| 2020-11-03 16:52:03 | 2ND REVIEW FBC-2017 RES. FUEL GAS |
| | PERMIT- 20041077 |
| | 11/3/2020 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THE REVISED GAS RISER DRAWING DOES NOT SHOW THE |
| | EXISTING RANGE AND POOL HEATER THAT WERE SHOWN ON THE |
| | FIRST SUBMITTED RISER DRAWING. PLEASE PROVIDE A |
| | COMPLETE RISER DRAWING THAT INCLUDES ALL EXISTING AND |
| | NEW INTERIOR OR EXTERIOR APPLIANCES, AND ALL EXISTING |
| | AND NEW PIPING- SECTIONS G2412.3 & G2412.4 FBC RES. |
| | SHOW THE LOCATION OF THE TEES FOR THE INTERIOR BRANCH |
| | PIPE AND POOL HEATER RUNS, AND THE LOCATIONS OF THE |
| | REQUIRED STEP-DOWN REGULATORS- SECTION G2421.1 & |
| | 2421.2. |
| | |
| | A) SHOW THE CORRECT TOTAL LOAD AND THE INDIVIDUAL LOADS |
| | OF THE SYSTEM- SECTIONS G2412.3, G2412.4, & G2413.2 FBC |
| | RES. |
| | |
| | B) PROVIDE THE TOTAL LENGTH DEVELOPED LENGTH OF THE |
| | PIPING FROM THE METER TO THE MOST REMOTE OUTLET, AND |
| | THE INDIVIDUAL BRANCH AND CUT PIPE LENGTHS- SECTIONS |
| | G2413.4.1 AND G2413.4.2 FBC RES. |
| | |
| | C) SHOW THE REQUIRED PIPE UNIONS FOR RIGID PIPING |
| | WITHIN 1 FT. OF EITHER SIDE THE STEP DOWN REGULATOR- |
| | SECTION G2421.2(7) FBC RES. |
| | |
| | D) THE GENERATOR SPECS SUBMITTED UNDER PERMIT 20041076 |
| | INDICATE A FULL LOAD CAPACITY OF 306,000 BTUH. PLEASE |
| | CORRECT THE LOAD SHOWN ON THE RISER. |
| | |
| | E) THE GAS RISER DRAWING DOES NOT BEAR THE SIGNATURE OF |
| | ROBERT ST. MARY WHO IS LISTED ON THE APPLICATION AS THE |
| | FL. LICENSED GAS CONTRACTOR- SECTION 107.2.1 WPB, AND |
| | FLORIDA STATUTES 471.003(2)(H) & 471.025. |
| | |
| | F) PLACE A NOTE TO INDICATE THE MINIMUM 10 FT. |
| | CLEARANCE FROM THE LOCATION OF THE GENERATOR TO |
| | MECHANICAL AND GRAVITY AIR INTAKES INTO THE BUILDING- |
| | SECTION-R303.5.1 FBC RES. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |