| 2020-06-22 08:49:02 | PLAN REVIEW - ELECTRICAL | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | PLANS EXAMINER BUILDING - PX3169 | | | PLANS EXAMINER 1&2 FAMILY - SFP306 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | CODES IN EFFECT: | | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | | | | 1ST REVIEW | | | | | | RESULTS: DENIED | | | | | | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED | | | BELOW. | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | 1. PROVIDE NEW PANEL SCHEDULE. IDENTIFY NEW AND | | | EXISTING CIRCUTS. | | | PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED | | | CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS, | | | AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY | | | WITH CODE. NEC 210.8, 210.12, 210.19, 210.20, 215.5, | | | 408.4; WPB FBC 107.3.5; FBC RE E3706.2, E3902 | | | | | | 2. PROVIDE UPDATED LOAD CALCULATIONS. | | | PROVIDE ACCURATE LOAD CALCULATIONS INCLUDING ALL LOADS | | | FOR THE SERVICE AS WELL AS THE LOAD CALCULATIONS FOR | | | THE INDIVIDUAL PANELS. NEC 220; FBC RE 3602.2. | | | | | | | | | | | | |
|