Plan Review Notes
Plan Review Notes For Permit 20050041
Permit Number 20050041
Review Stop P-IRRIGATE
Sequence Number 1
Notes
Date Text
2020-05-20 06:46:59REVIEWED BY JERRY SMITH:
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 20050041 609 8TH ST
  
  
 1ST REVIEW
 PLUMBING COMMENTS: DENIED
 1. PROVIDE AN EQUIPMENT SCHEDULE ON THE PLAN INDICATING
 THE MAKE AND MODEL OF THE PUMP PER WPB FBC 107.2.1.
 2. WELL SUPPLIED IRRIGATION SYSTEM SHALL NOT IN ANY WAY
 BE CONNECTED TO THE POTABLE WATER SYSTEM. PER WPB FBC
 107.2.1, PROVIDE DETAIL AND INSTRUCTION FOR REMOVAL OF
 BACKFLOW DEVICE AND CAPPING OF POTABLE WATER SYSTEM,
 PHYSICALLY SEPARATING THE TWO SYSTEMS AND ELIMINATING
 ANY POSSIBLE CROSS CONNECTION AS REQUIRED BY FBC PL
 608.1.
 3. THE TEXT IN NOTE 12 ON THE PUMP DETAIL IS OBSCURED.
 PER WPB FBC 107.2.1, CLARIFY.
  
 ADDITIONAL COMMENTS
 A SEPARATE PERMIT MAY BE REQUIRED FOR THE WELL
 A SEPARATE ELECTRICAL PERMIT MAY BE REQUIRED FOR THE
 PUMP
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
 ALL PLANS TO BE SIGNED AND SEALED BY THE DESIGNER AS
 REQUIRED BY FAC AND FS.
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-246-0882 MOBILE
  
 20050041 609 8TH ST
  
  