| 2020-05-27 16:02:52 | 2ND REVIEW FBC-2017 RES. FUEL GAS |
| | PERMIT #20041097 |
| | 5/27/2020 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) GAS ISOMETRIC: |
| | A) TABLE G2413.4(1) [402.4(2)]: FIREPLACE REQUIRES A |
| | 3/4" SCHEDULE 40 METALLIC PIPE- SECTION G2413.4.1 FBC |
| | RES. |
| | B) AS PREVIOUSLY REQUESTED IN THE 1ST REVIEW, INDICATE |
| | THE EHD (EQUIVALENT HYDRAULIC DIAMETERS) OF THE CSST |
| | LINES ON THE RISER- TABLES G2413.4(5), 402.4(15). TO |
| | HELP EXPEDITE THE REVIEW SUBMIT THE CORRECT TABLES FROM |
| | THE CSST MANUFACTURER WHICH WILL PROVIDE CONVERSION |
| | FROM EHD TO INCHES IN DIAMETER- SECTIONS G2413.4.1 AND |
| | G2415.2 FBC RES. |
| | C) THE TYPE, SIZE, AND LENGTH OF THE BRANCH PIPE |
| | SUPPLYING THE CLOTHES DRYER IS NOT SHOWN- SECTIONS |
| | G2413.4.1 AND G2413.4.2 FBC RES. |
| | |
| | 2) THE SUBMITTED MANUFACTURER'S DATA SHEET FOR THE |
| | FIREPLACE INDICATES IT IS AN OUTDOOR APPLIANCE. THE |
| | RISER INDICATES THE APPLIANCE TO BE LOCATED INDOORS- |
| | SECTION G2408.1 FBC RES. A) THE SPECS DO NOT INDICATE |
| | THE FIREPLACE WAS TESTED IN ACCORDANCE WITH ANSI |
| | Z21.88- SECTION G2435.1 FBC RES. |
| | |
| | 3) THE SUBMITTED MANUFACTURER'S SPECIFICATIONS FOR THE |
| | WATER HEATER AND THE COOKTOP INDICATE APPLIANCE GAS |
| | LOADS THAT DON'T MATCH THE PLANS: |
| | A) THE SPECS INDICATE SELECTED MODEL RG240T6N AT 40,000 |
| | BTUH; THE ISOMETRIC AND THE COMBUSTION AIR CALCS |
| | INDICATE 80,000 BTUH. |
| | B) THE SPECS INDICATE THE COOKTOP WITH ALL SIX BURNERS |
| | OPERATING AT 99,000 BTUH, THE ISOMETRIC INDICATES |
| | 120,000 BTUH, AND THE CALCS INDICATE 72,000 BTUH. |
| | C) THE SPECS FOR THE BBQ DO NOT INDICATE WHAT THE BTUH |
| | GAS LOAD OF THE APPLIANCE IS- SECTION 107.2.1 WPB. |
| | |
| | 4) THE REQUESTED INSTALLATION GUIDELINES FOR THE WATER |
| | HEATER, AND THE SPECS FOR THE CLOTHES DRYER WERE NOT |
| | PROVIDED- SECTION G2408.1 RES. |
| | |
| | 5) THE REQUESTED GAS VENTING PLAN AND INSTALLATION |
| | GUIDELINES FOR THE WATER HEATER WERE NOT PROVIDED- |
| | SECTION G2425.1 FBC RES. A) THE COPIED VENTING FIGURES |
| | FROM THE FBC-17 FUEL GAS ARE NOT ACCEPTABLE- SECTION |
| | 107.2.1 WPB. PROVIDE A SITE-SPECIFIC GAS VENTING |
| | DIAGRAM SHOWING THE TYPE AND SIZE OF VENT, VENT RUN |
| | THROUGH AND OUT OF THE BUILDING, TERMINATION LOCATION, |
| | HEIGHTS ABOVE THE ROOF, AND ANCHORING DETAILS. SUBMIT |
| | SPECIFICATIONS FOR ALL THE VENT FLUES, CONNECTORS, AND |
| | TERMINATION CAPS- SECTIONS G2426.1 THROUGH G2426.7 FBC |
| | RES. |
| | |
| | 6) THE GAS VENTING DIAGRAM FOR THE BBQ IS INCOMPLETE. |
| | IF THE BBQ IS LOCATED UNDER OVERHEAD CONSTRUCTION THE |
| | SPECS INDICATE A 1200 CFM EXHAUST HOOD IS REQUIRED. A) |
| | PROVIDE MANUFACTURER'S SPECIFICATIONS FOR THE HOOD AND |
| | VENT FLUE- SECTIONS G2426.1- G2426.7 26.7 FBC RES. B) |
| | PROVIDE A GAS VENTING DIAGRAM SHOWING THE TYPE AND SIZE |
| | OF VENT, VENT RUN AND TERMINATION LOCATION. INDICATE |
| | THE TERMINATION HEIGHT ABOVE THE ROOF (IF APPLICABLE) |
| | AND PROVIDE ANCHORING DETAILS. C) SHOW THE REQUIRED |
| | CLEARANCES FOR THE BBQ, THE EXHAUST HOOD AND THE VENT |
| | PER THE SPECS. |
| | |
| | 7) COMBUSTION AIR. PLEASE REFER TO SECTION G2407.5.1 |
| | (304.5.1) STANDARD METHOD. IF USING INDOOR AIR, THE |
| | MINIMUM REQUIRED VOLUME SHALL BE 50 CUBIC FEET PER |
| | 1,000 BTU/H OF THE APPLIANCE INPUT RATING. |
| | |
| | 8) PLEASE INDICATE HOW MAKEUP AIR IS BEING PROVIDED FOR |
| | THE CLOTHES DRYER AND PROVIDE A CALCULATION- SECTION |
| | G2407.1 FBC RES. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |