Plan Review Notes
Plan Review Notes For Permit 20041072
Permit Number 20041072
Review Stop E
Sequence Number 1
Notes
Date Text
2020-05-19 11:36:10ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) CONTRACTOR NEEDED, OWNER IS HOME STEADED IN THE
 COUNTY.
  
 2) PANEL LOCATION IS IN GARAGE OR LIVING ROOM NEED TO
 KNOW WHICH. IF IN GARAGE THE WORKING CLEARACNES ARE IN
 VIOLATION OF 110.26
  
 3) SMOKE ALARMS ARE REQUIRED IN THE EXISTING PORTION OF
 HOME.
 PROVIDE SMOKE/CO ALARMS IN EACH LOCATION REQUIRED PER
 CODE. SHOW ON PLAN ALL EXISTING ALARMS. IF NONE ARE
 EXISTING OR NOT TO CODE, SHOW AS NEW INSTALLATIONS. FBC
 R314.3, FBC 107.2.1
  
 4) OUTLET SPACING IS REQUIRED IN NEW AREAS OF ADDITION
 ROOM TO THE RIGHT OF THE KITCHEN IS LACKING OUTLET
 SPACING.
  
 5) ALL KITCHEN COUNTER OUTLETS TO BE GFCI
 PROTECTED.210.8
 E3902.6 KITCHEN RECEPTACLES. 125-VOLT, SINGLE-PHASE,
 15- AND 20-AMPERE RECEPTACLES THAT SERVE COUNTERTOP
 SURFACES SHALL HAVE GROUND-FAULT CIRCUIT-INTERRUPTER
 PROTECTION FOR PERSONNEL. [210.8(A)(6)].