| 2020-05-14 13:51:34 | REVIEWED BY JERRY SMITH. |
| | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION |
| | NFPA 54 = NATIONAL FUEL GAS CODE |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | 20041096 140 MONROE DR |
| | |
| | GAS COMMENTS: DENIED |
| | 1.SUBMIT CALCULATIONS FOR COMBUSTION AIR FOR THE RANGE |
| | PER FBC FG 304.1 |
| | 2.SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS |
| | METER / MP REGULATOR) TO THE MOST REMOTE OUTLET IN THE |
| | BUILDING AND / OR SYSTEM FBC FG 402.4.1, 402.4.2 |
| | 3.PER WPB FBC 107.2.1, SHOW PE TO GALVANIZED RIGID |
| | PIPING TRANSITION ON RISER DIAGRAM. |
| | 4.PER WPB FBC 107.2.1, PROVIDE THE MATERIAL AND TABLE |
| | USED IN SIZING PIPING DOWNSTREAM OF MP REGULATOR(S). |
| | INDICATE ON THE PLAN THE DISTANCE FROM REGULATOR TO |
| | APPLIANCE. |
| | 5.PER WPB FBC 107.2.1, PROVIDE DETAIL OF MP REGULATOR |
| | WITH SHUTOFF VALVE, UNION AND OTHER REQUIRED |
| | ACCESSORIES. COMPLY WITH FBC FG 410.2. |
| | 6.PER WPB FBC 107.2.1, PROVIDE SITE W/BUILDING AND |
| | POOL/DIMENSIONED BUILDING PLAN VIEW DRAWING SHOWING |
| | BUILDING AND LAYOUT INCLUSIVE OF ROOMS, DOORS AND |
| | WINDOWS, LOCATIONS OF GAS APPLIANCES, PIPE ROUTING AND |
| | METER. INDICATE ON THE PLAN IF THE TANKLESS WATER |
| | HEATER IS REPLACING AN EXISTING TANKLESS WATER HEATER |
| | OR IS IT REPLACING A STORAGE TANK TYPE WATER HEATER OR |
| | IS IT BEING ADDED TO THE EXISTING HOT WATER SYSTEM? |
| | INDICATE ON THE APPLICATION IN THE DESCRIPTION OF WORK. |
| | IF REPLACING OR SUPPLEMENTING, IDENTIFY AND SHOW |
| | LOCATION OF THE EXISTING WATER HEATER. SHOW HORIZONTAL |
| | DISTANCE FROM ANY OUTSIDE APPLIANCE EXHAUST TO NEAREST |
| | WINDOW OR OPERATING DOOR. THE HOUSE PLAN CAN BE HAND |
| | DRAWN. A PLAN OF RECORD IS AVAILABLE FROM THE WPB |
| | BUILDING DEPARTMENT BY CONTACTING CRAIG MCPHERSON AT |
| | 561-805-6684; EMAIL [email protected]. |
| | 7.PROVIDE SHUTOFF VALVE ON THE SUPPLY SIDE OF THE METER |
| | PER FBC FG 409.2. |
| | 8.PER WPB FBC 107.2.1, ALL PLANS SHALL BE BEAR THE |
| | PRINTED NAME AND SIGNATURE OF THE DESIGNER. |
| | |
| | A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS TIME |
| | AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE GENERATED |
| | UPON THE REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | END OF COMMENTS. |
| | |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | ALL PLANS TO BE SIGNED AND SEALED BY THE DESIGNER AS |
| | REQUIRED BY FAC AND FS. |
| | ALL PLANS TO BE DIGITALLY SIGNED AND SEALED BY THE |
| | DESIGNER IN ACCORDANCE WITH FAC AND FS. |
| | |
| | |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | EMAIL [email protected] |
| | PHONE 561-246-0882 MOBILE |
| | |
| | 20041096 140 MONROE DR |
| | |
| | |