2020-08-29 13:04:34IN SIZING A GAS LINE FOR THE ADDITION OF A NEW
 APPLIANCE WE MUST LOOK AT THE EXISTING GAS SYSTEM. IF
 WE CHANGE THE GAS PIPING SYSTEM WE MUST MAKE SURE THAT
 THE ENTIRE SYSTEM CAN CONTINUE TO OPERATE CORRECTLY. WE
 CANNOT JUST TIE INTO AN EXISTING GAS LINE WITHOUT
 RESIZING THE ENTIRE SYSTEM. BELOW IS A LIST OF ITEMS
 THAT MUST BE INCLUDED IN THE SUBMITTALS FOR AN ADDITION
 OF AN APPLIANCE TO AN EXISTING GAS LINE.
  
 1) PROVIDE THE EXISTING SYSTEMS OPERATING PRESSURE.
  
 2) IF NEEDED TO UPGRADE THE OPERATING PRESSURE, PLEASE
 PROVIDE NEW OPERATING PRESSURE OF SYSTEM.
  
 3) PROVIDE THE NEW LONGEST LENGTH USED TO SIZE THE
 ENTIRE GAS SYSTEM.
  
 4) PROVIDE THE GAS TABLES THAT WERE USED TO SIZE THE
 ENTIRE GAS SYSTEM.
  
 5) PROVIDE A CLEAR DIAGRAM SHOWING THE ATTACHMENT POINT
 WHERE THE NEW LINE CONNECTS TO THE EXISTING GAS LINE.
 PLEASE KEEP IN MIND THAT THE PIPING FROM THE GAS METER
 TO THIS CONNECTION POINT MUST BE SIZED FOR THE ENTIRE
 GAS SYSTEM, INCLUDING BOTH THE EXISTING GAS LINE AND
 THE NEW GAS LINE TO THE NEW APPLIANCE.
  
 6) PROVIDE A LEGIBLE DRAWING SHOWING EACH APPLIANCE,
 PIPE SIZES, TYPE OF MATERIAL FOR PIPING, DISTANCES,
 SHUT OFF VALVES AND REGULATORS. THE DRAWING MUST
 INCLUDE CUSTOMERS NAME AND ADDRESS OF PROJECT. THE
 DESIGNER OF THE SYSTEM MUST SIGN AND DATE EACH DRAWING.
  
 7) PROVIDE SPEC SHEETS FOR ALL NEW APPLIANCES WITH THE
 BTU?S OF EACH APPLIANCE CLEARLY MARKED.
  
 8) PROVIDE SPEC SHEETS FOR NEW REGULATORS INSTALLED.
 FBC FS 107.2.1
  