| Plan Review Notes For Permit 20050006 |
| Permit Number |
20050006 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2020-05-18 10:54:01 | ROOFING | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | | | | | ***AN INSPECTION LETTER FROM AN ENGINEER DOES NOT TAKE | | | THE PLACE OF THE ADDITIONAL ATTACHMENT DETAILS REQUIRED | | | IN THE REVIEW COMMENTS.*** | | | | | | 1) PLEASE PROVIDE SIGNED AND SEALED ADDITIONAL | | | ATTACHMENT DETAILS FROM AN ARCHITECT OR ENGINEER FOR | | | ROOF ZONES 2 AND 3 WHICH REQUIRE HIGHER WIND PRESSURES | | | THAN THE MAXIMUM SHOWN ON THE PRODUCT APPROVAL (-52.5) | | | - SEE GENERAL LIMITATION NUMBER 7 ON THE PRODUCT | | | APPROVAL. | | | 2) SIGNED AND SEALED ENGINEERING PROVIDED WILL NEED TO | | | BE DIGITALLY SIGNED AND SEALED BY THE ENGINEER TO BE | | | USED IN ELECTRONIC PLAN REVIEW. | | | | | | FYI - 668.003(2) AND (3), F.S. | | | (2) A PROFESSIONAL ENGINEER UTILIZING A DIGITAL | | | SIGNATURE TO ELECTRONICALLY SIGN AND SEAL ENGINEERING | | | PLANS, | | | SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS SHALL HAVE | | | THEIR IDENTITY AUTHENTICATED BY A CERTIFICATION | | | AUTHORITY |
|