Plan Review Notes
Plan Review Notes For Permit 20050017
Permit Number 20050017
Review Stop E
Sequence Number 1
Notes
Date Text
2020-05-21 12:30:09ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) RISER DIAGRAM REQUIRED 215.5
  
 PROVIDE RISER DIAGRAM OF EXISTING SERVICE. NEC 215.5;
 FBC 107.2.1
  
 2) LOAD CALC QND PANEL SCHEDULE REQUIRED
  
 PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE EXISTING
 AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE IS
 ADEQUATE. NEC 215.2, 220, 408.30;
 PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS,
 AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY
 WITH CODE. NEC 210.8, 210.12, 215.5, 408.4;
  
 3) LIGHTING CONTROL REQUIRED PER FBC ENERGY CODE
  
 PROVIDE LIGHTING CONTROL PER FBC ENERGY CODE. FBC CE
 405.2.2.2
  