| 2020-05-01 07:37:19 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT-20041164 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | THIS PERMIT IS FOR THE REFRIGERATION SYSTEMS FOR THE |
| | RACETRAC. PLEASE SUBMIT CODE COMPLIANT DRAWINGS |
| | ADDRESSING REQUIREMENTS FROM CHAPTER 11 OF THE FBC M |
| | CODE FOR THE REFRIGERATION FOR ALL EQUIPMENT ON THIS |
| | PROJECT. THE DOCUMENTS UPLOADED WITH THIS PROJECT ARE |
| | FOR THE MECHANICAL SYSTEMS ON THIS PROJECT. I CANNOT DO |
| | A REVIEW FOR THE REFRIGERATION ON THIS PROJECT UNTIL |
| | THE CORRECT DOCUMENTS HAVE BEEN SUBMITTED. FBC FS |
| | 107.2.1 |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| | UPDATED. |
| | |
| | |