| | OF THE WATER CLOSET MEASURED TO THE CENTERLINE OF THE |
| | DISPENSER. THE OUTLET OF THE DISPENSER SHALL BE 15 |
| | INCHES MINIMUM AND 48 INCHES MAXIMUM ABOVE THE FINISH |
| | FLOOR AND SHALL NOT BE LOCATED BEHIND GRAB BARS PER FBC |
| | ACC 604.8. |
| | 4. THE SEAT HEIGHT OF A WATER CLOSET ABOVE THE FINISH |
| | FLOOR SHALL BE 17 INCHES MINIMUM AND 19 INCHES MAXIMUM |
| | MEASURED TO THE TOP OF THE SEAT. SEATS SHALL NOT BE |
| | SPRUNG TO RETURN TO A LIFTED POSITION PER FBC ACC |
| | 604.4. |
| | 5. PER FBC ACC 609.4, GRAB BARS SHALL BE INSTALLED IN A |
| | HORIZONTAL POSITION, 33 INCHES MINIMUM AND 36 INCHES |
| | MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF |
| | THE GRIPPING SURFACE PER FBC ACC 609.4 |
| | 6. MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS |
| | SHALL BE INSTALLED WITH THE BOTTOM EDGE OF THE |
| | REFLECTING SURFACE 40 INCHES MAXIMUM ABOVE THE FINISH |
| | FLOOR OR GROUND PER FBC ACC 603.3 |
| | |