2020-07-09 13:28:112ND REVIEW FBC-2017 RES. PLUMBING
 PERMIT- 20041072
 7/9/2020
  
 CODES IN EFFECT:
  
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET 10A: THE FLAT LINE DRAIN DRAWING FOR THE
 MASTER BATHROOM AND THE SANITARY ISOMETRIC DO NOT
 MATCH. THE RISER APPEARS TO SHOW THE VENT STACK AT THE
 LAVATORIES CONNECTING DOWN STREAM OF THE OTHER BATH
 FIXTURES WHICH PER THE FLOOR PLAN LAYOUT WOULD NOT BE
 POSSIBLE. PLEASE REFER TO SECTIONS P3108.1 & P3108.1.2
 FBC P FOR PROPER WET VENTING OF THE SYSTEM AND CORRECT
 THE ISOMETRIC DRAWING.
  
 2) 10A, KITCHEN RISER: SHOW THE WATER SUPPLY AND DRAIN
 CONNECTIONS TO THE DISHWASHER, AND THE SUPPLY LINE TO
 THE REFRIGERATOR ICE MAKER. INDICATE HOW THE DISHWASHER
 SUPPLY LINE WILL BE PROTECTED FROM BACKFLOW PER
 SECTIONS P 2717.1 AND P2902.1 FBC RES., AND PROVIDE A
 WATER HAMMER ARRESTOR AND BACKFLOW PREVENTER FOR THE
 SUPPLY LINE TO THE ICE MAKER- SEE SECTIONS 2902.1 AND
 P2903.5.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  