| 2020-06-03 10:42:20 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT -20041081 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) REMOVE OPTIONAL EQUIPMENT AND GAS LINE FROM THIS |
| | DRAWING OR INCLUDE THIS EQUIPMENT AND SPECS FOR THIS |
| | EQUIPMENT UNDER THIS PERMIT.. THE PERMIT WILL NOT BE |
| | FOR OPTIONAL EQUIPMENT. FBC FS 107.2.1 |
| | |
| | 2) IT APPEARS THAT YOU ARE CUTTING THE EXISTING PIPE |
| | CLOSE TO THE METER AND INSTALLING A ?T? FITTING. PLEASE |
| | PROVIDE THE TYPE OF MATERIAL FOR EXISTING GAS PIPE IN |
| | THIS LOCATION. PLEASE ALSO SHOW THE SIZE OF THIS PIPE, |
| | PLEASE UNDERSTAND THAT THIS SHORT PIPE MUST BE SIZED |
| | FOR THE ENTIRE GAS LOAD OF THE METER AS IT IS SUPPLYING |
| | THE EXISTING HOUSE LOAD PLUS THE NEW LOAD OF THE |
| | GENERATOR. PLEASE INCLUDE THE GAS TABLE THAT IS USED TO |
| | SIZE THIS PIPE. FBC FG 402. |
| | |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| | UPDATED. |
| | |
| | |