| 2020-05-11 11:55:41 | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 20050017 |
| | ADD: 20050017 |
| | CONT: 2218 S DIXIE HWY. |
| | TEL: 561-324-3163 |
| | E-MAIL: [email protected] |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: MON. MAY 11TH/ 2020 |
| | ACTION: DENIED |
| | |
| | 1) NEITHER THE COVERSHEET NOR THE LIFE SAFETY SHEET |
| | PROVIDE THE MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. |
| | 107.3.5.1 COMMERCIAL BUILDINGS. |
| | 107.3.5.1.1 BUILDING REVIEW |
| | PROPOSED OCCUPANCY GROUP |
| | MINIMUM TYPE OF CONSTRUCTION |
| | SQUARE FOOTAGE OF EITHER THE TENANT SPACE OR BUILDING |
| | IS THE BUILDING FIRE SPRINKLERED? / IS FIRE SPRINKLERS |
| | REQUIRED? |
| | |
| | LIFE SAFETY REQUIREMENTS: |
| | OCCUPANT LOAD, IS IT GROSS OR NET |
| | |
| | 2) SHEET A-2 FLOOR PLAN SHOWS NEW INTERIOR WALLS METAL |
| | STUD PARTITIONS WITH GYPSUM BOARD PARTITION FULL |
| | HEIGHT. THE FLOOR PLAN DOES NOT PROVIDE THE 66666SIZE, |
| | GAUGE, SPACING OF THE METAL STUDS, AND HEIGHT OF THE |
| | PROPOSED STUDS NOR THE THICKNESS OF THE WALLBOARD. 2017 |
| | FBC-B TABLE 2508.1. |
| | |
| | 3) SHEET A-2, THE LIFE SAFETY SHEET NOR THE MECHANICAL |
| | SHEET INDICATE A HOOD SYSTEM OVER THE STOVE WITHIN THE |
| | KITCHEN. NONE OF THESE PLANS INDICATE IF THE KITCHEN IS |
| | OPERATIONAL, OR IF A SALES DISPLAY? ADDITIONAL |
| | INFORMATION IS REQUIRED. |
| | DOES THE KITCHEN NEED TO SHOW COMPLIANCE WITH THE 2017 |
| | FBC-B SECTION 904.2.2? |
| | |
| | 4) SHEET L-1 THE LIFE SAFETY SHEET SHOWS A SINGLE WATER |
| | FOUNTAIN, PLEASE SHOW COMPLIANCE WITH THE 2017 |
| | FBC-ACCESSIBILITY CODE SECTION 211.2 MINIMUM NUMBER: |
| | |
| | 5) THE FLOOR PLAN DOES NOT CLEARLY STATE IF THERE ARE |
| | GOING TO BE NEW OPENINGS IN A BLOCK WALL CREATING A |
| | LARGER TENANT SPACE. THE S-1 STRUCTURAL SHEET DOES HAVE |
| | A DETAIL FOR NEW OPENINGS IN CONCRETE BLOCK WALL. |
| | WITHIN THIS DETAIL THERE IS A NOTE STATING SEE PRECAST |
| | CONCRETE LINTELS SEE SCHEDULE, THERE IS NO SCHEDULE ON |
| | THIS SHEET. 107.2.1.2. ADDITIONAL INFORMATION IS |
| | REQUIRED. |
| | |
| | 6) THE LIFE SAFETY SHEET AND MECHANICAL SHEET DO NOT |
| | LINE UP FOR WALL LAYOUT. THE MECHANICAL SHEET DOES NOT |
| | SHOW ANY WING WALL JUST TO THE LEFT OF THE MECHANICAL |
| | ROOM WHEREAS THE LIFE SAFETY SHEET DOES. DISCREPANCY IN |
| | PLAN, ADDITIONAL INFORMATION IS REQUIRED. 107.2.1.2. |
| | |
| | 7) THE FLOOR PLAN AND LIFE SAFETY PLAN SHOW NEW |
| | RESTROOMS BUT THERE ARE NO DETAIL AS TO FLOOR PLAN OR |
| | ELEVATIONS SHOWING COMPLIANCE WITH CHAPTER 6 OF THE |
| | ACCESSIBILITY CODE. |
| | |
| | |
| | |
| | 8A) DISPROPORTIONATE COST. PLEASE REVIEW HOW YOU ARE TO |
| | MEET DISPROPORTIONATE COST. EITHER THE CONTRACTOR OR |
| | THE DESIGNER OF RECORD ON THEIR LETTERHEAD ARE TO |
| | PROVIDE ON THEIR LETTERHEAD HOW THEY ARE GOING TO SPEND |
| | UP TO THE 20% DISPROPORTIONATE FUNDS IN THE ORDER |
| | LISTED BELOW. 2017 FBC-ACCESSIBILITY CODE 202.4.1 |
| | DISPROPORTION COST: |
| | |
| | 8B) 2017 FBC-ACCESSIBILITY CODE SECTION 606.3 HEIGHT. |
| | LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE FRONT |
| | OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34 INCHES |
| | (865 MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND |
| | |
| | 9) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE |
| | THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED |
| | DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE |
| | MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS |
| | AND INFORMATION LACKING UNDER THE PRIOR REVIEW. |
| | |
| | PLEASE NOTE WE ARE WORKING FROM HOME IF YOU WOULD LIKE |
| | TO CONTACT ME, MY CELL NUMBER IS 561-718-9724. |