| 2020-05-06 11:11:04 | CODES IN EFFECT: |
| | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | |
| | PLAN REVIEW - BUILDING |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | PLANS EXAMINER ? BUILDING - PX3169 |
| | PLANS EXAMINER ? 1&2 FAMILY - SFP306 |
| | CONSTRUCTION SERVICES DIVISION |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | 1ST REVIEW |
| | |
| | RESULTS: DENIED |
| | |
| | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED |
| | BELOW. |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | 1. CUSTOM DOORS SHALL COMPLY WITH FBC SEC. 1709.5. (SEE |
| | EXCEPTION) |
| | |
| | |
| | 1709.5 EXTERIOR WINDOW AND DOOR ASSEMBLIES. |
| | THE DESIGN PRESSURE RATING OF EXTERIOR WINDOWS AND |
| | DOORS IN BUILDINGS SHALL BE DETERMINED IN ACCORDANCE |
| | WITH SECTION 1709.5.1 OR 1709.5.2. FOR THE PURPOSES OF |
| | THIS SECTION, THE REQUIRED DESIGN PRESSURE SHALL BE |
| | DETERMINED USING THE ALLOWABLE STRESS DESIGN LOAD |
| | COMBINATIONS OF SECTION 1605.3. |
| | |
| | EXCEPTION: CUSTOM DOORS. CUSTOM (ONE-OF-A-KIND) |
| | EXTERIOR DOOR ASSEMBLIES SHALL BE TESTED BY AN APPROVED |
| | TESTING LABORATORY OR BE DESIGNED AND ENGINEERED IN |
| | ACCORDANCE WITH ACCEPTED ENGINEERING PRACTICES BY A |
| | FLORIDA REGISTERED DESIGN PROFESSIONAL. SIGNED AND |
| | SEALED COPIES OF THE RATIONAL ANALYSIS AND CALCULATIONS |
| | SHALL BE PROVIDED TO THE BUILDING OFFICIAL UPON PERMIT |
| | APPLICATION. |
| | |