| Date |
Text |
| 2020-09-15 11:06:55 | 2ND REVIEW FBC-2017 PLUMBING |
| | PERMIT- 20041058 |
| | 9/15/2020 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | COMMENTS FROM THE 1ST REVIEW LISTED BELOW HAVE NOT BEEN |
| | COMPLETELY ADDRESSED. ADDITIONAL NOTES IN CAPS HAVE |
| | BEEN ADDED TO THOSE COMMENTS- PLEASE COMPLY. |
| | |
| | 2) AR1 & A1.3: PROVIDE PLUMBING FIXTURE CALCULATIONS IN |
| | ACCORDANCE WITH TABLE 403.3 FBC P. PROVIDE A SCHEDULE |
| | INDICATING THE REQUIRED AND PROVIDED PLUMBING FIXTURES |
| | FOR THE A2 OCCUPANCY. PLEASE NOTE THAT THE PLANS DO NOT |
| | INDICATE DRINKING FOUNTAINS, OR A SERVICE SINK ARE |
| | EITHER EXISTING OR PROPOSED. REFER TO SECTION 211.1- |
| | 2113 FBC ACC FOR ACCESSIBLE DRINKING FOUNTAIN |
| | REQUIREMENTS. SHEETS AR1 & A1.3: PLEASE INCLUDE THE |
| | REQUIRED SERVICE SINK AND DRINKING FOUNTAIN IN THE |
| | FIXTURE CALCULATION SCHEDULE. IF THE INTENTION IS TO |
| | PROVIDE DRINKING WATER TO CUSTOMERS IN A CONTAINER FREE |
| | OF CHARGE BY REQUEST PER SECTION 410.4 SUBSTITUTION, |
| | PLEASE PROVIDE A NOTE IN THE SCHEDULE TO SHOW |
| | COMPLIANCE. |
| | |
| | 3) A1.3: PROVIDE A WATER RISER DRAWING FOR THE |
| | RESTROOMS SHOWING PIPE SIZES, LOCATIONS OF SHUTOFF |
| | VALVES, WATER HAMMER ARRESTORS, BACKFLOW PREVENTERS, |
| | MIXING VALVES ETC.- SECTION 107.3.5.1.3 WPB AMENDMENTS |
| | TO THE FBC. SHEETS A1.6: WATER HAMMER ARRESTORS ARE |
| | REQUIRED FOR SUPPLY LINES TO THE WATER CLOSET AUTO |
| | FLUSH VALVES AND THE URINAL- SECTION 604.9 FBC P. |
| | PLEASE SHOW THEIR LOCATIONS IN THE WATER DIAGRAMS. |
| | |
| | 4) A1.0 & A1.3: PROVIDE A SANITARY ISOMETRIC AND WATER |
| | RISER DRAWING FOR ALL PLUMBING ALTERATIONS IN THE |
| | KITCHEN/FOOD AND BEVERAGE PREP AREAS. SEE COMMENT ABOVE |
| | FOR WATER RISER REQUIREMENTS. SHEET A1.0, A1.6: SHOW |
| | THE BEFORE AND AFTER LOCATIONS OF THE RELOCATED |
| | HANDSINK AND THE MOP SINK. SHOW A FLAT LINE DRAWING |
| | THAT SHOWS THE POINT OF CONNECTIONS OF THE DRAINS TO |
| | THE GREASE WASTE LINE. IT IS NOT CLEAR IF THE MOP SINK |
| | IS A NEW INSTALLATION OR A REPLACEMENT. PLEASE NOTE |
| | THAT REVISED GREASE WASTE CALULATIONS MUST PROVIDED FOR |
| | NEW GREASE WASTE LOADS DRAINING INTO THE SYSTEM- |
| | SECTION 1003.3 FBC P. PROVIDE A SLAB REPAIR DETAIL- |
| | SECTION 107.2.1 WPB. |
| | |
| | 5) A1.0 & A1.3: PROVIDE PLUMBING FLAT LINE DRAWINGS |
| | SHOWING THE SANITARY AND GREASE WASTE LINE RUNS, THE |
| | WATER DISTRIBUTION SYSTEM, AND POINTS OF CONNECTION. |
| | SHOW IN THE RISER AND FLAT LINE DRAWING HOW HOT WATER |
| | IS BEING SUPPLIED TO THE LAVATORIES, HAND SINK, AND ALL |
| | OTHER FIXTURES REQUIRING HOT OR TEMPERED WATER- SECTION |
| | 107.2.1 WPB AND SECTION 607.1 FBC P. PLEASE NOTE THAT |
| | GREASE WASTE CALCULATIONS ARE REQUIRED IF ANY NEW |
| | FIXTURES ARE TO BE DRAINED INTO THE EXISTING SYSTEM- |
| | SECTION 1003.3.1. SHEETS A1.3 & A1.6: THE PLANS DO NOT |
| | SHOW HOW HOT WATER IS BEING SUPPLIED TO THE FIXTURES. |
| | SHOW THE LOCATION OF THE EXISTING WATER HEATER AND |
| | PROVIDE A SCOPE OF WORK FOR THE APPLIANCE- EXISTING OR |
| | TO BE REPLACED? VERIFY THAT THE DISTANCE FROM THE WATER |
| | HEATER TO THE MOST REMOTE FIXTURE REQUIRING HOT WATER |
| | DOES NOT EXCEED 50 FT. OR PROVIDE A RECIRCULATION LINE- |
| | SECTION 607.2 FBC P. |
| | |
| | 7) A1.3: PROVIDE A PLUMBING FIXTURE AND DEVICE SCHEDULE |
| | THAT INCLUDES THE RESTROOMS AND KITCHEN AREA- SECTION |
| | 107.2.1 WPB & SECTION 405.9 FBC P. SHEET A1.6: THE MOP |
| | SINK AND FLOOR DRAIN WERE NOT INCLUDED IN THE SCHEDULE. |
| | A DEVICE SCHEDULE WAS NOT PROVIDED. |
| | |
| | 8) A1.3: THE MEN'S TOILET ROOM DOOR SHALL NOT SWING |
| | INTO THE CLEAR FLOOR SPACE OF THE URINAL PER SECTION- |
| | 603.2.3 FBC ACC. SHEET A1.3: THE PLAN SHOWS NO CHANGE |
| | TO THE DOOR SWINGING INTO THE CLEAR FLOOR SPACE OF THE |
| | URINAL. |
| | |
| | 9) PLEASE PROVIDE A PLUMBING SUB-PERMIT APPLICATION- |
| | SECTION 105.1 WPB AMENDMENTS TO THE FBC-17. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |