| 2020-11-03 16:41:11 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| | MANUAL REVISED 2017 |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH |
| | EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | 20040980 2417 SPRUCE AVE |
| | |
| | 4TH REVIEW |
| | PLUMBING COMMENTS: DENIED |
| | A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS |
| | REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW |
| | PROCESS BUT IS TYPICALLY ADDRESSED ON THE ARCHITECTURAL |
| | PLANS. ANY COMMENTS CONCERNING THESE REQUIREMENTS MUST |
| | BE SATISFACTORILY ADDRESSED PRIOR TO A PLUMBING REVIEW |
| | APPROVAL. |
| | |
| | 1.PER WPB FBC 107.2.1, PROVIDE NOTE ON S1-2 "PLUMBING |
| | FIXTURES AND WATER HEATER SHOWN IN TEA PREP AREA ARE |
| | EXISTING. SEE CLOSED PERMIT 20030394" AND SHOW EXISTING |
| | ABOVE GROUND GREASE INTERCEPTOR IN THE SAME ROOM. |
| | PLEASE NOTE THAT PER FBC PL 1003.2, WASTES THAT DO NOT |
| | REQUIRE TREATMENT OR SEPARATION SHALL NOT BE DISCHARGED |
| | INTO ANY INTERCEPTOR OR SEPARATOR. |
| | |
| | 2.PER WPB FBC 107.2.1, PROVIDE NOTE ON S1-2 "SHOWER |
| | BATHROOM AND HALF BATH ARE EXISTING (SEE CLOSED PERMIT |
| | 13090363/EXPIRED PERMIT 11050468)." |
| | |
| | 3.PER WPB FBC 107.2.1, PROVIDE SANITARY RISER DIAGRAM |
| | FOR NEW THREE COMPARTMENT SINK AT THE KAVA BAR. |
| | |
| | 4.PER WPB FBC 107.2.1, PROVIDE WATER RISER DIAGRAM FOR |
| | NEW THREE COMPARTMENT SINK AT THE KAVA BAR. |
| | |
| | 5.PER WPB FBC 107.2.1, ON S1-2 FLOOR PLAN PROVIDE WATER |
| | AND SANITARY PIPE ROUTING TO EXISTING PIPING SYSTEMS |
| | FOR NEW THREE COMPARTMENT SINK AT THE KAVA BAR. |
| | |
| | 6. AS PREVIOUSLY REQUESTED, PROVIDE DETAIL OF WATER |
| | HEATER SHOWING HEATER W/STORAGE CAPACITY, PIPING |
| | INCLUDING CW, HW, VALVES (INCLUDING VACUUM RELIEF VALVE |
| | IF APPLICABLE FBC PL 504.2) , THERMAL EXPANSION CONTROL |
| | DEVICE (INCLUDING SIZE), T&P DISCHARGE (INCLUDING |
| | TERMINATION) AND WATER HEATER PAN AND DRAIN (INCLUDING |
| | TERMINATION) PER WPB FPC 107.2.1; COMPLY WITH FBC PL |
| | 607.3, 503.1, 504.1, 504.4, 504.4.1, 504.5, 504.6, |
| | 504.7, 504.7.1 AND 504.7.2. WATER HEATER SHALL CONFORM |
| | TO FBC EC TABLE C404.2 |
| | PER THE GENERAL CONTRACTOR, THE WATER HEATER IS AN |
| | EXISTING ELECTRIC WATER HEATER RHEEM MODEL # 81SV30D-B |
| | 240V/3500KW NON SIMULTANEOUS 30 GALLON STORAGE TYPE; |
| | SERIAL # 0497B25563 MANUFACTURED APRIL 1997. SHOW |
| | COMPLIANCE WITH FBC EC TABLE C404.2. PLEASE NOTE, THE |
| | SUBMITTED MANUFACTURER?S SPECIFICATION SHEETS DO NOT |
| | INCLUDE THIS WATER HEATER AS IT HAS APPARENTLY BEEN |
| | DISCONTINUED. IF THE WATER HEATER IS OUT OF COMPLIANCE, |
| | IT SHALL BE REPLACED. |
| | |
| | 7.REGARDING THE NOTE ON S1-1 "DRINKING FOUNTAIN HAS |
| | BEEN ELIMINATED, SHOULD A CLIENT OR PATRON NEED A GLASS |
| | OF WATER, THEY MAY ASK THE BARTENDER FOR ONE", PLEASE |
| | BE ADVISED THAT FBC PL 410.4 STATES " WHERE RESTAURANTS |
| | PROVIDE DRINKING WATER IN A CONTAINER FREE OF CHARGE, |
| | DRINKING FOUNTAINS SHALL NOT BE REQUIRED IN THOSE |
| | RESTAURANTS"; THE NEW OCCUPANCY IS M-MERCANTILE. IN |
| | ORDER FOR THIS RULE TO BE APPLIED AN A2 OCCUPANCY WHICH |
| | INCLUDES RESTAURANTS, BARS, ETC., WOULD ALLOW THIS RULE |
| | TO BE USED. AT THIS TIME, A DRINKING FOUNTAIN |
| | (BI-LEVEL) IS STILL REQUIRED WITH AN ALCOVE TO COMPLY |
| | WITH FBC ACC 307.2. |
| | |
| | 8.PROVIDE SPECIFICATION FOR PIPING MATERIAL AND HOT |
