2020-07-08 07:13:14CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 20040922 5503 N FLAGLER DR
  
 2ND REVIEW
  
 GAS COMMENTS: DENIED
 A PLUMBING PERMIT AND PLAN APPEARS TO BE REQUIRED FOR A
 COMPLETE INSTALLATION. PLEASE PROVIDE A PERMIT
 APPLICATION NUMBER INDICATING THE REQUIRED PLUMBING
 WORK.
 THE TANKLESS WATER HEATER REQUIRES 120V ELECTRIC FOR
 IGNITION. AN ELECTRICAL PERMIT AND PLAN IS REQUIRED FOR
 ANY NEW ELECTRICAL WORK.
  
 1. PLEASE HAVE A SIGNATURE ON THE HOUSE PLAN #14 AS
 WELL AS THE ISOMETRIC DRAWING BY THE PERSON DESIGNING
 THE SYSTEM, PER FAC 61G15-23.001, FS 471 PER WPB FBC
 107.2.1.
 2. REGARDING HOUSE PLAN #14, PER WPB FBC 107.2.1, SHOW
 LOCATION OF THE METER. SHOW VERTICAL AND HORIZONTAL
 ROUTING OF PIPE FROM METER TO THE TANKLESS WATER
 HEATER. INDICATE UNDERGROUND PIPING.
 3. NEW COMMENT: PER WPB FBC 107.2.1, SUBMIT
 MANUFACTURER, MANUFACTURER?S SPECIFICATION AND
 INSTALLATION GUIDE FOR CSST TUBING. VERTICAL PIPING AT
 EXTERIOR WALL AND AT METER IS INDICATED AS CSST. IS
 THIS PIPING EXPOSED ON THE EXTERIOR? CLARIFY. PROVIDE
 PROTECTION OF PIPING AS REQUIRED IN THE MANUFACTURER?S
 INSTALLATION GUIDE OR SPECIFY AND INSTALL SCHEDULE 40
 STEEL PIPE FOR THE EXPOSED VERTICAL PIPING AND PROVIDE
 TABLE FOR THE SAME. MANUFACTURER?S INSTALLATION GUIDE
 SHALL BE ON SITE FOR ALL INSPECTIONS.
 4. RESPONSE LETTER STATES THIS IS A 2PSI SYSTEM. THE
 REGULATOR DOWNSTREAM OF THE METER ACCORDING TO
 SUBMITTAL IS A MP REGULATOR GOING FROM 2 PSI TO LESS
 THAN 2PSI. PER WPB FBC 107.2.1, INDICATE ON THE PLAN ON
 THE PLAN THE SYSTEM THAT IS 2PSI AND THE PORTION WHICH
 IS LESS THAN 2 PSI. PROVIDE MATERIAL SPEC FOR 2PSI
 PIPING, MAXIMUM LENGTH OF 2 PSI FROM METER TO
 REGULATOR, TABLE AND SIZING.
 5. REGARDING ISOMETRIC DRAWING, THE PVC SLEEVE TURNS UP
 AND IS VENTED AT THE METER LOCATION. AT THE HOUSE IT
 APPEARS TO DEAD END HORIZONTALLY. PER WPB FBC 107.2.1,
 CLARIFY.
 6. REGARDING ISOMETRIC DRAWING, A LISTED SHUTOFF VALVE
 SHALL BE INSTALLED AHEAD OF, NOT DOWNSTREAM OF THE MP
 REGULATOR PER FBC RES G2420.4
 7. PER WPB FBC 107.2.1, RESUBMIT MANUFACTURER?S
 SPECIFICATION FOR THE TANKLESS WATER HEATER. IDENTIFY
 ON THE MANUFACTURER?S SPECIFICATION THE MANUFACTURER?S
 MODEL NUMBER OF THE UNIT BEING PROVIDED. MANUFACTURER?S
 SPECIFICATION SHALL BE ON SITE FOR INSPECTION. GAS
 APPLIANCE SHALL BE LISTED AND LABELED. THE INSTALLATION
 MANUALS FOR ALL GAS APPLIANCES/EQUIPMENT SHALL BE
 ONSITE AT THE TIME OF INSPECTION PER THE 2017 FBC RES.
 SEC. G2413.2 AND G2404.3.
 8. PLEASE PROVIDE AN UPDATED TABLE, TWO COPIES OF THE
 SIZING TABLES USED IN THE DESIGN FOR THE GAS SYSTEM OR
 PLACE A NOTE ON BOTH SETS OF PLANS LISTING THE SIZING
 TABLES FROM GAS CODES OR ANOTHER STANDARD THAT WERE
 USED IN THE DESIGN OF THIS SYSTEM PER THE 2017 FBC RES.
 SEC. G2413.3. TO BE CLEAR, THIS APPLIES TO 2PSI AND
 LESS THAN 2PSI AND FOR EACH MATERIAL
 9. SUBMIT TWO COPIES OF A HOUSE PLAN SHOWING THE
 LOCATION OF THE TANKLESS WATER HEATER AND THE LOCATION
 AND DISTANCE OF ANY OPERABLE DOORS OR WINDOWS IN
 RELATION TO THE WATER HEATER. THE LOCATION OF THE WATER
 HEATER SHALL COMPLY WITH THE MANUFACTURER'S
 INSTALLATION INSTRUCTIONS. THE HOUSE PLAN CAN BE
 HAND-DRAWN PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1. INFORMATION ON CONSTRUCTION DOCUMENTS.
 10. TO BE CLEAR, TANKLESS HOT WATER PIPING, NOT
 TANKLESS WATER HEATER, MUST BE INSULATED WITH A MINIMUM
 R-3 PER THE 2017 FBC RE 403.5.3, PLEASE PUT A NOTE ON
 PLANS.
  
 END OF COMMENTS.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
 ALL PLANS TO BE SIGNED AND SEALED BY THE DESIGNER AS
 REQUIRED BY FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-246-0882 MOBILE
  
 20040922 5503 N FLAGLER DR
  
  
2020-07-07 11:14:36JERALD SMITH