| Plan Review Notes For Permit 20041058 |
| Permit Number |
20041058 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2020-09-14 11:31:29 | 2ND REVIEW COMMENTS | | | | | | | | | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | | | | THE COOLER DOORS ARE WITHIN THE MEANS OF EGRESS, THEY | | | ARE THE ONLY WAY OUT AND THE TWO INTERIOR DOORS SHALL | | | BE IDENTIFIED AND MARKED AS AN EXIT. | | | | | | BOTH DOORS ARE INDICATED AS # 9. | | | | | | THE EXTERIOR DOORS MARKED AS 3A AND 9 WOULD NOT BE | | | REQUIRED TO BE MARKED AS EXIT. | | | | | | | | | | | | THE BELOW PREVIOUS COMMENTS A RE-SUBMITTED: | | | | | | | | | 1) SHEET A 1.0 - AT THE OUSIDE OF THE NEW COOLER THERE | | | APPEARS TO BE 2 DOORS # 3A AND # 9. | | | | | | IS THIS DOOR PROPOSED AS AN EXIT DOOR FROM THE COOLER? | | | IF SO, PLEASE PROVIDE FOR COMPLAINCE WITH NFPA 101, CH | | | 7 MEANS OF EGRESS. | | | | | | BOTH DOORS OPEN OUT AND THERE APPEARS TO BE A DEADBOLT | | | ON DOOR 3A (GENERAL NOTES- DOOR 3A # 2) | | | | | | | | | | | | 2) SHEET E 1 - THERE IS NO INDICATIONS OF EXIT SIGNAGE | | | WITHIN THE NEW COOLERS. | | | | | | | | | | | | | | | 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | | | | |
|