Plan Review Notes
Plan Review Notes For Permit 20050001
Permit Number 20050001
Review Stop P
Sequence Number 1
Notes
Date Text
2020-06-04 08:54:231ST REVIEW FBC-2017 RES.
 PERMIT- 20050001
 6/4/2020
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SECTION 107.2.1 WPB: THE PLUMBING PLANS AND
 SPECIFICATIONS ARE INCOMPLETE AND DO NOT SHOW THE
 CONNECTIONS OF THE MAIN POOL RETURN (PRESSURE) PIPING
 CONNECTING TO THE NEW PUMP, AND THE NEW PUMP CONNECTION
 TO THE EXISTING POOL EQUIPMENT- FILTER, HEATER,
 CHLORINATOR ETC. REFER TO SECTIONS R4501.6- R4501.8 FBC
 RES. AND PROVIDE COMPLETE POOL PIPING AND EQUIPMENT
 DIAGRAMS INCLUDING:
 A) TOTAL POOL VOLUME.
 B) POOL TURNOVER RATES AT LOW AND HIGH SPEED, AND
 DESIGN FLOW RATE.
 C) TDH CALCULATIONS.
 D) PUMP CURVE
 E) PIPE FLOW VELOCITIES- PRESSURE AND SUCTION.
 F) CHANNEL DRAIN GPM FLOW RATES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  