Plan Review Notes
Plan Review Notes For Permit 20041058
Permit Number 20041058
Review Stop P
Sequence Number 2
Notes
Date Text
2020-09-15 11:06:552ND REVIEW FBC-2017 PLUMBING
 PERMIT- 20041058
 9/15/2020
  
 CODES IN EFFECT:
  
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
 COMMENTS FROM THE 1ST REVIEW LISTED BELOW HAVE NOT BEEN
 COMPLETELY ADDRESSED. ADDITIONAL NOTES IN CAPS HAVE
 BEEN ADDED TO THOSE COMMENTS- PLEASE COMPLY.
  
 2) AR1 & A1.3: PROVIDE PLUMBING FIXTURE CALCULATIONS IN
 ACCORDANCE WITH TABLE 403.3 FBC P. PROVIDE A SCHEDULE
 INDICATING THE REQUIRED AND PROVIDED PLUMBING FIXTURES
 FOR THE A2 OCCUPANCY. PLEASE NOTE THAT THE PLANS DO NOT
 INDICATE DRINKING FOUNTAINS, OR A SERVICE SINK ARE
 EITHER EXISTING OR PROPOSED. REFER TO SECTION 211.1-
 2113 FBC ACC FOR ACCESSIBLE DRINKING FOUNTAIN
 REQUIREMENTS. SHEETS AR1 & A1.3: PLEASE INCLUDE THE
 REQUIRED SERVICE SINK AND DRINKING FOUNTAIN IN THE
 FIXTURE CALCULATION SCHEDULE. IF THE INTENTION IS TO
 PROVIDE DRINKING WATER TO CUSTOMERS IN A CONTAINER FREE
 OF CHARGE BY REQUEST PER SECTION 410.4 SUBSTITUTION,
 PLEASE PROVIDE A NOTE IN THE SCHEDULE TO SHOW
 COMPLIANCE.
  
 3) A1.3: PROVIDE A WATER RISER DRAWING FOR THE
 RESTROOMS SHOWING PIPE SIZES, LOCATIONS OF SHUTOFF
 VALVES, WATER HAMMER ARRESTORS, BACKFLOW PREVENTERS,
 MIXING VALVES ETC.- SECTION 107.3.5.1.3 WPB AMENDMENTS
 TO THE FBC. SHEETS A1.6: WATER HAMMER ARRESTORS ARE
 REQUIRED FOR SUPPLY LINES TO THE WATER CLOSET AUTO
 FLUSH VALVES AND THE URINAL- SECTION 604.9 FBC P.
 PLEASE SHOW THEIR LOCATIONS IN THE WATER DIAGRAMS.
  
 4) A1.0 & A1.3: PROVIDE A SANITARY ISOMETRIC AND WATER
 RISER DRAWING FOR ALL PLUMBING ALTERATIONS IN THE
 KITCHEN/FOOD AND BEVERAGE PREP AREAS. SEE COMMENT ABOVE
 FOR WATER RISER REQUIREMENTS. SHEET A1.0, A1.6: SHOW
 THE BEFORE AND AFTER LOCATIONS OF THE RELOCATED
 HANDSINK AND THE MOP SINK. SHOW A FLAT LINE DRAWING
 THAT SHOWS THE POINT OF CONNECTIONS OF THE DRAINS TO
 THE GREASE WASTE LINE. IT IS NOT CLEAR IF THE MOP SINK
 IS A NEW INSTALLATION OR A REPLACEMENT. PLEASE NOTE
 THAT REVISED GREASE WASTE CALULATIONS MUST PROVIDED FOR
 NEW GREASE WASTE LOADS DRAINING INTO THE SYSTEM-
 SECTION 1003.3 FBC P. PROVIDE A SLAB REPAIR DETAIL-
 SECTION 107.2.1 WPB.
  
 5) A1.0 & A1.3: PROVIDE PLUMBING FLAT LINE DRAWINGS
 SHOWING THE SANITARY AND GREASE WASTE LINE RUNS, THE
 WATER DISTRIBUTION SYSTEM, AND POINTS OF CONNECTION.
 SHOW IN THE RISER AND FLAT LINE DRAWING HOW HOT WATER
 IS BEING SUPPLIED TO THE LAVATORIES, HAND SINK, AND ALL
 OTHER FIXTURES REQUIRING HOT OR TEMPERED WATER- SECTION
 107.2.1 WPB AND SECTION 607.1 FBC P. PLEASE NOTE THAT
 GREASE WASTE CALCULATIONS ARE REQUIRED IF ANY NEW
 FIXTURES ARE TO BE DRAINED INTO THE EXISTING SYSTEM-
 SECTION 1003.3.1. SHEETS A1.3 & A1.6: THE PLANS DO NOT
 SHOW HOW HOT WATER IS BEING SUPPLIED TO THE FIXTURES.
 SHOW THE LOCATION OF THE EXISTING WATER HEATER AND
 PROVIDE A SCOPE OF WORK FOR THE APPLIANCE- EXISTING OR
 TO BE REPLACED? VERIFY THAT THE DISTANCE FROM THE WATER
 HEATER TO THE MOST REMOTE FIXTURE REQUIRING HOT WATER
 DOES NOT EXCEED 50 FT. OR PROVIDE A RECIRCULATION LINE-
 SECTION 607.2 FBC P.
  
 7) A1.3: PROVIDE A PLUMBING FIXTURE AND DEVICE SCHEDULE
 THAT INCLUDES THE RESTROOMS AND KITCHEN AREA- SECTION
 107.2.1 WPB & SECTION 405.9 FBC P. SHEET A1.6: THE MOP
 SINK AND FLOOR DRAIN WERE NOT INCLUDED IN THE SCHEDULE.
 A DEVICE SCHEDULE WAS NOT PROVIDED.
  
 8) A1.3: THE MEN'S TOILET ROOM DOOR SHALL NOT SWING
 INTO THE CLEAR FLOOR SPACE OF THE URINAL PER SECTION-
 603.2.3 FBC ACC. SHEET A1.3: THE PLAN SHOWS NO CHANGE
 TO THE DOOR SWINGING INTO THE CLEAR FLOOR SPACE OF THE
 URINAL.
  
 9) PLEASE PROVIDE A PLUMBING SUB-PERMIT APPLICATION-
 SECTION 105.1 WPB AMENDMENTS TO THE FBC-17.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  