| Date |
Text |
| 2020-09-09 11:51:15 | 09/09/20 3RD PLUMBING REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. SIGNED AND SEALED DRAWINGS NEED TO BE |
| | DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR |
| | ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW - OR - |
| | IF YOUR ENGINEER DOES NOT HAVE AN ELECTRONIC OR DIGITAL |
| | SIGNATURE - PLEASE DROP OFF (CITY HALL DROP BOX) THE |
| | ORIGINAL SIGNED AND SEALED DOCUMENT ALONG WITH A "PLAN |
| | REVIEW REQUEST FORM" EXPLAINING THE REASON FOR |
| | SUBMITTING THE DOCUMENT OR DRAWINGS. PLAN REVIEW |
| | REQUEST FORM CAN BE OBTAINED BY E MAILING [email protected] |
| | AND ASKING FOR THE FORM. |
| | |
| | 2. A SUB PLUMBING PERMIT IS REQUIRED BY A LICENSED |
| | CONTRACTOR FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS |
| | TO THE FBC SEC. 105.1. |
| | |
| | 3. PLEASE SHOW THE SOURCE OF HOT WATER FOR THE LAV, IF |
| | AN INSTA HOT DEVICE WILL BE USED PLEASE PROVIDE |
| | SPECIFICATIONS FOR IT. THIS LAV WILL REQUIRE TO BE |
| | TEMPERED WATER, SOME DEVICES COME EQUIPPED FOR TEMPERED |
| | WATER DEVICE AND THEY MUST COMPLY WITH ASSE 1070 PER |
| | THE 2017 FBC SEC. P 607.4. |
| | |
| | 4. PLEASE SHOW WATER SERVICE SUPPLY AND SHUT OFF VALVE |
| | PER THE 2017 FBC SEC. P 306.4. |
| | |
| | 5. PLEASE SHOW HAMMER ARRESTOR FOR DRINKING FOUNTAIN |
| | PER THE 2017 FBC SEC. 604.9. |
| | |
| | 6. ON SHEET A-2 YOU SHOW THE DRINKING FOUNTAIN BEHIND |
| | THE URINAL AND ON L-1 YOU SHOW IT NEXT TO THE BATHROOM |
| | DOOR PLEASE CLARIFY LOCATION, THE DRINKING FOUNTAIN |
| | CANNOT DISCHARGE INTO A HORIZONTAL WET VENT PER THE |
| | 2017 FBC SEC. P 912.1. |
| | |
| | 7. SUBMIT A SLAB REPAIR DETAIL AND SHOW THE WIDTH OF |
| | THE REPAIR, THE MINIMUM THICKNESS OF THE CONCRETE TO BE |
| | REPLACED, AND THE PSI OF THE CONCRETE. SHOW THE SIZE |
| | AND LENGTH OF THE DOWELS, THE MINIMUM EMBEDMENT DEPTH |
| | INTO THE EXISTING SLAB, THE ANCHORING MATERIAL FOR THE |
| | DOWELS AND THE SPACING OF THE DOWELS ON CENTER. THE |
| | REPAIR SHALL ALSO INCLUDE TERMITE TREATMENT OF THE SOIL |
| | AND THE REQUIRED VAPOR BARRIER OVER WELL-COMPACTED |
| | SOIL. A COPY OF THE TERMITE CERTIFICATE SHALL BE ONSITE |
| | FOR A FINAL INSPECTION. |
| | |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | LUIS A. CRESPO |
| | PLUMBING PLAN EXAMINER / INSPECTOR |
| | EMAIL: [email protected] OFFICE: 561 805-6720 |
| | |