| 2020-05-08 08:33:12 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | FAC = FLORIDA ADMINISTRATIVE CODE |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. THE APPROVED PLANS HAVE BEEN DESIGNED BY NADER |
| | GROUBAN, ARCHITECT, ANY REVISIONS TO THIS PLAN MUST BE |
| | PREPARED BY THE ARCHITECT OF RECORD. PROVIDE |
| | CORRECTION. WPB FBC 105.1 |
| | 2. RISER DIAGRAM IS NOT CODE COMPLIANT. FEEDER |
| | CONDUCTORS FROM TRANSFER SWITCH TO MCB PANELS IS SHOWN |
| | AS 2/0 WIRE TO A 200 AMP MAIN BREAKER. WIRE SIZES FROM |
| | NEC 310.15(B)(7), OR FBC RE E3603.1, CAN ONLY BE USED |
| | WHEN THE SERVICE CONDUCTOR SUPPLIES 100% OF THE LOAD. |
| | SINCE THIS IS NOT THE CASE, PROVIDE CORRECTED WIRE SIZE |
| | FROM METER CAN TO PANELS. NEC 310.15(B)(7) AND (B)(16); |
| | FBC RE E3603.1, E3705.1 |
| | 3. CONDUCTORS FROM TRANSFER SWITCH TO MAIN BREAKER |
| | PANELS ARE FEEDERS THAT ARE DOWNSTREAM FROM THE MAIN |
| | AND REQUIRE AN EQUIPMENT GROUNDING CONDUCTOR, SIZED PER |
| | CODE. PROVIDE CORRECTION. NEC 250.122; FBC RE E3704.6, |
| | 3607.3.1 |
| | 4. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT |
| | SERVICE. SHOW ON PLAN. NEC 250.94; FBC RE E3609.3 |
| | |
| | |
| | |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH |
| | ITEM ALONG WITH THE CITY RESUBMITTAL FORM. |
| | ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL |
| | SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS. |
| | ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD |
| | REMAIN IN PACKAGE AND BE MARKED OLD SHEETS. |
| | |