Plan Review Notes
Plan Review Notes For Permit 20041077
Permit Number 20041077
Review Stop G
Sequence Number 2
Notes
Date Text
2020-11-03 16:52:032ND REVIEW FBC-2017 RES. FUEL GAS
 PERMIT- 20041077
 11/3/2020
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE REVISED GAS RISER DRAWING DOES NOT SHOW THE
 EXISTING RANGE AND POOL HEATER THAT WERE SHOWN ON THE
 FIRST SUBMITTED RISER DRAWING. PLEASE PROVIDE A
 COMPLETE RISER DRAWING THAT INCLUDES ALL EXISTING AND
 NEW INTERIOR OR EXTERIOR APPLIANCES, AND ALL EXISTING
 AND NEW PIPING- SECTIONS G2412.3 & G2412.4 FBC RES.
 SHOW THE LOCATION OF THE TEES FOR THE INTERIOR BRANCH
 PIPE AND POOL HEATER RUNS, AND THE LOCATIONS OF THE
 REQUIRED STEP-DOWN REGULATORS- SECTION G2421.1 &
 2421.2.
  
 A) SHOW THE CORRECT TOTAL LOAD AND THE INDIVIDUAL LOADS
 OF THE SYSTEM- SECTIONS G2412.3, G2412.4, & G2413.2 FBC
 RES.
  
 B) PROVIDE THE TOTAL LENGTH DEVELOPED LENGTH OF THE
 PIPING FROM THE METER TO THE MOST REMOTE OUTLET, AND
 THE INDIVIDUAL BRANCH AND CUT PIPE LENGTHS- SECTIONS
 G2413.4.1 AND G2413.4.2 FBC RES.
  
 C) SHOW THE REQUIRED PIPE UNIONS FOR RIGID PIPING
 WITHIN 1 FT. OF EITHER SIDE THE STEP DOWN REGULATOR-
 SECTION G2421.2(7) FBC RES.
  
 D) THE GENERATOR SPECS SUBMITTED UNDER PERMIT 20041076
 INDICATE A FULL LOAD CAPACITY OF 306,000 BTUH. PLEASE
 CORRECT THE LOAD SHOWN ON THE RISER.
  
 E) THE GAS RISER DRAWING DOES NOT BEAR THE SIGNATURE OF
 ROBERT ST. MARY WHO IS LISTED ON THE APPLICATION AS THE
 FL. LICENSED GAS CONTRACTOR- SECTION 107.2.1 WPB, AND
 FLORIDA STATUTES 471.003(2)(H) & 471.025.
  
 F) PLACE A NOTE TO INDICATE THE MINIMUM 10 FT.
 CLEARANCE FROM THE LOCATION OF THE GENERATOR TO
 MECHANICAL AND GRAVITY AIR INTAKES INTO THE BUILDING-
 SECTION-R303.5.1 FBC RES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  