Plan Review Notes
Plan Review Notes For Permit 20040909
Permit Number 20040909
Review Stop B
Sequence Number 2
Notes
Date Text
2020-06-29 08:38:55PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW: THE COMMENT FROM
 THE FIRST REVIEW WAS NOT ADDRESSED.
  
 1) THE PROJECT IS LOCATED IN EXPOSURE C WITH A 170MPH
 VULT WINDSPEED. NO MEAN ROOF HEIGHT WAS PROVIDED. THE
 PROPERTY APPRAISER WEBSITE SHOWS THIS AS A TWO STORY
 STRUCTURE. ROOF ZONE 3 WITH A 20' ROOF HEIGHT HAS A
 -102 PSF UPLIFT PRESSURE. IF THE ROOF HEIGHT IS MORE
 THAN 20 FEET THE UPLIFT PRESSURE INCREASES. THE MAXIMUM
 DESIGN PRESSURE FOR THE W-207 SYSTEM THAT YOU SELECTED
 FROM FL1654 HAS A MAXIMUM DESIGN PRESSURE OF -90 PSF.
 SELECT A SYSTEM WITH AN ADEQUATE DESIGN PRESSURE.