| 2020-04-29 07:54:32 | 04/29/30 1ST PLUMBING/GAS REVIEW **DENIED** WITH |
| | COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. PLEASE HAVE A SIGNATURE ON THE ISOMETRIC DRAWING OF |
| | THE PERSON DESIGNING THE SYSTEM, NOT IN ACCORDANCE WITH |
| | FLORIDA ADMINISTRATIVE CODE 61G15-23.001, FLORIDA |
| | STATUTE 471 PER THE WPB AMENDMENTS TO THE FBC SEC. |
| | 107.1 GENERAL. |
| | |
| | 2. TYPE OF GAS (LP OR NATURAL) PER THE WPB AMENDMENTS |
| | TO THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. |
| | |
| | 3. INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM |
| | ON THE PLAN PER 2017 FBC RES. SEC. G2413.2. |
| | |
| | 4. PLEASE SUBMIT MANUFACTURES SPECIFICATION FOR |
| | TANKLESS UNIT AND MOST TANKLESS UNIT CALL FOR 10.5" |
| | WATER COLUMN AND THE SERVICE METER DISCHARGES ARE A 12" |
| | WATER COLUMN REQUIRING A REGULATOR FOR THIS UNIT AS PER |
| | MANUFACTURER'S SPECIFICATION PER THE WPB AMENDMENTS TO |
| | THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. |
| | |
| | 5. SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE |
| | PRESSURE REGULATORS. REGULATORS INSTALLED ON THE |
| | EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR |
| | INSTALLATION PER THE 2017 FBC RES. SEC. G2421.1. |
| | |
| | 6. GAS APPLIANCES SHALL BE LISTED AND LABELED. THE |
| | INSTALLATION MANUALS FOR ALL GAS APPLIANCES/EQUIPMENT |
| | SHALL BE ONSITE AT THE TIME OF INSPECTION PER THE 2017 |
| | FBC RES. SEC. G2413.2 AND G2404.3. |
| | |
| | 7. SUBMIT MANUFACTURER'S SPECIFICATION |
| | SHEETS/INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO |
| | VERIFY COMPLIANCE WITH 2017 FBC RES. SEC. G2408.1, |
| | (RANGE AND BBQ). |
| | |
| | 8. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE 2017 |
| | FBC RES. SEC. G2407.1 AND G2439.4 (RANGE). |
| | |
| | 9. PLEASE PROVIDE AN UPDATED TABLE, TWO COPIES OF THE |
| | SIZING TABLE USED IN THE DESIGN FOR THE GAS SYSTEM OR |
| | PLACE A NOTE ON BOTH SETS OF PLANS LISTING THE SIZING |
| | TABLES FROM GAS CODES OR ANOTHER STANDARD THAT WERE |
| | USED IN THE DESIGN OF THIS SYSTEM PER THE 2017 FBC RES. |
| | SEC. G2413.3. |
| | |
| | 10. INDICATE ON THE PLAN IF THE GRILL IS LOCATED UNDER |
| | A ROOF PER THE WPB AMENDMENTS TO FBC SEC. 107.2.1. |
| | |
| | 11. IF GRILL IS UNDER COVERED PATIO, PLEASE PROVIDE |
| | MANUFACTURES RECOMMENDATION FOR A VENTILATION HOOD PER |
| | THE 2017 FBC RES. SEC. G2408. |
| | 1. |
| | 12. PLEASE SHOW ON ISOMETRIC ALL SHUT OFF VALVES, DRIP |
| | LEG UNIONS IN FRONT OF REGULATOR 1" OF EITHER SIDE PER |
| | THE 2017 FBC RES. SEC G2421.2. |
| | |
| | 13. THERE ARE SECTIONS OF PRINTING ON THE GAS RISER |
| | DRAWING THAT ARE ILLEGIBLE. SUBMIT A CLEAR AND LEGIBLE |
| | SHEET THAT REFLECTS THE SCOPE OF WORK BEING DONE PER |
| | THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1. INFORMATION |
| | ON CONSTRUCTION DOCUMENTS. |
| | |
| | 14. SUBMIT TWO COPIES OF A HOUSE PLAN SHOWING THE |
| | LOCATION OF THE TANKLESS WATER HEATER AND THE LOCATION |
| | AND DISTANCE OF ANY OPERABLE DOORS OR WINDOWS IN |
| | RELATION TO THE WATER HEATER. THE LOCATION OF THE WATER |
| | HEATER SHALL COMPLY WITH THE MANUFACTURER'S |
| | INSTALLATION INSTRUCTIONS. THE HOUSE PLAN CAN BE |
| | HAND-DRAWN PER THE WPB AMENDMENTS TO THE FBC SEC. |
| | 107.2.1. INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 15. TANKLESS HOT WATER MUST BE INSULATED WITH A MINIMUM |
| | R-3 PER THE 2017 FBC RE 403.5.3, PLEASE PUT A NOT ON |
| | PLANS. |
| | |
| | 16. THE CLAIMED VALUE APPEARS TO BE UNDERESTIMATED ON |
| | THE APPLICATION, PLEASE PROVIDE A BONA FIDE SIGNED |
| | CONTRACT PER THE WPB AMENDMENTS TO THE FBC 109.3. |
| | BUILDING PERMITS VALUATIONS. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | LUIS A. CRESPO |
| | PLUMBING INSPECTOR / |
| | PLUMBING PLAN REVIEW |
| | AVAILABLE FROM 1:00 PM TO 4:00 PM |
| | [email protected] |
| | 561-805-6720 |
| | |