Plan Review Notes
Plan Review Notes For Permit 20050017
Permit Number 20050017
Review Stop B
Sequence Number 1
Notes
Date Text
2020-05-11 11:55:412017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20050017
 ADD: 20050017
 CONT: 2218 S DIXIE HWY.
 TEL: 561-324-3163
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. MAY 11TH/ 2020
 ACTION: DENIED
  
 1) NEITHER THE COVERSHEET NOR THE LIFE SAFETY SHEET
 PROVIDE THE MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 107.3.5.1 COMMERCIAL BUILDINGS.
 107.3.5.1.1 BUILDING REVIEW
 PROPOSED OCCUPANCY GROUP
 MINIMUM TYPE OF CONSTRUCTION
 SQUARE FOOTAGE OF EITHER THE TENANT SPACE OR BUILDING
 IS THE BUILDING FIRE SPRINKLERED? / IS FIRE SPRINKLERS
 REQUIRED?
  
 LIFE SAFETY REQUIREMENTS:
 OCCUPANT LOAD, IS IT GROSS OR NET
  
 2) SHEET A-2 FLOOR PLAN SHOWS NEW INTERIOR WALLS METAL
 STUD PARTITIONS WITH GYPSUM BOARD PARTITION FULL
 HEIGHT. THE FLOOR PLAN DOES NOT PROVIDE THE 66666SIZE,
 GAUGE, SPACING OF THE METAL STUDS, AND HEIGHT OF THE
 PROPOSED STUDS NOR THE THICKNESS OF THE WALLBOARD. 2017
 FBC-B TABLE 2508.1.
  
 3) SHEET A-2, THE LIFE SAFETY SHEET NOR THE MECHANICAL
 SHEET INDICATE A HOOD SYSTEM OVER THE STOVE WITHIN THE
 KITCHEN. NONE OF THESE PLANS INDICATE IF THE KITCHEN IS
 OPERATIONAL, OR IF A SALES DISPLAY? ADDITIONAL
 INFORMATION IS REQUIRED.
 DOES THE KITCHEN NEED TO SHOW COMPLIANCE WITH THE 2017
 FBC-B SECTION 904.2.2?
  
 4) SHEET L-1 THE LIFE SAFETY SHEET SHOWS A SINGLE WATER
 FOUNTAIN, PLEASE SHOW COMPLIANCE WITH THE 2017
 FBC-ACCESSIBILITY CODE SECTION 211.2 MINIMUM NUMBER:
  
 5) THE FLOOR PLAN DOES NOT CLEARLY STATE IF THERE ARE
 GOING TO BE NEW OPENINGS IN A BLOCK WALL CREATING A
 LARGER TENANT SPACE. THE S-1 STRUCTURAL SHEET DOES HAVE
 A DETAIL FOR NEW OPENINGS IN CONCRETE BLOCK WALL.
 WITHIN THIS DETAIL THERE IS A NOTE STATING SEE PRECAST
 CONCRETE LINTELS SEE SCHEDULE, THERE IS NO SCHEDULE ON
 THIS SHEET. 107.2.1.2. ADDITIONAL INFORMATION IS
 REQUIRED.
  
 6) THE LIFE SAFETY SHEET AND MECHANICAL SHEET DO NOT
 LINE UP FOR WALL LAYOUT. THE MECHANICAL SHEET DOES NOT
 SHOW ANY WING WALL JUST TO THE LEFT OF THE MECHANICAL
 ROOM WHEREAS THE LIFE SAFETY SHEET DOES. DISCREPANCY IN
 PLAN, ADDITIONAL INFORMATION IS REQUIRED. 107.2.1.2.
  
 7) THE FLOOR PLAN AND LIFE SAFETY PLAN SHOW NEW
 RESTROOMS BUT THERE ARE NO DETAIL AS TO FLOOR PLAN OR
 ELEVATIONS SHOWING COMPLIANCE WITH CHAPTER 6 OF THE
 ACCESSIBILITY CODE.
  
  
  
 8A) DISPROPORTIONATE COST. PLEASE REVIEW HOW YOU ARE TO
 MEET DISPROPORTIONATE COST. EITHER THE CONTRACTOR OR
 THE DESIGNER OF RECORD ON THEIR LETTERHEAD ARE TO
 PROVIDE ON THEIR LETTERHEAD HOW THEY ARE GOING TO SPEND
 UP TO THE 20% DISPROPORTIONATE FUNDS IN THE ORDER
 LISTED BELOW. 2017 FBC-ACCESSIBILITY CODE 202.4.1
 DISPROPORTION COST:
  
 8B) 2017 FBC-ACCESSIBILITY CODE SECTION 606.3 HEIGHT.
 LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE FRONT
 OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34 INCHES
 (865 MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND
  
 9) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
 PLEASE NOTE WE ARE WORKING FROM HOME IF YOU WOULD LIKE
 TO CONTACT ME, MY CELL NUMBER IS 561-718-9724.
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  