Notes
Date Text
2020-06-19 07:24:32CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 NFPA 54 = NATIONAL FUEL GAS CODE
 NFPA 58 = LIQUIFIED PETROLEUM GAS CODE
 NFPA 96 = STANDARD FOR VENTILATION CONTROLAND FIRE
 PROTECTION OF COMMERCIAL COOKING OPERATIONS 2017
 NFPA 99 = HEALTH CARE FACILITIES CODE
 NFPA 99B = STANDARD FOR HYPERBARIC FACILITIES
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 20050025 2701 S DIXIE HWY
  
 1ST REVIEW
  
 REVIEW OF SHELL CONSTRUCTION ONLY. TENANT BUILD OUT
 UNDER A SEPARATE PERMIT.
 RE: GREASE INTERCEPTOR; SHALL BE PROVIDED ON THE TENANT
 BUILDOUT PERMIT. A SEPARATE PERMIT WILL BE REQUIRED;
 SHOWN ON SHELL PLANS FOR REFERENCE ONLY.
  
 PLUMBING COMMENTS: DENIED
 1. RE: CIVIL DRAWING C.5; REFERENCE IS MADE TO CIVIL
 DRAWING C.10 REGARDING THE PROPOSED RPZ BACKFLOW
 PREVENTOR. THIS DRAWING IS NOT INCLUDED IN THE
 SUBMITTAL; NOTED WPB UTILITIES DETAILS WS-1 AND WS-11
 ARE REQUIRED. PER WPB FBC 107.2.1, SUBMIT C.10. A
 SEPARATE PERMIT IS REQUIRED FOR THE BACKFLOW PREVENTER.
 2. RE: AS-102: DETAIL 4; COMBO ROOF DRAIN IS NOT
 APPLICABLE TO A COMBINATION PRIMARY/SECONDARY ROOF
 DRAIN. PER WPB 107.2.1, PROVIDE A DETAIL SHOWING THE
 PRIMARY/SECONDARY ROOF DRAIN. PROPERLY IDENTIFY THE
 STANDARD DRAIN DETAIL AND THE COMBINATION
 PRIMARY/SECONDARY DRAIN DETAIL.
 3. RE: PS-000 PLUMBING FIXTURE SCHEDULE; THE SCHEDULED
 RD-2 ZURN Z-100LP-ERC IS NOT A COMBINATION
 PRIMARY/SECONDARY DUAL OUTLET ROOF DRAIN AS NOTED IN
 DESCRIPTION. PER WPB FBC 107.2.1, PROVIDE A AN
 APPLICABLE DRAIN.
 4. PER WPB FBC 107.2.1, PROVIDE A PRIMARY AND SECONDARY
 STORM WATER RISER DIAGRAM. IDENTIFY PRIMARY AND
 SECONDARY ON THE PLAN.
 5. RE: CIVIL DRAWING C.3, THE SITE STORM LATERALS DO
 NOT MATCH THE STORM PIPING LAYOUT ON PS-201 PLUMBING
 PLAN. PER WPB FBC 107.2.1, CLARIFY AND RECONCILE.
 6. AS-701: DETAIL 4, CANOPY ROOF DRAIN
 A. PER WPB FBC 107.2.1, PROVIDE MAXIMUM ELEVATION
 DIFFERENCE BETWEEN TOP OF CANOPY EDGE AND RIM OF CANOPY
 ROOF DRAIN.
 B. PER WPB FBC 107.2.1, PROVIDE SIZE OF ALUMINUM
 DOWNSPOUT
 C. PER WPB FBC 107.2.1, SPECIFY AND PROVIDE TRANSITION
 FITTING FROM PIPE TO ALUMINUM DOWNSPOUT
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 ALL PLANS TO BE DIGITALLY SIGNED AND SEALED BY THE
 DESIGNER IN ACCORDANCE WITH FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-246-0882 MOBILE
  
 20050025 2701 S DIXIE HWY
  
  
  