| | 20050033 500 @ CLEMATIS ST |
| | |
| | 2ND REVIEW |
| | PLUMBING COMMENTS: DENIED |
| | |
| | ORIGINAL COMMENT: |
| | 1. PLAN SHEET L2.03 INDICATES AN EXISTING CONTROLLER |
| | FOR THE SYSTEM. PLAN SHEET L2.12 SECTION 2.14 APPEARS |
| | TO REQUIRE A NEW CONTROLLER WITH SPECIFIC REQUIREMENTS. |
| | PER WPB FBC 107.2.1, CLARIFY. |
| | |
| | RESPONSE: |
| | A NEW METER, BACKFLOW PREVENTOR AND CONTROLLER HAVE |
| | BEEN SPECIFIED FOR THIS BLOCK. SEE L2.03 FOR LOCATION. |
| | |
| | NEW COMMENTS: |
| | 1. PLAN SHEET L2.03 ONLY INDICATES EXISTING METER |
| | BACKFLOW PREVENTOR AND CONTROLLER TO BE ABANDONED. |
| | THERE IS NO INDICATION OF ANY NEW METER, BACKFLOW |
| | PREVENTOR AND CONTROLLER ON ANY PLAN SHEET FOR 500 |
| | BLOCK. ADDITIONALLY I SEE NO CONNECTION POINT FOR |
| | SERVICE TO THE SYSTEM. PER WPB FBC 107.2.1, PROVIDE ON |
| | PLANS THE LOCATION OF THE NEW METER, BACKFLOW PREVENTOR |
| | AND CONTROLLER, AS WELL AS A RAIN SENSOR W/ MOUNTING |
| | LOCATION AND MOUNTING DETAIL FOR 500 BLOCK. |
| | |
| | 2. PER WPB FBC 107.2.1, PROVIDE LOCATION OF THE |
| | REQUIRED RAIN SENSOR AND NOTE EXISTING OR NEW. |
| | |
| | END OF COMMENTS. |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | ALL PLANS TO BE DIGITALLY SIGNED AND SEALED BY THE |
| | DESIGNER IN ACCORDANCE WITH FAC AND FS. |
| | |
| | |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | EMAIL [email protected] |
| | PHONE 561-246-0882 MOBILE |
| | |
| | 20050033 500 @ CLEMATIS ST |
| | |