2020-08-13 14:25:13CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 20050060 1791 PALM BEACH LAKES BLVD # W113
  
 1ST REVIEW
 PLUMBING COMMENTS:
  
 I. A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS
 REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW
 PROCESS BUT IS TYPICALLY ADDRESSED ON THE ARCHITECTURAL
 PLANS. ANY COMMENTS CONCERNING THESE REQUIREMENTS MUST
 BE SATISFACTORILY ADDRESSED PRIOR TO A PLUMBING REVIEW
 APPROVAL.
  
 II. THIS IS AN ALTERATION AS DESCRIBED IN FBC
 DEFINITIONS. EXISTING TOILET ROOM TO REMAIN SHALL
 COMPLY WITH ALL PROVISIONS OF THE 2017 FLORIDA BUILDING
 CODES INCLUDING BUT NOT LIMITED TO THE ACCESSIBILITY
 REQUIREMENTS AND WALL FINISHES AS WELL AS THE
 REQUIREMENTS OF THE 2017 WEST PALM BEACH AMENDMENTS TO
 THE FLORIDA BUILDING CODE.
  
 1. REGARDING P-100 PLUMBING PLAN, PER WPB FBC 107.2.1,
 THE PLUMBING FIXTURE SCHEDULE FOR THE EXISTING TOILET
 ROOM SHALL BE AVAILABLE FOR REVIEW AND SHOW COMPLIANCE
 WITH THE 2017 FLORIDA BUILDING CODES. DO NOT CROSS OUT,
 BUT NOTE AS EXISTING IF THEY ARE COMPLIANT, OTHERWISE
 SPECIFY COMPLIANT FIXTURES.
 2. REGARDING P-100 PLUMBING PLAN, PER WPB FBC 107.2.1,
 THE WATER RISER DIAGRAM SHALL REFLECT THE NOTE
 REQUIRING THE WATER SUPPLY CONNECTION TO THE WATER
 COOLER. IF THE CONNECTION IS TO BE INTEGRATED WITH THE
 EXISTING PIPING THEN THE EXISTING PIPING SHALL BE
 SHOWN.
 3. REGARDING P-100 PLUMBING PLAN, DOES THE WATER COOLER
 HAVE A DRAIN? IS IT GOING TO PROVIDE FILTERED WATER TO
 THE END USER? WILL IT PROVIDE HOT WATER AND CHILLED
 COLD WATER? PER WPB FBC 107.2.1, PROVIDE A
 MANUFACTURER'S SPECIFICATION/INSTALLATION MANUAL FOR
 THE WATER COOLER.
 4. REGARDING P-100 PLUMBING PLAN, THE AO SMITH DEL 6
 ELECTRIC WATER HEATER IS A BOTTOM FED WATER HEATER AND
 REQUIRES A VACUUM RELIEF VALVE IN THE COLD WATER SUPPLY
 PER FBC PL 504.2. ADDITIONALLY, IS THE CHECK VALVE IN
 THE COLD WATER LINE NECESSARY? THERE APPARENTLY IS NO
 RECIRCULATING HOT WATER AND THERE IS THE REQUIRED
 THERMAL EXPANSION PROTECTION IN PLACE. PLEASE CLARIFY.
 5. REGARDING P-100 PLUMBING PLAN, PROVIDE DETAIL FOR
 THE WATER HEATER SUPPORT BRACKET AND ANCHORS PER WPB
 FBC 107.2.1.
 6. PER FBC PL 606.1(5), FULL-OPEN VALVES SHALL BE
 INSTALLED ON THE TOP OF EVERY WATER DOWN-FEED PIPE IN
 OCCUPANCIES OTHER THAN ONE- AND TWO-FAMILY RESIDENTIAL
 OCCUPANCIES.
 7. REGARDING THE MOP SINK AND THE EXISTING TOILET ROOM,
 PER WPB 107.2.1, WALLS AND PARTITIONS WITHIN 2 FEET OF
 SERVICE SINKS, URINALS AND WATER CLOSETS SHALL HAVE A
 SMOOTH, HARD, NONABSORBENT SURFACE, TO A HEIGHT OF NOT
 LESS THAN 4 FEET ABOVE THE FLOOR, AND EXCEPT FOR
 STRUCTURAL ELEMENTS, THE MATERIALS USED IN SUCH WALLS
 SHALL BE OF A TYPE THAT IS NOT ADVERSELY AFFECTED BY
 MOISTURE.
  
 III. PER WPB 107.2.1, PROVIDE DETAILS FOR THE
 ACCESSIBLE PLUMBING FIXTURES IN THE EXISTING BATHROOM
 AND FOR THE NEW ACCESSIBLE DRINKING FOUNTAIN(S).
  
