| 2021-03-16 10:37:26 | 3RD REVIEW FBC-2017 PLUMBING |
| | PERMIT- 20041058 |
| | 3/16/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | COMMENTS FROM THE 1ST AND 2ND REVIEWS LISTED BELOW HAVE |
| | NOT BEEN COMPLETELY ADDRESSED. NOTES IN CAPS HAVE BEEN |
| | ADDED FOR FURTHER CLARIFICATION. |
| | |
| | 2) AR1 & A1.3: PROVIDE PLUMBING FIXTURE CALCULATIONS IN |
| | ACCORDANCE WITH TABLE 403.3 FBC P. PROVIDE A SCHEDULE |
| | INDICATING THE REQUIRED AND PROVIDED PLUMBING FIXTURES |
| | FOR THE A2 OCCUPANCY. PLEASE NOTE THAT THE PLANS DO NOT |
| | INDICATE DRINKING FOUNTAINS, OR A SERVICE SINK ARE |
| | EITHER EXISTING OR PROPOSED. REFER TO SECTION 211.1- |
| | 2113 FBC ACC FOR ACCESSIBLE DRINKING FOUNTAIN |
| | REQUIREMENTS. SHEETS AR1 & A1.3: PLEASE INCLUDE THE |
| | REQUIRED SERVICE SINK AND DRINKING FOUNTAIN IN THE |
| | FIXTURE CALCULATION SCHEDULE. IF THE INTENTION IS TO |
| | PROVIDE DRINKING WATER TO CUSTOMERS IN A CONTAINER FREE |
| | OF CHARGE BY REQUEST PER SECTION 410.4 SUBSTITUTION, |
| | PLEASE PROVIDE A NOTE IN THE SCHEDULE TO SHOW |
| | COMPLIANCE. |
| | |
| | 3) A1.3: PROVIDE A WATER RISER DRAWING FOR THE |
| | RESTROOMS SHOWING PIPE SIZES, LOCATIONS OF SHUTOFF |
| | VALVES, WATER HAMMER ARRESTORS, BACKFLOW PREVENTERS, |
| | MIXING VALVES ETC.- SECTION 107.3.5.1.3 WPB AMENDMENTS |
| | TO THE FBC. SHEETS A1.6: WATER HAMMER ARRESTORS ARE |
| | REQUIRED FOR SUPPLY LINES TO THE WATER CLOSETS. |
| | |
| | 4) A1.0 & A1.3: PROVIDE A SANITARY ISOMETRIC AND WATER |
| | RISER DRAWING FOR ALL PLUMBING ALTERATIONS IN THE |
| | KITCHEN/FOOD AND BEVERAGE PREP AREAS. SEE COMMENT ABOVE |
| | FOR WATER RISER REQUIREMENTS. SHEET A1.0, A1.6: THE MOP |
| | SINK DETAIL 1/A.16 IS MISLABELED AS FLOOR DRAIN/SINK |
| | PLAN. SHOW THE MOP SINK POINT OF CONNECTION TO THE |
| | GREASE WASTE LINE. |
| | |
| | 5) A1.0 & A1.3: PROVIDE PLUMBING FLAT LINE DRAWINGS |
| | SHOWING THE SANITARY AND GREASE WASTE LINE RUNS, THE |
| | WATER DISTRIBUTION SYSTEM, AND POINTS OF CONNECTION. |
| | SHOW IN THE RISER AND FLAT LINE DRAWING HOW HOT WATER |
| | IS BEING SUPPLIED TO THE LAVATORIES, HAND SINK, AND ALL |
| | OTHER FIXTURES REQUIRING HOT OR TEMPERED WATER- SECTION |
| | 107.2.1 WPB AND SECTION 607.1 FBC P. PLEASE NOTE THAT |
| | GREASE WASTE CALCULATIONS ARE REQUIRED IF ANY NEW |
| | FIXTURES ARE TO BE DRAINED INTO THE EXISTING SYSTEM- |
| | SECTION 1003.3.1. SHEETS A1.3 & A1.6: A REFER TO |
| | SECTION AND TABLE C404.5.1 FBC ENERGY CONSERVATION. THE |
| | MAXIMUM 2 FT. PIPING LENGTHS FROM THE SOURCE OF HOT |
| | WATER TO THE PUBLIC LAVATORIES IS EXCEEDED. PLEASE |
| | PROVIDE EITHER A RECIRCULATION LINE OR POINT OF USE |
| | WATER HEATERS AT THE LAV SINKS. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |