| 2020-09-21 15:16:46 | THERE WERE SEVERAL COMMENTS THANK WERE NOT ADDRESSED |
| | ABD ARE RESUBMITTED BELOW: |
| | |
| | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | |
| | |
| | 2) THERE ARE NO INDICATIONS OF EXIT SIGNS |
| | |
| | PLEASE PROVIDE. |
| | |
| | |
| | 3) THERE ARE NO INDICATIONS OF DOOR HARDWARE/ LOCKS ON |
| | THE DOORS. |
| | |
| | PER NFPA 101, CH 7, MEANS OF EGRESS |
| | |
| | 7.2.1.5 LOCKS, LATCHES, AND ALARM DEVICES. |
| | |
| | 7.2.1.5.1 DOOR LEAVES SHALL BE ARRANGED TO BE OPENED |
| | READILY FROM |
| | THE EGRESS SIDE WHENEVER THE BUILDING IS OCCUPIED. |
| | 7.2.1.5.2* THE REQUIREMENT OF 7.2.1.5.1 SHALL NOT APPLY |
| | TO DOOR |
| | LEAVES OF LISTED FIRE DOOR ASSEMBLIES AFTER EXPOSURE TO |
| | ELEVATED |
| | TEMPERATURE IN ACCORDANCE WITH THE LISTING, BASED ON |
| | LABORATORY |
| | FIRE TEST PROCEDURES. |
| | 7.2.1.5.3 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE |
| | OF A KEY, A |
| | TOOL, OR SPECIAL KNOWLEDGE OR EFFORT FOR OPERATION FROM |
| | THE EGRESS |
| | SIDE. |
| | 7.2.1.5.4 THE REQUIREMENTS OF 7.2.1.5.1 AND 7.2.1.5.3 |
| | SHALL NOT |
| | APPLY WHERE OTHERWISE PROVIDED IN CHAPTERS 18 THROUGH |
| | 23. |
| | 7.2.1.5.5 KEY-OPERATED LOCKS. |
| | 7.2.1.5.5.1* EXTERIOR DOOR ASSEMBLIES SHALL BE |
| | PERMITTED TO HAVE |
| | KEY-OPERATED LOCKS FROM THE EGRESS SIDE, PROVIDED THAT |
| | ALL OF THE |
| | FOLLOWING CRITERIA ARE MET: |
| | (1) THIS ALTERNATIVE IS PERMITTED IN CHAPTERS 11 |
| | THROUGH 43 FOR |
| | THE SPECIFIC OCCUPANCY. |
| | (2) A READILY VISIBLE, DURABLE SIGN IN LETTERS NOT LESS |
| | THAN 1 IN. |
| | (25 MM) HIGH ON A CONTRASTING BACKGROUND THAT READS AS |
| | FOLLOWS IS LOCATED ON OR ADJACENT TO THE DOOR LEAF: |
| | THIS |
| | DOOR TO REMAIN UNLOCKED WHEN THE |
| | BUILDING IS OCCUPIED. |
| | (3) THE LOCKING DEVICE IS OF A TYPE THAT IS READILY |
| | DISTINGUISHABLE |
| | AS LOCKED. |
| | (4) A KEY IS IMMEDIATELY AVAILABLE TO ANY OCCUPANT |
| | INSIDE THE |
| | BUILDING WHEN IT IS LOCKED. |
| | |
| | PLEASE PROIDE DETAILS IN COMPLIANCE |
| | |
| | |
| | |
| | 4) THERE ARE NO DETAILS REGARDING THE CABINET |
| | STRUCTURE. |
| | |
| | PLEASE PROVIDE HEIGHT/WIDTH, DOORS, ETC AND THE PURPOSE |
| | THIS STRUCTURE SERVES. |
| | |
| | |
| | |
| | 5) THERE APPEARS TO BE STOVE LOCATED IN THE REAR AREA. |
| | PLEASE CONFIRM AND WHAT IT'S PURPOSE IS AND ITS HOOD |
| | AND FIRE SUPRESSION SYSTEM. |
| | |
| | RESIDENTIAL STOVES SHOULD NOT BE LOCATED IN CERTAIN |
| | OCCUPANCIES, BASED ON HOW THEY ARE USED AND HOW THEY |
| | ARE PROTECTED. |
| | |
| | PLEASE PROVIDE DETAILS OR REMOVE. |
| | |
| | |
| | |
| | NEW COMMENT: |
| | |
| | 1) THE EXIT FROM THE KITCHEN GOES THROUGH THE STORAGE |
| | AREA. |
| | |
| | PER NFPA 101 , CH 7 MEANS OF EGRESS |
| | |
| | 7.5.2 IMPEDIMENTS TO EGRESS. SEE ALSO 7.1.9 AND |
| | 7.2.1.5. |
| | 7.5.2.1* ACCESS TO AN EXIT SHALL NOT BE THROUGH |
| | KITCHENS, |
| | STOREROOMS OTHER THAN AS PROVIDED IN CHAPTERS 36 AND |
| | 37, |
| | RESTROOMS, CLOSETS, BEDROOMS OR SIMILAR SPACES, OR |
| | OTHER ROOMS OR |
| | SPACES SUBJECT TO LOCKING, UNLESS PASSAGE THROUGH SUCH |
| | ROOMS OR |
| | SPACES IS PERMITTED FOR THE OCCUPANCY BY CHAPTER 18, |
| | 19, 22, OR 23. |
| | |
| | 7.5.1.6 EXIT ACCESS FROM ROOMS OR SPACES SHALL BE |
| | PERMITTED TO BE |
| | THROUGH ADJOINING OR INTERVENING ROOMS OR AREAS, |
| | PROVIDED THAT SUCH |
| | ROOMS OR AREAS ARE ACCESSORY TO THE AREA SERVED. |
| | FOYERS, LOBBIES, AND |
| | RECEPTION ROOMS CONSTRUCTED AS REQUIRED FOR CORRIDORS |
| | SHALL NOT BE |
| | CONSTRUED AS INTERVENING ROOMS. EXIT ACCESS SHALL BE |
| | ARRANGED SO |
| | THAT IT IS NOT NECESSARY TO PASS THROUGH ANY AREA |
| | IDENTIFIED UNDER |
| | PROTECTION FROM HAZARDS IN CHAPTERS 11 THROUGH 43. |
| | |
| | THE KITCHEN EXIT CAN PASS THROUGH TO THE FRONT DOOR. |
| | |
| | |
| | |
| | 6) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | 7) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |