Plan Review Notes
Plan Review Notes For Permit 20050017
Permit Number 20050017
Review Stop P
Sequence Number 3
Notes
Date Text
2020-09-09 11:51:1509/09/20 3RD PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. SIGNED AND SEALED DRAWINGS NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW - OR -
 IF YOUR ENGINEER DOES NOT HAVE AN ELECTRONIC OR DIGITAL
 SIGNATURE - PLEASE DROP OFF (CITY HALL DROP BOX) THE
 ORIGINAL SIGNED AND SEALED DOCUMENT ALONG WITH A "PLAN
 REVIEW REQUEST FORM" EXPLAINING THE REASON FOR
 SUBMITTING THE DOCUMENT OR DRAWINGS. PLAN REVIEW
 REQUEST FORM CAN BE OBTAINED BY E MAILING [email protected]
 AND ASKING FOR THE FORM.
  
 2. A SUB PLUMBING PERMIT IS REQUIRED BY A LICENSED
 CONTRACTOR FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS
 TO THE FBC SEC. 105.1.
  
 3. PLEASE SHOW THE SOURCE OF HOT WATER FOR THE LAV, IF
 AN INSTA HOT DEVICE WILL BE USED PLEASE PROVIDE
 SPECIFICATIONS FOR IT. THIS LAV WILL REQUIRE TO BE
 TEMPERED WATER, SOME DEVICES COME EQUIPPED FOR TEMPERED
 WATER DEVICE AND THEY MUST COMPLY WITH ASSE 1070 PER
 THE 2017 FBC SEC. P 607.4.
  
 4. PLEASE SHOW WATER SERVICE SUPPLY AND SHUT OFF VALVE
 PER THE 2017 FBC SEC. P 306.4.
  
 5. PLEASE SHOW HAMMER ARRESTOR FOR DRINKING FOUNTAIN
 PER THE 2017 FBC SEC. 604.9.
  
 6. ON SHEET A-2 YOU SHOW THE DRINKING FOUNTAIN BEHIND
 THE URINAL AND ON L-1 YOU SHOW IT NEXT TO THE BATHROOM
 DOOR PLEASE CLARIFY LOCATION, THE DRINKING FOUNTAIN
 CANNOT DISCHARGE INTO A HORIZONTAL WET VENT PER THE
 2017 FBC SEC. P 912.1.
  
 7. SUBMIT A SLAB REPAIR DETAIL AND SHOW THE WIDTH OF
 THE REPAIR, THE MINIMUM THICKNESS OF THE CONCRETE TO BE
 REPLACED, AND THE PSI OF THE CONCRETE. SHOW THE SIZE
 AND LENGTH OF THE DOWELS, THE MINIMUM EMBEDMENT DEPTH
 INTO THE EXISTING SLAB, THE ANCHORING MATERIAL FOR THE
 DOWELS AND THE SPACING OF THE DOWELS ON CENTER. THE
 REPAIR SHALL ALSO INCLUDE TERMITE TREATMENT OF THE SOIL
 AND THE REQUIRED VAPOR BARRIER OVER WELL-COMPACTED
 SOIL. A COPY OF THE TERMITE CERTIFICATE SHALL BE ONSITE
 FOR A FINAL INSPECTION.
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved