| 2020-07-13 10:17:51 | 1ST REVIEW FBC-2017 PLUMBING |
| | PERMIT- 20041058 |
| | 7/13/2020 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET AR1: PROVIDE A LIST OF CURRENT CODES AND |
| | STANDARDS USED IN THE DESIGN OF THE PROJECT. PLEASE |
| | NOTE THAT ALL PLANS SHALL BE DESIGNED IN ACCORDANCE |
| | WITH THE 2017 FLORIDA BUILDING CODES SIXTH EDITION. |
| | REFERENCES ARE MADE TO THE ADA ON SHEET A1.3. PLEASE |
| | NOTE THAT THE PLANS SHALL BE IN COMPLIANCE WITH THE |
| | FBC-17 ACCESSIBILITY CODE. PLEASE REVISE THE REFERENCES |
| | TO AVOID CONFUSION- SECTION 107.2.1 WPB. |
| | |
| | 2) AR1 & A1.3: PROVIDE PLUMBING FIXTURE CALCULATIONS IN |
| | ACCORDANCE WITH TABLE 403.3 FBC P. PROVIDE A SCHEDULE |
| | INDICATING THE REQUIRED AND PROVIDED PLUMBING FIXTURES |
| | FOR THE A2 OCCUPANCY. PLEASE NOTE THAT THE PLANS DO NOT |
| | INDICATE DRINKING FOUNTAINS, OR A SERVICE SINK ARE |
| | EITHER EXISTING OR PROPOSED. REFER TO SECTION 211.1- |
| | 2113 FBC ACC FOR ACCESSIBLE DRINKING FOUNTAIN |
| | REQUIREMENTS. |
| | |
| | 3) A1.3: PROVIDE A WATER RISER DRAWING FOR THE |
| | RESTROOMS SHOWING PIPE SIZES, LOCATIONS OF SHUTOFF |
| | VALVES, WATER HAMMER ARRESTORS, BACKFLOW PREVENTERS, |
| | MIXING VALVES ETC.- SECTION 107.3.5.1.3 WPB AMENDMENTS |
| | TO THE FBC. |
| | |
| | 4) A1.0 & A1.3: PROVIDE A SANITARY ISOMETRIC AND WATER |
| | RISER DRAWING FOR ALL PLUMBING ALTERATIONS IN THE |
| | KITCHEN/FOOD AND BEVERAGE PREP AREAS. SEE COMMENT ABOVE |
| | FOR WATER RISER REQUIREMENTS. |
| | |
| | 5) A1.0 & A1.3: PROVIDE PLUMBING FLAT LINE DRAWINGS |
| | SHOWING THE SANITARY AND GREASE WASTE LINE RUNS, THE |
| | WATER DISTRIBUTION SYSTEM, AND POINTS OF CONNECTION. |
| | SHOW IN THE RISER AND FLAT LINE DRAWING HOW HOT WATER |
| | IS BEING SUPPLIED TO THE LAVATORIES, HAND SINK, AND ALL |
| | OTHER FIXTURES REQUIRING HOT OR TEMPERED WATER- SECTION |
| | 107.2.1 WPB AND SECTION 607.1 FBC P. PLEASE NOTE THAT |
| | GREASE WASTE CALCULATIONS ARE REQUIRED IF ANY NEW |
| | FIXTURES ARE TO BE DRAINED INTO THE EXISTING SYSTEM- |
| | SECTION 1003.3.1. |
| | |
| | 6) A1.3: TEMPERED WATER SHALL BE PROVIDED TO THE |
| | LAVATORY PER SECTION 416.5 FBC P. PLEASE NOTE THAT |
| | TEMPERED SHALL BE SUPPLIED THROUGH A WATER TEMPERATURE |
| | LIMITING DEVICE THAT CONFORMS TO ASSE 1070- SECTION |
| | 607.1.2 FBC P. |
| | |
| | 7) A1.3: PROVIDE A PLUMBING FIXTURE AND DEVICE SCHEDULE |
| | THAT INCLUDES THE RESTROOMS AND KITCHEN AREA- SECTION |
| | 107.2.1 WPB & SECTION 405.9 FBC P. |
| | |
| | 8) A1.3: THE MEN'S TOILET ROOM DOOR SHALL NOT SWING |
| | INTO THE CLEAR FLOOR SPACE OF THE URINAL PER SECTION- |
| | 603.2.3 FBC ACC. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |