Plan Review Notes
Plan Review Notes For Permit 20040996
Permit Number 20040996
Review Stop G
Sequence Number 1
Notes
Date Text
2020-05-14 13:29:30REVIEWED BY JERRY SMITH.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 NFPA 54 = NATIONAL FUEL GAS CODE
 NFPA 58 = LIQUIFIED PETROLEUM GAS CODE
 NFPA 96 = STANDARD FOR VENTILATION CONTROLAND FIRE
 PROTECTION OF COMMERCIAL COOKING OPERATIONS 2017
 NFPA 99 = HEALTH CARE FACILITIES CODE
 NFPA 99B = STANDARD FOR HYPERBARIC FACILITIES
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 20040996 237 EDGEWOOD DR
  
  
 GAS COMMENTS:DENIED
 1.SUBMIT CALCULATIONS FOR COMBUSTION AIR FOR THE RANGE
 PER FBC FG 304.1
 2.SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS
 METER / MP REGULATOR) TO THE MOST REMOTE OUTLET IN THE
 BUILDING AND / OR SYSTEM FBC FG 402.4.1, 402.4.2
 3.INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM(S)
 ON THE PLAN PER FBC FG 402.1, 402.4.3 THRU 402.6
 4.PER WPB FBC 107.2.1, SHOW PE TO GALVANIZED RIGID
 PIPING TRANSITION ON RISER DIAGRAM.
 5.PER WPB FBC 107.2.1, PROVIDE THE TABLE USED IN SIZING
 SCHEDULE 40 GALVANIZED PIPE
 (A) BETWEEN THE PE TRANSITION AND THE MP REGULATOR;
 NOTE THAT THE 70? DEVELOPED LENGTH FOR THE 2 PSI SYSTEM
 SHALL INCLUDE THE GALVANIZED PIPING. IF 70? IS NOT
 SUFFICIENT THEN PROVIDE UPDATED DEVELOPED LENGTH.
 (B) DOWNSTREAM OF MP REGULATOR(S). INDICATE ON THE PLAN
 THE DISTANCE FROM REGULATOR TO APPLIANCE.
 6.PER WPB FBC 107.2.1, PROVIDE DETAIL OF MP REGULATOR
 WITH SHUTOFF VALVE, UNION AND OTHER REQUIRED
 ACCESSORIES. COMPLY WITH FBC FG 410.2.
 7.SUBMIT MANUFACTURER?S SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY
 COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND FBC FG
 402.2, AND 301.3. GAS APPLIANCES SHALL BE LISTED AND
 LABELED. PLEASE NOTE, THE INSTALLATION MANUALS FOR ALL
 GAS APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME
 OF INSPECTION PER FBC FG 305.1.
 8.IS THE TANKLESS WATER HEATER LOCATED INDOORS OR
 OUTDOORS. PER WPB FBC 107.2.1, CLARIFY.
 10.PER WPB FBC 107.2.1, PROVIDE A DIMENSIONED PLAN VIEW
 DRAWING SHOWING BUILDING LAYOUT INCLUSIVE OF ROOMS,
 DOORS AND WINDOWS, LOCATIONS OF GAS APPLIANCES, PIPE
 ROUTING AND METER. INDICATE ON THE PLAN IF THE TANKLESS
 WATER HEATER IS REPLACING AN EXISTING TANKLESS WATER
 HEATER OR IS IT REPLACING A STORAGE TANK TYPE WATER
 HEATER OR IS IT BEING ADDED TO THE EXISTING HOT WATER
 SYSTEM? INDICATE ON THE APPLICATION IN THE DESCRIPTION
 OF WORK. IF REPLACING OR SUPPLEMENTING, IDENTIFY AND
 SHOW LOCATION OF THE EXISTING WATER HEATER. SHOW
 HORIZONTAL DISTANCE FROM ANY OUTSIDE APPLIANCE EXHAUST
 TO NEAREST WINDOW OR OPERATING DOOR. THE HOUSE PLAN CAN
 BE HAND DRAWN. A PLAN OF RECORD IS AVAILABLE FROM THE
 WPB BUILDING DEPARTMENT BY CONTACTING CRAIG MCPHERSON
 AT 561-805-6684; EMAIL [email protected].
 11.PER WPB FBC 107.2.1, SHOW LOCATION OF MP REGULATOR
 AND SHUT OFF VALVE FOR THE RANGE. ADDITIONALLY, SHOW
 APPLIANCE SHUTOFF VALVE FOR THE RANGE AS REQUIRED BY
 FBC FG 409.5.1.
 12.PROVIDE SHUTOFF VALVE ON THE SUPPLY SIDE OF THE
 METER PER FBC FG 409.2.
 13.PROVIDE DOCUMENTATION THAT REGULATORS INSTALLED ON
 THE EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR
 OUTDOOR INSTALLATION TO COMPLY WITH FBC FG 410.1.
  
 A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS TIME
 AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE GENERATED
 UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 END OF COMMENTS.
  
 PLUMBING PERMIT REQUIRED
 A PLUMBING PLAN HAS NOT BEEN INCLUDED IN THIS SUBMITTAL
 PACKAGE. A PLUMBING PLAN REVIEW HAS NOT BEEN PERFORMED
 AT THIS TIME. A SEPARATE PLUMBING PERMIT AND PLANS WILL
 BE REQUIRED FOR A CONTRACTOR TO PERFORM THE RELATED
 WORK. PROVIDE COMPLETE PLANS, APPLIANCE/ EQUIPMENT
 SPECIFICATIONS AND RISER DIAGRAMS THAT REFLECT THE
 ENTIRE SCOPE OF PLUMBING WORK TO BE DONE. WPB AMEND. TO
 FBC SEC. 107.2.1.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
 ALL PLANS TO BE SIGNED AND SEALED BY THE DESIGNER AS
 REQUIRED BY FAC AND FS.
 ALL PLANS TO BE DIGITALLY SIGNED AND SEALED BY THE
 DESIGNER IN ACCORDANCE WITH FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-246-0882 MOBILE
  