Plan Review Notes
Plan Review Notes For Permit 20041058
Permit Number 20041058
Review Stop P
Sequence Number 1
Notes
Date Text
2020-07-13 10:17:511ST REVIEW FBC-2017 PLUMBING
 PERMIT- 20041058
 7/13/2020
  
 CODES IN EFFECT:
  
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET AR1: PROVIDE A LIST OF CURRENT CODES AND
 STANDARDS USED IN THE DESIGN OF THE PROJECT. PLEASE
 NOTE THAT ALL PLANS SHALL BE DESIGNED IN ACCORDANCE
 WITH THE 2017 FLORIDA BUILDING CODES SIXTH EDITION.
 REFERENCES ARE MADE TO THE ADA ON SHEET A1.3. PLEASE
 NOTE THAT THE PLANS SHALL BE IN COMPLIANCE WITH THE
 FBC-17 ACCESSIBILITY CODE. PLEASE REVISE THE REFERENCES
 TO AVOID CONFUSION- SECTION 107.2.1 WPB.
  
 2) AR1 & A1.3: PROVIDE PLUMBING FIXTURE CALCULATIONS IN
 ACCORDANCE WITH TABLE 403.3 FBC P. PROVIDE A SCHEDULE
 INDICATING THE REQUIRED AND PROVIDED PLUMBING FIXTURES
 FOR THE A2 OCCUPANCY. PLEASE NOTE THAT THE PLANS DO NOT
 INDICATE DRINKING FOUNTAINS, OR A SERVICE SINK ARE
 EITHER EXISTING OR PROPOSED. REFER TO SECTION 211.1-
 2113 FBC ACC FOR ACCESSIBLE DRINKING FOUNTAIN
 REQUIREMENTS.
  
 3) A1.3: PROVIDE A WATER RISER DRAWING FOR THE
 RESTROOMS SHOWING PIPE SIZES, LOCATIONS OF SHUTOFF
 VALVES, WATER HAMMER ARRESTORS, BACKFLOW PREVENTERS,
 MIXING VALVES ETC.- SECTION 107.3.5.1.3 WPB AMENDMENTS
 TO THE FBC.
  
 4) A1.0 & A1.3: PROVIDE A SANITARY ISOMETRIC AND WATER
 RISER DRAWING FOR ALL PLUMBING ALTERATIONS IN THE
 KITCHEN/FOOD AND BEVERAGE PREP AREAS. SEE COMMENT ABOVE
 FOR WATER RISER REQUIREMENTS.
  
 5) A1.0 & A1.3: PROVIDE PLUMBING FLAT LINE DRAWINGS
 SHOWING THE SANITARY AND GREASE WASTE LINE RUNS, THE
 WATER DISTRIBUTION SYSTEM, AND POINTS OF CONNECTION.
 SHOW IN THE RISER AND FLAT LINE DRAWING HOW HOT WATER
 IS BEING SUPPLIED TO THE LAVATORIES, HAND SINK, AND ALL
 OTHER FIXTURES REQUIRING HOT OR TEMPERED WATER- SECTION
 107.2.1 WPB AND SECTION 607.1 FBC P. PLEASE NOTE THAT
 GREASE WASTE CALCULATIONS ARE REQUIRED IF ANY NEW
 FIXTURES ARE TO BE DRAINED INTO THE EXISTING SYSTEM-
 SECTION 1003.3.1.
  
 6) A1.3: TEMPERED WATER SHALL BE PROVIDED TO THE
 LAVATORY PER SECTION 416.5 FBC P. PLEASE NOTE THAT
 TEMPERED SHALL BE SUPPLIED THROUGH A WATER TEMPERATURE
 LIMITING DEVICE THAT CONFORMS TO ASSE 1070- SECTION
 607.1.2 FBC P.
  
 7) A1.3: PROVIDE A PLUMBING FIXTURE AND DEVICE SCHEDULE
 THAT INCLUDES THE RESTROOMS AND KITCHEN AREA- SECTION
 107.2.1 WPB & SECTION 405.9 FBC P.
  
 8) A1.3: THE MEN'S TOILET ROOM DOOR SHALL NOT SWING
 INTO THE CLEAR FLOOR SPACE OF THE URINAL PER SECTION-
 603.2.3 FBC ACC.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  