| 2020-05-15 09:28:42 | 1ST REVIEW FBC-2017 FUEL GAS |
| | PERMIT #20041156 |
| | 5/15/2020 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) GAS ISOMETRIC: |
| | A) INDICATED ON THE ISO ARE EXTERIOR AND INTERIOR RUN |
| | LENGTHS. PLEASE INDICATE THE TOTAL DEVELOPED LENGTH OF |
| | THE SYSTEM TO THE MOST REMOTE OUTLET. IT APPEARS THAT |
| | THE VERTICAL LENGTH OF GALVANIZED PIPING BETWEEN THE |
| | TWO CSST RUNS WAS NOT INCLUDED- SECTIONS G2413.4.1 & |
| | G2413.4.2 FBC RES |
| | B) INDICATE THE TOTAL BTUH LOAD OF THE SYSTEM-- SECTION |
| | 2413.2. PLEASE NOTE THAT THE ISO INDICATES THE |
| | GENERATOR TO BE 330,000 BTUH, BUT THERE IS ANOTHER |
| | INCOMPLETE RISER DRAWING UPLOADED THAT INDICATES IT TO |
| | BE 360.000 BTUH. |
| | C) INDICATE THE GAS DELIVERY PRESSURE AT THE METER, AND |
| | THE STEP-DOWN PRESSURES AT THE GENERATOR AND |
| | APPLIANCES- SECTION G2413.2 & G2413.4.3 |
| | D)) SHOW THE LOCATIONS OF ALL (MP) STEPDOWN REGULATORS |
| | AND REQUIRED SHUT OFF VALVES. PLEASE NOTE THAT WHERE |
| | CONNECTED TO RIGID PIPING, A UNION SHALL BE INSTALLED |
| | WITHIN 1 FT. OF EITHER SIDE OF THE MP REGULATOR- |
| | SECTION G2421.2(7). |
| | E) LIST ALL PIPE SIZING TABLES USED FOR THE PE, |
| | GALVANIZED, AND CSST PIPING- SEE TABLES G2413.4(1) |
| | THROUGH G2413.4(21) FBC RES. |
| | |
| | 2) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE NEW |
| | GENERATOR- SECTION G2403.3 FBC RES. |
| | |
| | 3) PROVIDE A COPY OF A SURVEY OR SITE DRAWING SHOWING |
| | THE LOCATION OF THE GENERATOR AND CLEARANCE DISTANCES |
| | TO OPERABLE OPENINGS INTO THE BUILDING. PLEASE NOTE A |
| | 10' CLEARANCE IS REQUIRED PER SECTION R303.5.1 FBC RES. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |