| 2020-07-09 13:28:11 | 2ND REVIEW FBC-2017 RES. PLUMBING |
| | PERMIT- 20041072 |
| | 7/9/2020 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET 10A: THE FLAT LINE DRAIN DRAWING FOR THE |
| | MASTER BATHROOM AND THE SANITARY ISOMETRIC DO NOT |
| | MATCH. THE RISER APPEARS TO SHOW THE VENT STACK AT THE |
| | LAVATORIES CONNECTING DOWN STREAM OF THE OTHER BATH |
| | FIXTURES WHICH PER THE FLOOR PLAN LAYOUT WOULD NOT BE |
| | POSSIBLE. PLEASE REFER TO SECTIONS P3108.1 & P3108.1.2 |
| | FBC P FOR PROPER WET VENTING OF THE SYSTEM AND CORRECT |
| | THE ISOMETRIC DRAWING. |
| | |
| | 2) 10A, KITCHEN RISER: SHOW THE WATER SUPPLY AND DRAIN |
| | CONNECTIONS TO THE DISHWASHER, AND THE SUPPLY LINE TO |
| | THE REFRIGERATOR ICE MAKER. INDICATE HOW THE DISHWASHER |
| | SUPPLY LINE WILL BE PROTECTED FROM BACKFLOW PER |
| | SECTIONS P 2717.1 AND P2902.1 FBC RES., AND PROVIDE A |
| | WATER HAMMER ARRESTOR AND BACKFLOW PREVENTER FOR THE |
| | SUPPLY LINE TO THE ICE MAKER- SEE SECTIONS 2902.1 AND |
| | P2903.5. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |