| Plan Review Notes For Permit 20050017 |
| Permit Number |
20050017 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-05-21 12:30:09 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | 1) RISER DIAGRAM REQUIRED 215.5 | | | | | | PROVIDE RISER DIAGRAM OF EXISTING SERVICE. NEC 215.5; | | | FBC 107.2.1 | | | | | | 2) LOAD CALC QND PANEL SCHEDULE REQUIRED | | | | | | PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE EXISTING | | | AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE IS | | | ADEQUATE. NEC 215.2, 220, 408.30; | | | PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED | | | CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS, | | | AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY | | | WITH CODE. NEC 210.8, 210.12, 215.5, 408.4; | | | | | | 3) LIGHTING CONTROL REQUIRED PER FBC ENERGY CODE | | | | | | PROVIDE LIGHTING CONTROL PER FBC ENERGY CODE. FBC CE | | | 405.2.2.2 | | | |
|