| 2020-09-16 13:01:24 | 2ND REVIEW FBC-2017 MECHANICAL |
| | PERMIT-20041120 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THE A/C CHANGE OUT COMPLIANCE FORM IS NOT COMPLETE. |
| | PLEASE CIRCLE EITHER THE SEER OR EER BESIDE YOUR 14. |
| | THE AREA ON THE FORM FOR THE EXISTING SYSTEM COMPONENTS |
| | HAS THE WORD ?NONE? IN THE LINE WHERE THE MANUFACTURER |
| | SHOULD BE. DOES THIS MEAN THERE IS NO EXISTING UNIT |
| | NOW? IF THAT IS THE CASE THERE IS NO USE FOR THIS FORM. |
| | THIS WOULD BE CONSIDERED A NEW INSTALLATION FOR AN |
| | EXISTING BUILDING. PLEASE EXPLAIN? FBC FS 107.2.1 |
| | |
| | 2) PLEASE SEE NOTE 4 OF 1ST REVIEW, PLEASE PROVIDE |
| | VENTILATION CALCULATIONS FOR THIS CONDITIONED SPACE. |
| | FBC M TABLE 403.3.1.1 (WAREHOUSE SPACE THIS UNIT IS |
| | CONDITIONING, SQUARE FOOTAGE X 0.06 FOR THE AREA |
| | OUTDOOR AIRFLOW RATE IN THE BREATHING ZONE). |
| | |
| | 3) THE ENERGY CALCULATIONS PROVIDED INDICATE THE TOTAL |
| | COOLING LOADS ON EQUIPMENT IS 78,542: THE RHEEM UNIT |
| | RACA 14060AJT***AA COOLING CAPACITY IS 59,000. THIS |
| | DOES NOT APPEAR TO BE SUFFICIENT TO COOL THIS SPACE. |
| | THE DRAWING INDICATES ANOTHER EXISTING UNIT IN THIS |
| | AREA. WITH NO MEASUREMENTS PROVIDED FOR FLOOR AREA OF |
| | THIS WAREHOUSE THERE IS NO WAY FOR ME TO KNOW IF YOU |
| | ARE TRYING TO CONDITION THE ENTIRE SPACE WITH THIS NEW |
| | UNIT OR TRYING TO CONDITION A CERTAIN AREA OF THIS |
| | SPACE. PLEASE PROVIDE MORE DETAILS TO DETERMINE THIS. |
| | FBC FS 107.2.1 |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| | UPDATED. |
| | |
| | |