2020-08-04 09:34:03CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 NFPA 54 = NATIONAL FUEL GAS CODE
 NFPA 58 = LIQUIFIED PETROLEUM GAS CODE
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 20050053 1321 ALPHA ST
  
 A GAS GRILL IS SHOWN ON 021 G-1.2 SITE DETAILS. A GAS
 PLAN HAS NOT BEEN INCLUDED IN THIS SUBMITTAL PACKAGE. A
 GAS PLAN REVIEW HAS NOT BEEN PERFORMED AT THIS TIME. A
 SEPARATE GAS PERMIT AND PLANS WILL BE REQUIRED FOR A
 CONTRACTOR TO PERFORM THE RELATED WORK. PROVIDE
 COMPLETE PLANS, APPLIANCE/ EQUIPMENT SPECIFICATIONS AND
 GAS RISER THAT REFLECT THE ENTIRE SCOPE OF GAS WORK TO
 BE DONE. WPB AMEND. TO FBC SEC. 107.2.1.
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER THE
 FBC-R, SEC. G2404.3.
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER FBC-FUEL
 GAS SEC. 301.3.
 A SEPARATE PERMIT AND PLANS ARE REQUIRED FOR THE GAS
 INSTALLATION OR MODIFICATION OF SYSTEM.
  
  
 1ST REVIEW
 PLUMBING COMMENTS: DENIED
  
 1. PE DIGITAL SIGNATURES FOR PLUMBING AND ELECTRICAL
 DRAWINGS ARE NOT VALID; PER THE WPB AMENDMENTS TO THE
 FBC, EACH SHEET OF PLAN IS REQUIRED TO BE SIGNED AND
 SEALED BY THE PERSON RESPONSIBLE FOR THE DESIGN. A
 DIGITAL PLAN REQUIRES A DIGITAL SIGNATURE WITH THE
 PROPER THIRD PARTY VERIFICATION. THE DIGITAL SIGNATURE
 MUST INCLUDE THE STATEMENT "SIGNED AND SEALED" AS PER
 FAC 61G15-23.004. PROVIDE CORRECTION. WPB FBC 107.1; FS
 471/481
  
 2. PER WPB FBC 107.2.1, PROVIDE PLAN SHEET P6.1
 REFERENCED ON PLAN SHEET P1.0 TO SHOW HOSE BIB
 LOCATIONS AND PROVIDE A WATER RISER DIAGRAM.
  
  
 A COMPREHENSIVE REVIEW COULD NOT BE ACCOMPLISHED AT
 THIS TIME. PLEASE RESUBMIT CLEARLY LEGIBLE PLANS AND A
 RESPONSE NARRATIVE ADDRESSING THE PLUMBING COMMENTS
 FROM THE FIRST REVIEW.
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 ALL PLANS TO BE DIGITALLY SIGNED AND SEALED BY THE
 DESIGNER IN ACCORDANCE WITH FAC AND FS.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-246-0882 MOBILE
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved