| Date |
Text |
| 2020-05-15 12:05:00 | |
| | 1ST REVIEW FBC-2017 FUEL GAS |
| | PERMIT #20041097 |
| | 5/15/2020 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) GAS ISOMETRIC: |
| | A) THE 1/2" GALVANIZED PIPE SUPPLYING THE 72,000 BTUH |
| | COOKTOP SHALL BE SIZED AT 3/4" PER TABLE G2413.4(1) FBC |
| | RES. |
| | B) INDICATE THE EHD'S (EQUIVALENT HYDRAULIC DIAMETERS) |
| | OF THE CSST LINES- TABLE G2413.4(5). |
| | |
| | 2) SUBMIT MANUFACTURER'S SPECIFICATIONS AND |
| | INSTALLATION GUIDELINES FOR ALL GAS-FIRED APPLIANCES - |
| | SECTION G2403.3 & G2408.1. |
| | |
| | 3) PROVIDE GAS VENTING PLANS FOR THE WATER HEATER, |
| | FIREPLACE AND BBQ- SECTION G2425.1 |
| | |
| | 4) INDICATE HOW COMBUSTION WILL BE PROVIDED TO THE |
| | INDOOR APPLIANCES AND EQUIPMENT. PLEASE INCLUDE |
| | CALCULATIONS- SECTION G2407.1 |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |
| | |