Plan Review Notes
Plan Review Notes For Permit 20041058
Permit Number 20041058
Review Stop P
Sequence Number 3
Notes
Date Text
2021-03-16 10:37:263RD REVIEW FBC-2017 PLUMBING
 PERMIT- 20041058
 3/16/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
 COMMENTS FROM THE 1ST AND 2ND REVIEWS LISTED BELOW HAVE
 NOT BEEN COMPLETELY ADDRESSED. NOTES IN CAPS HAVE BEEN
 ADDED FOR FURTHER CLARIFICATION.
  
 2) AR1 & A1.3: PROVIDE PLUMBING FIXTURE CALCULATIONS IN
 ACCORDANCE WITH TABLE 403.3 FBC P. PROVIDE A SCHEDULE
 INDICATING THE REQUIRED AND PROVIDED PLUMBING FIXTURES
 FOR THE A2 OCCUPANCY. PLEASE NOTE THAT THE PLANS DO NOT
 INDICATE DRINKING FOUNTAINS, OR A SERVICE SINK ARE
 EITHER EXISTING OR PROPOSED. REFER TO SECTION 211.1-
 2113 FBC ACC FOR ACCESSIBLE DRINKING FOUNTAIN
 REQUIREMENTS. SHEETS AR1 & A1.3: PLEASE INCLUDE THE
 REQUIRED SERVICE SINK AND DRINKING FOUNTAIN IN THE
 FIXTURE CALCULATION SCHEDULE. IF THE INTENTION IS TO
 PROVIDE DRINKING WATER TO CUSTOMERS IN A CONTAINER FREE
 OF CHARGE BY REQUEST PER SECTION 410.4 SUBSTITUTION,
 PLEASE PROVIDE A NOTE IN THE SCHEDULE TO SHOW
 COMPLIANCE.
  
 3) A1.3: PROVIDE A WATER RISER DRAWING FOR THE
 RESTROOMS SHOWING PIPE SIZES, LOCATIONS OF SHUTOFF
 VALVES, WATER HAMMER ARRESTORS, BACKFLOW PREVENTERS,
 MIXING VALVES ETC.- SECTION 107.3.5.1.3 WPB AMENDMENTS
 TO THE FBC. SHEETS A1.6: WATER HAMMER ARRESTORS ARE
 REQUIRED FOR SUPPLY LINES TO THE WATER CLOSETS.
  
 4) A1.0 & A1.3: PROVIDE A SANITARY ISOMETRIC AND WATER
 RISER DRAWING FOR ALL PLUMBING ALTERATIONS IN THE
 KITCHEN/FOOD AND BEVERAGE PREP AREAS. SEE COMMENT ABOVE
 FOR WATER RISER REQUIREMENTS. SHEET A1.0, A1.6: THE MOP
 SINK DETAIL 1/A.16 IS MISLABELED AS FLOOR DRAIN/SINK
 PLAN. SHOW THE MOP SINK POINT OF CONNECTION TO THE
 GREASE WASTE LINE.
  
 5) A1.0 & A1.3: PROVIDE PLUMBING FLAT LINE DRAWINGS
 SHOWING THE SANITARY AND GREASE WASTE LINE RUNS, THE
 WATER DISTRIBUTION SYSTEM, AND POINTS OF CONNECTION.
 SHOW IN THE RISER AND FLAT LINE DRAWING HOW HOT WATER
 IS BEING SUPPLIED TO THE LAVATORIES, HAND SINK, AND ALL
 OTHER FIXTURES REQUIRING HOT OR TEMPERED WATER- SECTION
 107.2.1 WPB AND SECTION 607.1 FBC P. PLEASE NOTE THAT
 GREASE WASTE CALCULATIONS ARE REQUIRED IF ANY NEW
 FIXTURES ARE TO BE DRAINED INTO THE EXISTING SYSTEM-
 SECTION 1003.3.1. SHEETS A1.3 & A1.6: A REFER TO
 SECTION AND TABLE C404.5.1 FBC ENERGY CONSERVATION. THE
 MAXIMUM 2 FT. PIPING LENGTHS FROM THE SOURCE OF HOT
 WATER TO THE PUBLIC LAVATORIES IS EXCEEDED. PLEASE
 PROVIDE EITHER A RECIRCULATION LINE OR POINT OF USE
 WATER HEATERS AT THE LAV SINKS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  