2020-06-15 15:39:301ST REVIEW FBC-2017 MECHANICAL
 PERMIT-20040996
  
 CODES IN EFFECT:
  
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE RESPOND TO THE 1ST CYCLE REVIEWER?S COMMENTS.
  
 2) PLEASE SHOW THE CALCULATION OF WHERE THE 3000 CFM
 COMBUSTION AIR IS GOING TO BE TAKEN FOR THE RANGE. FBC
 FS 107.2.1
  
 3) PLEASE PROVIDE A DRAWING SHOWING THE ROOMS AND THE
 GAS LINES RUNNING THRU THE HOUSE. I CAN NOT TELL IF
 SOME OF THE PE IS BURIED UNDER THE HOME. FBC FS 107.2.1
  
 4) PLEASE REFINE THE DRAWING. I CAN NOT DISTINGUISH
 FROM THE ?SQUARE? HOW THIS GAS LINE IS RUNNING. WHERE
 IS THE REGULATOR LOCATION FOR THE RANGE? PLEASE SHOW
 THE REGULATOR FOR THE WATER HEATER. THE DRAWING NEEDS
 TO BE CLEAR AS TO THE DIRECTION OF THE GAS LINE. FBC FS
 107.2.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  