| | WATER INSULATION. PARTIALLY COMPLIED; STILL NEED PIPING |
| | MATERIAL. |
| | |
| | 9.AGAIN: THE SHOWER IS NOT BEING USED. PER WPB FBC |
| | 107.2.1, PROVIDE DETAILS ON DECOMMISSIONING OF THE |
| | UNIT, INCLUDING BUT NOT LIMITED TO CAPPING THE DRAIN TO |
| | PREVENT SEWER GAS FROM ENTERING THE BUILDING DUE TO |
| | TRAP EVAPORATION. TO BE CLEAR, PROVIDE NOTE ON THE |
| | PLAN. IT IS NOT ENOUGH TO NOTE ON RESPONSE LETTER AS |
| | THE INSPECTOR LOOKS AT THE PLANS WHEN MAKING |
| | INSPECTION. |
| | ADDITIONALLY, THERE IS STILL NO SIDE WALL INDICATED FOR |
| | THE WATER CLOSET AS REQUIRED BY FBC ACC 604.2. PER WPB |
| | FBC 107.2.1 PROVIDE ON THE PLANS THE REQUIRED SIDE |
| | WALL. |
| | |
| | 10.AS NOTED IN THE LAST REVIEW,2017 FBC-B 1210.2.2. |
| | WALLS & PARTITIONS. THIS COMMENT IS A RESULT OF THE |
| | BUILDING OFFICIAL INTERPRETATION. IN RESTROOMS EPOXY |
| | PAINT IS NO LONGER CONSIDERED A SMOOTH HARD, |
| | NON-ABSORBENT SURFACE. |
| | WALLS & PARTITIONS WITHIN 2 FEET OF SERVICE SINKS, |
| | URINALS, AND WATER CLOSETS SHALL HAVE A SMOOTH, HARD, |
| | NON-ABSORBENT SURFACE TO A HEIGHT OF NOT LESS THAN 4 |
| | FEET ABOVE THE FLOOR, EXCEPT FOR STRUCTURAL ELEMENTS, |
| | THE MATERIAL USED IN SUCH WALLS SHALL BE OF A TYPE THAT |
| | IS NOT ADVERSELY AFFECTED BY MOISTURE. |
| | PER WPB FBC 107.2.1, PROVIDE NOTE ON PLANS REQUIRING |
| | WALLS AND PARTITIONS WITHIN 2 FEET OF SERVICE SINKS, |
| | URINALS, AND WATER CLOSETS SHALL HAVE A SMOOTH, HARD, |
| | NON-ABSORBENT SURFACE TO A HEIGHT OF NOT LESS THAN 4 |
| | FEET ABOVE THE FLOOR, EXCEPT FOR STRUCTURAL ELEMENTS, |
| | THE MATERIAL USED IN SUCH WALLS SHALL BE OF A TYPE THAT |
| | IS NOT ADVERSELY AFFECTED BY MOISTURE PER FBC 1210.2.2 |
| | AND SPECIFICALLY NOTE THAT PAINT OR EPOXY IS NOT |
| | ACCEPTABLE. |
| | |
| | 11. AGAIN: PER WPB FBC 107.2.1, SHOW HOW TEMPERED WATER |
| | IS SUPPLIED TO LAVATORIES. SHOW COMPLIANCE WITH FBC PL |
| | 607.1 AND 416.5; ADDED COMMENT: DEVICES SHALL CONFORM |
| | TO ASSE 1070. |
| | |
| | 12.THIS COMMENT HAS BEEN ACKNOWLEDGED IN THE RESPONSE |
| | LETTER: AS THIS PERMIT IS AFTER THE FACT, AT THE |
| | PLUMBING INSPECTOR'S DISCRETION, SHOW THAT ANY EXISTING |
| | PLUMBING INFRASTRUCTURE, INCLUSIVE OF PIPING, PLUMBING |
| | FIXTURES AND APPLIANCES SHOWN ON THE DEMOLITION PLAN, |
| | IS CODE COMPLIANT. THIS MAY REQUIRE PROVIDING |
| | DOCUMENTATION OF, OPENING OF WALLS AND FLOORS, PRESSURE |
| | TESTS, VIDEO CAM OF BURIED SANITARY, ETC., AS |
| | DETERMINED BY THE PLUMBING INSPECTOR. PLEASE CALL TIM |
| | LARGE AT 561-805-6692 FOR ADDITIONAL INFORMATION AND/OR |
| | CLARIFICATION |
| | |
| | |
| | A COMPREHENSIVE REVIEW COULD NOT BE ACCOMPLISHED AT |
| | THIS TIME. PLEASE RESUBMIT CLEARLY LEGIBLE PLANS AND A |
| | RESPONSE NARRATIVE ADDRESSING THE PLUMBING COMMENTS |
| | FROM THE PREVIOUS REVIEW. |
| | |
| | END OF COMMENTS. |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING |
| | EACH ITEM ALONG WITH THE CITY RE-SUBMITTAL FORM. |
| | PLEASE, ADDITIONALLY, INSERT CORRECTED PAGES INTO TO |
| | SUBMITTAL AND REMOVE OR VOID THE PREVIOUSLY REVIEWED |
| | SHEETS. |
| | ALL PLANS TO BE DIGITALLY SIGNED AND SEALED BY THE |
| | DESIGNER IN ACCORDANCE WITH FAC AND FS. |
| | |
| | |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | EMAIL [email protected] |
| | PHONE 561-246-0882 MOBILE |
| | |
| | 20040980 2417 SPRUCE AVE |
| | |