 A. THE WATER CLOSET SHALL BE POSITIONED WITH A WALL OR
 PARTITION TO THE REAR AND TO ONE SIDE. THE CENTERLINE
 OF THE WATER CLOSET SHALL BE 16 INCHES MINIMUM TO 18
 INCHES MAXIMUM FROM THE SIDE WALL OR PARTITION PER FBC
 ACC 604.2
 B. CLEARANCE AROUND A WATER CLOSET SHALL BE 60 INCHES
 MINIMUM MEASURED PERPENDICULAR FROM THE SIDE WALL AND
 56 INCHES MINIMUM MEASURED PERPENDICULAR FROM THE REAR
 WALL PER FBC ACC 604.3.1
 C. THE SIDE WALL GRAB BAR SHALL BE 42 INCHES LONG
 MINIMUM, LOCATED 12 INCHES (305 MM) MAXIMUM FROM THE
 REAR WALL AND EXTENDING 54 INCHES MINIMUM FROM THE REAR
 WALL PER FBC ACC 604.5.1
 D. THE REAR WALL GRAB BAR SHALL BE 36 INCHES LONG
 MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER
 CLOSET 12 INCHES MINIMUM ON ONE SIDE AND 24 INCHES
 MINIMUM ON THE OTHER SIDE PER FBC ACC 604.5.2
 E. FLUSH CONTROLS SHALL BE HAND OPERATED OR AUTOMATIC.
 HAND OPERATED FLUSH CONTROLS SHALL COMPLY WITH 309.
 FLUSH CONTROLS SHALL BE LOCATED ON THE OPEN SIDE OF THE
 WATER CLOSET PER FBC ACC 604.6
 F. TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES MINIMUM AND 9 INCHES MAXIMUM IN FRONT
 OF THE WATER CLOSET MEASURED TO THE CENTERLINE OF THE
 DISPENSER. THE OUTLET OF THE DISPENSER SHALL BE 15
 INCHES MINIMUM AND 48 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR AND SHALL NOT BE LOCATED BEHIND GRAB BARS PER FBC
 ACC 604.8.
 G. THE SEAT HEIGHT OF A WATER CLOSET ABOVE THE FINISH
 FLOOR SHALL BE 17 INCHES (430 MM) MINIMUM AND 19 INCHES
 (485 MM) MAXIMUM MEASURED TO THE TOP OF THE SEAT. SEATS
 SHALL NOT BE SPRUNG TO RETURN TO A LIFTED POSITION PER
 FBC ACC 604.4.
 H. PER FBC ACC 609.4, GRAB BARS SHALL BE INSTALLED IN A
 HORIZONTAL POSITION, 33 INCHES MINIMUM AND 36 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP (NOT
 THE CENTER) OF THE GRIPPING SURFACE,
 I. LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE
 FRONT OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34
 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR GROUND PER FBC
 ACC 606.3, ADDITIONALLY SHOW TOE AND KNEE CLEARANCE AS
 REQUIRED BY FBC ACC 306.2 AND 306.3
 J. UNITS SHALL HAVE A CLEAR FLOOR OR GROUND SPACE
 COMPLYING WITH 305 POSITIONED FOR A FORWARD APPROACH
 AND CENTERED ON THE UNIT. KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED PER FBC ACC 602.2
 K. MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS
 SHALL BE INSTALLED WITH THE BOTTOM EDGE OF THE
 REFLECTING SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE
 THE FINISH FLOOR OR GROUND. MIRRORS NOT LOCATED ABOVE
 LAVATORIES OR COUNTERTOPS SHALL BE INSTALLED WITH THE
 BOTTOM EDGE OF THE REFLECTING SURFACE 35 INCHES (890
 MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
 L. DRINKING FOUNTAIN SHALL COMPLY WITH FBC ACC 306 KNEE
 AND TOE CLEARANCE, 307 PROTRUDING OBJECTS, 309 OPERABLE
 PARTS, 602.4 SPOUT HEIGHT, 602.5 SPOUT LOCATION 602.6
 WATER FLOW AND 602.7 DRINKING FOUNTAIN FOR STANDING
 PERSON
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
 ALL PLANS TO BE DIGITALLY SIGNED AND SEALED BY THE
 DESIGNER IN ACCORDANCE WITH FAC AND FS.
  
 A COMPREHENSIVE REVIEW COULD NOT BE ACCOMPLISHED AT
 THIS TIME. PLEASE RESUBMIT CLEARLY LEGIBLE PLANS AND A
 RESPONSE NARRATIVE ADDRESSING THE PLUMBING COMMENTS
 FROM THE FIRST REVIEW.
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER