2020-09-16 13:01:242ND REVIEW FBC-2017 MECHANICAL
 PERMIT-20041120
  
 CODES IN EFFECT:
  
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE A/C CHANGE OUT COMPLIANCE FORM IS NOT COMPLETE.
 PLEASE CIRCLE EITHER THE SEER OR EER BESIDE YOUR 14.
 THE AREA ON THE FORM FOR THE EXISTING SYSTEM COMPONENTS
 HAS THE WORD ?NONE? IN THE LINE WHERE THE MANUFACTURER
 SHOULD BE. DOES THIS MEAN THERE IS NO EXISTING UNIT
 NOW? IF THAT IS THE CASE THERE IS NO USE FOR THIS FORM.
 THIS WOULD BE CONSIDERED A NEW INSTALLATION FOR AN
 EXISTING BUILDING. PLEASE EXPLAIN? FBC FS 107.2.1
  
 2) PLEASE SEE NOTE 4 OF 1ST REVIEW, PLEASE PROVIDE
 VENTILATION CALCULATIONS FOR THIS CONDITIONED SPACE.
 FBC M TABLE 403.3.1.1 (WAREHOUSE SPACE THIS UNIT IS
 CONDITIONING, SQUARE FOOTAGE X 0.06 FOR THE AREA
 OUTDOOR AIRFLOW RATE IN THE BREATHING ZONE).
  
 3) THE ENERGY CALCULATIONS PROVIDED INDICATE THE TOTAL
 COOLING LOADS ON EQUIPMENT IS 78,542: THE RHEEM UNIT
 RACA 14060AJT***AA COOLING CAPACITY IS 59,000. THIS
 DOES NOT APPEAR TO BE SUFFICIENT TO COOL THIS SPACE.
 THE DRAWING INDICATES ANOTHER EXISTING UNIT IN THIS
 AREA. WITH NO MEASUREMENTS PROVIDED FOR FLOOR AREA OF
 THIS WAREHOUSE THERE IS NO WAY FOR ME TO KNOW IF YOU
 ARE TRYING TO CONDITION THE ENTIRE SPACE WITH THIS NEW
 UNIT OR TRYING TO CONDITION A CERTAIN AREA OF THIS
 SPACE. PLEASE PROVIDE MORE DETAILS TO DETERMINE THIS.
 FBC FS 107.2.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
  