| 2020-06-19 07:24:32 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| | MANUAL REVISED 2017 |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH |
| | EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| | FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION |
| | NFPA 54 = NATIONAL FUEL GAS CODE |
| | NFPA 58 = LIQUIFIED PETROLEUM GAS CODE |
| | NFPA 96 = STANDARD FOR VENTILATION CONTROLAND FIRE |
| | PROTECTION OF COMMERCIAL COOKING OPERATIONS 2017 |
| | NFPA 99 = HEALTH CARE FACILITIES CODE |
| | NFPA 99B = STANDARD FOR HYPERBARIC FACILITIES |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | 20050025 2701 S DIXIE HWY |
| | |
| | 1ST REVIEW |
| | |
| | REVIEW OF SHELL CONSTRUCTION ONLY. TENANT BUILD OUT |
| | UNDER A SEPARATE PERMIT. |
| | RE: GREASE INTERCEPTOR; SHALL BE PROVIDED ON THE TENANT |
| | BUILDOUT PERMIT. A SEPARATE PERMIT WILL BE REQUIRED; |
| | SHOWN ON SHELL PLANS FOR REFERENCE ONLY. |
| | |
| | PLUMBING COMMENTS: DENIED |
| | 1. RE: CIVIL DRAWING C.5; REFERENCE IS MADE TO CIVIL |
| | DRAWING C.10 REGARDING THE PROPOSED RPZ BACKFLOW |
| | PREVENTOR. THIS DRAWING IS NOT INCLUDED IN THE |
| | SUBMITTAL; NOTED WPB UTILITIES DETAILS WS-1 AND WS-11 |
| | ARE REQUIRED. PER WPB FBC 107.2.1, SUBMIT C.10. A |
| | SEPARATE PERMIT IS REQUIRED FOR THE BACKFLOW PREVENTER. |
| | 2. RE: AS-102: DETAIL 4; COMBO ROOF DRAIN IS NOT |
| | APPLICABLE TO A COMBINATION PRIMARY/SECONDARY ROOF |
| | DRAIN. PER WPB 107.2.1, PROVIDE A DETAIL SHOWING THE |
| | PRIMARY/SECONDARY ROOF DRAIN. PROPERLY IDENTIFY THE |
| | STANDARD DRAIN DETAIL AND THE COMBINATION |
| | PRIMARY/SECONDARY DRAIN DETAIL. |
| | 3. RE: PS-000 PLUMBING FIXTURE SCHEDULE; THE SCHEDULED |
| | RD-2 ZURN Z-100LP-ERC IS NOT A COMBINATION |
| | PRIMARY/SECONDARY DUAL OUTLET ROOF DRAIN AS NOTED IN |
| | DESCRIPTION. PER WPB FBC 107.2.1, PROVIDE A AN |
| | APPLICABLE DRAIN. |
| | 4. PER WPB FBC 107.2.1, PROVIDE A PRIMARY AND SECONDARY |
| | STORM WATER RISER DIAGRAM. IDENTIFY PRIMARY AND |
| | SECONDARY ON THE PLAN. |
| | 5. RE: CIVIL DRAWING C.3, THE SITE STORM LATERALS DO |
| | NOT MATCH THE STORM PIPING LAYOUT ON PS-201 PLUMBING |
| | PLAN. PER WPB FBC 107.2.1, CLARIFY AND RECONCILE. |
| | 6. AS-701: DETAIL 4, CANOPY ROOF DRAIN |
| | A. PER WPB FBC 107.2.1, PROVIDE MAXIMUM ELEVATION |
| | DIFFERENCE BETWEEN TOP OF CANOPY EDGE AND RIM OF CANOPY |
| | ROOF DRAIN. |
| | B. PER WPB FBC 107.2.1, PROVIDE SIZE OF ALUMINUM |
| | DOWNSPOUT |
| | C. PER WPB FBC 107.2.1, SPECIFY AND PROVIDE TRANSITION |
| | FITTING FROM PIPE TO ALUMINUM DOWNSPOUT |
| | |
| | |
| | END OF COMMENTS. |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |
| | ALL PLANS TO BE DIGITALLY SIGNED AND SEALED BY THE |
| | DESIGNER IN ACCORDANCE WITH FAC AND FS. |
| | |
| | |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | EMAIL [email protected] |
| | PHONE 561-246-0882 MOBILE |
| | |
| | 20050025 2701 S DIXIE HWY |
| | |
| | |
| | |