Date Text
2020-05-26 15:23:581ST REVIEW FBC-2017 PLUMBING
 PERMIT- 20050017
 5/26/2020
  
 CODES IN EFFECT:
  
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SECTION 107.3.5.1.3 WPB- PROVIDE PLUMBING PLANS AND
 DETAILS INCLUDING:
  
 A) SCOPE OF WORK OUTLINE.
 B) SANITARY ISOMETRIC.
 C) WATER RISER.
 D) SANITARY DRAINAGE AND WATER DISTRIBUTION LAYOUT
 DRAWINGS SHOWING PIPING RUNS AND POINTS OF CONNECTIONS
 TO THE EXISTING BUILDING DRAIN AND WATER SUPPLY LINES.
  
 2) PROVIDE ENLARGED DIMENSIONED DRAWINGS OF THE NEW
 WOMEN'S TOILET ROOM TO SHOW COMPLIANCE WITH SECTION
 213.2 FBC ACC. THE ENLARGED DRAWINGS SHALL SHOW:
 A) CLEAR FLOOR SPACE DIMENSIONS FOR THE WATER CLOSET-
 SECTION 604.3 FBC ACC.
 B) CLEAR FLOOR SPACE DIMENSION FOR THE LAVATORY-
 SECTION 606.2.
 C) TURNING SPACE DIAMETER- SECTION 304.3.
 D) CENTERLINE OF THE WATER CLOSET FROM THE SIDE WALLS
 OR PARTITIONS- SECTION 604.2.
 E) HEIGHT OF THE WATER CLOSET SEATS FROM THE FINISHED
 FLOORS- SECTION 604.4.
 F) HEIGHT OF THE FRONT RIM OF THE LAVATORY FROM THE
 FINISHED FLOOR- SECTION 606.3
 G) KNEE AND TOE CLEARANCES FOR THE LAVATORY- SECTION
 306.
 H) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB
 BARS- SECTION 604.5
 I) LOCATIONS OF THE WATER CLOSET FLUSH CONTROL- SECTION
 604.6.
 J) LOCATIONS, CLEARANCES, AND MOUNTING HEIGHTS FOR
 PAPER DISPENSERS- SECTION 604.7
 H) HEIGHT OF THE MIRROR FROM THE FINISHED FLOOR TO THE
 BOTTOM OF THE REFLECTIVE SURFACE- SECTION 603.3.
  
 3) SHEET A2 SHOWS A RELOCATED WHEELCHAIR ACCESSIBLE
 DRINKING FOUNTAIN. PROVIDE ENLARGED DIMENSIONED
 DRAWINGS AND DETAILS INDICATING:
 A) CLEAR FLOOR SPACE FOR FORWARD WHEELCHAIR APPROACH-
 SECTION 602.2. FBC ACC.
 B) KNEE AND TOE CLEARANCES- SECTION 306.
 C) SPOUT HEIGHT AND SPOUT LOCATION- SECTION 602.4 AND
 602.5.
  
 4) REFER TO SECTION 211.2 FBC ACC: NO FEWER THAN TWO
 DRINKING FOUNTAINS SHALL BE PROVIDED. ONE DRINKING
 FOUNTAIN SHALL COMPLY WITH SECTIONS 602.1- 602.6, AND
 ONE SHALL COMPLY WITH 602.7. SECTION 602.7 REQUIRES
 THAT SPOUT OUTLETS FOR STANDING PERSONS SHALL BE 38
 INCHES MINIMUM AND 43 INCHES MAXIMUM FROM THE FINISHED
 FLOOR. IT APPEARS THAT AN ADDITIONAL FOUNTAIN WILL HAVE
 TO BE INSTALLED.
  
 5) SHOW THE LOCATION OF THE REQUIRED SERVICE SINK-
 TABLE 403.3. FBC P.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.