| Plan Review Notes For Permit 20041072 |
| Permit Number |
20041072 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-05-19 11:36:10 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | 1) CONTRACTOR NEEDED, OWNER IS HOME STEADED IN THE | | | COUNTY. | | | | | | 2) PANEL LOCATION IS IN GARAGE OR LIVING ROOM NEED TO | | | KNOW WHICH. IF IN GARAGE THE WORKING CLEARACNES ARE IN | | | VIOLATION OF 110.26 | | | | | | 3) SMOKE ALARMS ARE REQUIRED IN THE EXISTING PORTION OF | | | HOME. | | | PROVIDE SMOKE/CO ALARMS IN EACH LOCATION REQUIRED PER | | | CODE. SHOW ON PLAN ALL EXISTING ALARMS. IF NONE ARE | | | EXISTING OR NOT TO CODE, SHOW AS NEW INSTALLATIONS. FBC | | | R314.3, FBC 107.2.1 | | | | | | 4) OUTLET SPACING IS REQUIRED IN NEW AREAS OF ADDITION | | | ROOM TO THE RIGHT OF THE KITCHEN IS LACKING OUTLET | | | SPACING. | | | | | | 5) ALL KITCHEN COUNTER OUTLETS TO BE GFCI | | | PROTECTED.210.8 | | | E3902.6 KITCHEN RECEPTACLES. 125-VOLT, SINGLE-PHASE, | | | 15- AND 20-AMPERE RECEPTACLES THAT SERVE COUNTERTOP | | | SURFACES SHALL HAVE GROUND-FAULT CIRCUIT-INTERRUPTER | | | PROTECTION FOR PERSONNEL. [210.8(A)(6)]. |
|