| Plan Review Notes For Permit 20040909 |
| Permit Number |
20040909 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-05-28 08:20:04 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE PROJECT IS LOCATED IN EXPOSURE C WITH A 170MPH | | | VULT WINDSPEED. NO MEAN ROOF HEIGHT WAS PROVIDED. THE | | | PROPERTY APPRAISER WEBSITE SHOWS THIS AS A TWO STORY | | | STRUCTURE. ROOF ZONE 3 WITH A 20' ROOF HEIGHT HAS A | | | -102 PSF UPLIFT PRESSURE. IF THE ROOF HEIGHT IS MORE | | | THAN 20 FEET THE UPLIFT PRESSURE INCREASES. THE MAXIMUM | | | DESIGN PRESSURE FOR THE W-207 SYSTEM THAT YOU SELECTED | | | FROM FL1654 HAS A MAXIMUM DESIGN PRESSURE OF -90 PSF. | | | SELECT A SYSTEM WITH AN ADEQUATE DESIGN PRESSURE. |
|