Plan Review Notes
Plan Review Notes For Permit 20041119
Permit Number 20041119
Review Stop B
Sequence Number 1
Notes
Date Text
2020-05-01 10:57:35ROOFING
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) ROOFING SYSTEM TO BE USED ON THE PROVIDED PRODUCT
 APPROVAL REQUIRES ADDITIONAL SIGNED AND SEALED
 ATTACHMENT DETAILS FROM AN ARCHITECT OR ENGINEER FOR
 ROOF WIND ZONES 2 AND 3 WHICH REQUIRE A HIGHER PRESSURE
 THAN THE MAXIMUM SHOWN ON THE PRODUCT APPROVAL (-52.5)
 - SEE GENERAL LIMITATION NUMBER 7 ON THE PRODUCT
 APPROVAL. SIGNED AND SEALED DRAWINGS OR DOCUMENTS WILL
 NEED TO BE DIGITALY SIGNED AND SEALED TO BE USED IN
 ELECTRONIC PLAN REVIEW.
 2) PLEASE PROVIDE A BUILDING PERMIT COMPLETED BY A
 LICENSED ROOFING CONTRACTOR OR PROVIDE INFORMATION FROM
 THE LICENSING AGENCY THAT ALLOWS A GC TO INSTALL
 ROOFING.
  