| 2020-06-16 13:55:06 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | FAC = FLORIDA ADMINISTRATIVE CODE |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. RECEPTACLES INSTALLED TO SERVE THE COUNTER TOP IN |
| | KITCHEN, INCLUDING THE ISLAND, REQUIRE GFCI PROTECTION. |
| | SOME AREAS REQUIRE AFCI AND GFCI PROTECTION. PROVIDE |
| | CORRECTION. NEC 210.8, 210.12 |
| | 2. PROVIDE LAYOUT OF EXISTING RECEPTACLE OUTLETS IN |
| | KITCHEN TO CONFIRM CODE COMPLIANCE. WPB FBC 107.2.1 |
| | 3. LOAD CALCULATION USES 240 VOLT FOR THE CALCULATION. |
| | MOST BUIDLINGS OF THIS TYPE HAVE A 208 VOLT 3 PHASE |
| | SYSTEM. PROVIDE CLARIFICATIOIN AND/OR CORRECTION FOR |
| | LOAD CALCULATION AS NEEDED. NEC 110.4, 220.5 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH |
| | ITEM ALONG WITH THE CITY RESUBMITTAL FORM. |
| | ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL |
| | SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS. |
| | ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD |
| | REMAIN IN PACKAGE AND BE MARKED OLD SHEETS. |
| | |