| 2020-06-15 15:39:30 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT-20040996 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PLEASE RESPOND TO THE 1ST CYCLE REVIEWER?S COMMENTS. |
| | |
| | 2) PLEASE SHOW THE CALCULATION OF WHERE THE 3000 CFM |
| | COMBUSTION AIR IS GOING TO BE TAKEN FOR THE RANGE. FBC |
| | FS 107.2.1 |
| | |
| | 3) PLEASE PROVIDE A DRAWING SHOWING THE ROOMS AND THE |
| | GAS LINES RUNNING THRU THE HOUSE. I CAN NOT TELL IF |
| | SOME OF THE PE IS BURIED UNDER THE HOME. FBC FS 107.2.1 |
| | |
| | 4) PLEASE REFINE THE DRAWING. I CAN NOT DISTINGUISH |
| | FROM THE ?SQUARE? HOW THIS GAS LINE IS RUNNING. WHERE |
| | IS THE REGULATOR LOCATION FOR THE RANGE? PLEASE SHOW |
| | THE REGULATOR FOR THE WATER HEATER. THE DRAWING NEEDS |
| | TO BE CLEAR AS TO THE DIRECTION OF THE GAS LINE. FBC FS |
| | 107.2.1 |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| | UPDATED. |
| | |
| | |