| 2020-04-28 15:48:09 | ROOFING | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected]. | | | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | | 1) PLEASE PROVIDE SIGNED AND SEALED ADDITIONAL | | | ATTACHMENT DETAILS FROM AN ARCHITECT OR ENGINEER FOR | | | ROOF WIND ZONES 3 THAT REQUIRE A HIGHER WIND PRESSURE | | | THAN THE MAXIMUM SHOWN FOR THE ROOFING SYSTEM CIRCLED | | | ON THE PRODUCT APPROVAL (-82.5) EXPOSURE "C" REQUIRES | | | WIND ZONE 3 AT (-95.7). | | | |
|