| 2020-08-12 11:58:37 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT-20041086 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) WHAT IS THE SYSTEM OPERATING PRESSURE AT THE METER? |
| | FBC FS 107.2.1 |
| | |
| | 2) WHAT IS THE SIZE OF THE PIPE LEAVING THE METER AND |
| | SUPPLYING THE SYSTEM? (WHERE THE NEW GAS LINE WILL BE |
| | TIED INTO THE EXISTING SYSTEM) FBC FS 107.2.1 |
| | |
| | 3) THE NEW LINE TO THE NEW GENERATOR IS CALLING FOR 1/2 |
| | LB PRESSURE BUT THE GAS TABLE SUPPLIED IN THIS |
| | SUBMITTAL PACKAGE IS FOR A 2 LB SYSTEM. PLEASE BE |
| | CONSISTENT. FBC FS 107.2.1 |
| | |
| | 4) THE CLOUDED AREAS OF THE DRAWING INDICATE THAT THIS |
| | IS NEW WORK. PLEASE SHOW FITTINGS, DRIP LEG AND |
| | REGULATORS FOR THIS NEW WORK. FBC FS 107.2.1 |
| | |
| | 5) TABLE 402.4(2) IS A LESS THAN 2 PSI WITH .5? |
| | PRESSURE DROP. PLEASE IDENTIFY WHERE THIS IS LOCATED ON |
| | THE DRAWING PROVIDED. FBC FS 107.2.1 |
| | |
| | 6) TABLE 402.4(19) IS FOR A 5 LB SYSTEM WITH CSST |
| | PIPING, IS THIS DESIGN FOR A 5 LB SYSTEM? THIS DRAWING |
| | DOES NOT SHOW ANY CSST PIPING. PLEASE REMOVE THIS IF IT |
| | IS A TYPO. FBC FS 107.2.1 |
| | |
| | 7) PLEASE PROVIDE OWNER?S NAME AND ADDRESS ON THE |
| | DRAWING. FBC FS 107.2.1 |
| | |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| | UPDATED. |
| | |
| | |